Plan Review Details - Permit 22060005
Plan Review Stops For Permit 22060005
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-07-25 Cont ID  
Sent By dbattles Date 2022-07-25 Time 12:51 Rev Time 0.00
Received By dbattles Date 2022-07-25 Time 12:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By shill Date 2022-07-19 Time 14:55 Rev Time 0.00
Received By shill Date 2022-07-19 Time 14:55 Sent To  
Notes
2022-07-19 14:56:26****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC107, PROVIDE A PLAN SHOWING LOCATION OF PROPOSED
 INSTALLATION.
  
 2. PROVIDE THE FOLLOWING TEST REPORTS FOR THE PROPOSED
 UNDERLAYMENT (FLOOR MUFFLER SPEC SHEET WAS UPLOADED),
 STC, IIC, FLAME SPREAD:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By pleduc Date 2022-07-26 Time   Rev Time 0.00
Received By pleduc Date 2022-07-26 Time 12:05 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-06 Cont ID  
Sent By pleduc Date 2022-06-06 Time   Rev Time 0.00
Received By pleduc Date 2022-06-06 Time 12:14 Sent To  
Notes
2022-06-06 12:36:20THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT THE SPEC SHEET FOR THE ACTUAL
 PROPOSED LAMINATE FLOORING DOES NOT INDICATE A FLAME
 RATING.
  
 LMINATE FLOORING IS MANUFACTURED AROUND THE WORLD AND
 NOT ALL ARE TESTED AND MEETING LISTED AND NFPA
 STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED FINISHED
 LAMINATE FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
 I CHECKED MY RESOURCES ONLINE AND COULD NOT FIND THE
 FLAME RATING FOR THIS PRODUCT.
  
 YOU MAY NEED TO CONTACT HOMEDEPOT TO REQUEST THE
 SPECFIC MANUFACTURER'S SPEC SHEET
  
  
 2) A FLOOR PLAN WA NOT SUBMITTED TO SEPCIFICAALY
 INDICATE WHERE THE FLOORING WILL BE INSTALLED.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PALN
 INDICATING THE AREAS FOR THE PROPOSED FLOORING.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-27 Cont ID  
Sent By aoliver Date 2022-07-27 Time 07:40 Rev Time 0.00
Received By aoliver Date 2022-07-25 Time 12:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By shill Date 2022-07-19 Time 14:57 Rev Time 0.00
Received By shill Date 2022-06-03 Time 10:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By shill Date 2022-07-19 Time 14:56 Rev Time 0.00
Received By shill Date 2022-07-19 Time 14:56 Sent To  
Notes
***NONE***