| Plan Review Stops For Permit 22051488 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-07-15 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-07-15 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2022-07-15 10:48:24 | SPOKE WITH OWNER REQUESTED TO RETIRE ALL THE UNIT | | | ADDRESSES, THIS PERMIT IS FOR A SINGLE FAMILY HOME. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-07-08 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-07-08 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2022-07-08 14:59:44 | CURRENTLY THIS PARCEL HAS AND BUILDING HAS 3 ADDRESSES | | | 529 39TH ST, 529 39TH ST # 1 AND 529 39TH ST # 2, THE | | | PLANS APPEAR THAT THIS WILL NOW BE A SINGLE FAMILY HOME | | | AND THAT THE TWO ADDRESSES OF 529 39TH ST # 1 AND 529 | | | 39TH ST # 2 MAY BE ABLE TO RETIRE. PLEASE CONTACT | | | [email protected] OR CALL 561-805-6659 TO CONFIRM | | | THAT THOSE TWO ADDRESSES CAN BE RETIRED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-19 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-19 |
Time |
09:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-25 |
Time |
15:16 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-25 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2022-08-25 15:17:26 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | FBC R 905.3 & FRSA/TRI CLAY/CONCRETE ROOF TILE | | | INSTALLATION MANUAL/ NOA 17-0727.07, THE UNDERLAYMENT & | | | CLAY TILE INSTALLATION SHALL COMPLY WITH THIS CODE | | | SECTION, MANUAL, & NOA. | | | | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-16 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-16 |
Time |
06:09 |
Sent To |
|
|
| Notes |
| 2022-08-16 08:32:53 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | FBC R 905.3 & FRSA/TRI CLAY/CONCRETE ROOF TILE | | | INSTALLATION MANUAL/ NOA 17-0727.07, THE UNDERLAYMENT & | | | CLAY TILE INSTALLATION SHALL COMPLY WITH THIS CODE | | | SECTION, MANUAL, & NOA. | | | | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED. | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-25 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-25 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2022-07-25 11:28:42 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, THE PLANS ARE NOT CLEAR AS TO WHICH | | | AREAS ARE BEING RENOVATED. THE MAJORITY OF SYMBOL | | | INDICATORS HAVE BEEN BLACKED OUT ON THE FOLLOWING PLAN | | | SHEETS: SP101, SP102, A101, A102, A104, A105, A106, & | | | A107. | | | 2.) FBC R 301.2/FBC B 107.2.1, THE FOLLOWING PLAN SHEET | | | NOTES NEED TO BE CORRECTED FROM FBC CODE 2001 TO FBC R | | | 2020 AND THE WIND SPEED FROM 140MPH TO 170 VULT: S101 & | | | S102. | | | 3.) FBC B 107.3.4.1, THE COVER SHEET HAS AN AREA | | | LABELED DEFERRED SUBMITTALS BUT THERE ARE NO DEFERRED | | | SUBMITTALS LISTED. PLEASE INDICATE THE INTENDED | | | DEFERRED SUBMITTALS OR REMOVE NOTE IF THERE ARE NO | | | INTENDED DEFERRED SUBMITTALS. | | | 4.) FBC R 905.3.3, PROVIDE UNDERLAYMENT DETAILS AND | | | SUBMIT PRODUCT APPROVAL FOR CLAY TILE ROOFING | | | UNDERLAYMENT. NOTE: A ROOFING SUB-PERMIT IS REQUIRED. | | | 5.) FBC R301.2.1.2, PROVIDE DESIGN WIND LOAD PRESSURES | | | AND REQUIREMENTS FOR WINDOW AND DOOR OPENINGS ON. THIS | | | INFORMATION NEEDS TO BE ON PLAN SHEETS. THE PRODUCT | | | APPROVALS ARE ALSO REQUIRED FOR ALL WINDOWS AND DOORS | | | INCLUDING GARAGE DOOR. | | | | | | NOTE: PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL COMMENTS | | | MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY | | | REVIEWED SHEETS DETACHED. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-09-06 |
Time |
21:54 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-09-06 |
Time |
20:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-26 |
Time |
21:11 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-08-26 |
Time |
21:05 |
Sent To |
|
|
| Notes |
| 2022-08-26 21:11:12 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE RISER DIAGRAM OF EXISTING SERVICE. FBC | | | 107.2.1 | | | | | | 2. PROVIDE LOAD CALCULATION TO INCLUE ALL LOADS BOTH | | | NEW AND EXISTING. NEC 220 FBC 107.2.1 | | | | | | 3. AFCI PROTECTION REQUIRED. A NOTE ON PLAN WILL | | | SUFFICE. NEC 210.12 | | | | | | 4. TAMPERPROOF RECEPTACLES REQUIRED. A NOTE ON PLAN | | | WILL SUFFICE. NEC 406.12 | | | | | | 5. SMOKE/CO ALARMS REQUIRED PER FBC-R 314 AND 314. | | | | | | 6. PROVIDE PANEL SCHEDULE NEC 408 FBC 107.2.1 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-08-11 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-08-11 |
Time |
12:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-07-22 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-07-22 |
Time |
12:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-25 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-25 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2022-08-25 13:44:26 | PER APPLICANT'S REQUEST, GAS WAS NOT REVIEW UNDER THIS | | | PERMIT. A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR | | | THE GAS PIPING AND APPLIANCE INSTALLATIONS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-08-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-10 |
Time |
12:38 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-10 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2022-08-10 12:38:58 | 1ST REVIEW FBC-2020 FUEL GAS | | | PERMIT- 22051488 | | | 8/10/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P103: THE GAS RISER IS INCOMPLETE. PROVIDE A | | | COMPLETE GAS RISER DRAWING THAT INCLUDES ALL NEW AND | | | EXISTING GAS PIPING AND APPLIANCES AT THE RESIDENCE- | | | SECTION G2412.3 & G2412.4 FBC RES. REFER TO FBC RES. | | | CHAPTER 24 FUEL GAS- THE RISER SHALL INDICATE: | | | A) TYPE OF GAS- NATURAL OR LP. | | | B) DELIVERY PRESSURE AT THE METER. | | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | D) TYPES AND SIZES OF PIPING. | | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | | UNIONS. | | | H) OUTLET PRESSURES AT REGULATORS. | | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | K) PIPE SIZING TABLES. | | | | | | 2) P101: PROVIDE A DIRECT VENT DIAGRAM FOR THE TANKLESS | | | WATER HEATER. PLEASE SHOW THE TYPE AND SIZE OF AIR | | | INTAKE AND EXHAUST DUCTS, THE DUCT RUNS, AND | | | TERMINATION LOCATIONS- SEE G2427.1 & G2448.1 FBC RES. | | | | | | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE COOKTOP | | | AND INDICATE HOW AIR WILL BE PROVIDED SEC. G2407.1 & | | | G2447.1 FBC RES. | | | | | | 4) PROVIDE COMBUSTION/MAKEUP AIR CALCULATIONS FOR THE | | | DRYER AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. | | | G2407.1 & G2439.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-08-24 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-08-24 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-08-11 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-08-11 |
Time |
13:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-07-22 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-07-22 |
Time |
16:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-22 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-21 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-19 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-09 |
Time |
08:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-26 |
Time |
21:11 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-08-24 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-16 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-09 |
Time |
16:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-25 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-08 |
Time |
10:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-22 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-22 |
Time |
07:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-19 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-19 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2022-09-19 07:59:10 | THERE IS NOW NO DUCTWORK SHOWN ON THELATEST MECHANICAL | | | SHEET M101 BUT THERE ARE NUMBERS IN SQUARE BOXES WITH | | | NO NOTES THAT RELATE TO THESE BOXES. PLEASE PROVIDE A | | | COMPLETE MECHANICAL DESIGN FOR THIS PROJECT. FBC | | | 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-25 |
Time |
07:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-25 |
Time |
06:59 |
Sent To |
|
|
| Notes |
| 2022-08-25 07:02:53 | 1) SHEET M101: THE NOTE FOR THE LAUNDRY ROOM IS CALLING | | | FOR MAKE UP AIR BUT EF-4 IS AN EXHAUST FAN WHICH | | | REMOVES AIR FROM THE ROOM. PROVIDE A DESIGN FOR THE | | | MAKE UP AIR IF REQUIRED FOR THIS SPACE AND REMOVE THE | | | EXHAUST FAN. FBC 107.3.5 | | | | | | 2) AGAIN, PLEASE PROVIDE THE DUCT SIZES FOR THE NEW | | | DUCTWORK. FBC 107.3.5 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-12 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-12 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2022-08-12 10:23:59 | PROVIDE A MECHANICAL DRAWING THAT SHOWS THE DUCT SIZE | | | OF THE NEW DUCTWORK AND PROVIDE THE CFM'S OF THE HOOD | | | EXHAUST FAN AND THE MAKE UP AIR IF REQUIRED BY FRC | | | M1503. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-11 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-11 |
Time |
12:10 |
Sent To |
|
|
| Notes |
| 2022-07-11 12:14:11 | PROVIDE A SCOPE OF WORK FOR THE MECHANICAL DESIGN. IS | | | THE AHU BEING CHANGED OUT OR IS IT EXISTING TO STAY? IS | | | THIS MECHANICAL DESIGN USING AN ABOVE CEILING PLENUM | | | FOR THE RETURN? I SEE RETURN REGISTERS BUT NO DUCT | | | WORK. PROVIDE A COMPLETE MECHANICAL DRAWING SHOWING THE | | | RETURN DUCT WORK AND THE RETURNS FROM ALL ROOMS WITH | | | DOORS. FBC 107.2.1 | | | | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-25 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-25 |
Time |
12:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-10 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-10 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2022-08-10 12:18:17 | 2ND REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22051488 | | | 7/11/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P103: PLEASE SHOW THE SIZE OF THE MAIN HOT AND COLD | | | WATER MAIN DISTRIBUTION PIPES- SEC. P2903.1 FBC RES. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-11 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-11 |
Time |
15:17 |
Sent To |
|
|
| Notes |
| 2022-07-11 16:08:05 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22051488 | | | 7/11/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET P102: PROVIDE A SANITARY DRAINAGE AND VENT | | | ISOMETRIC DRAWING- SEC. 107.3.5.3 WPB. | | | | | | 2) P102: PROVIDE A TWO-WAY CLEANOUT AT THE INTERSECTION | | | OF THE NEW BUILDING DRAIN AND EXISTING SEWER LINE- | | | SECS. P3005.2.3 & P3005.2.8(2) FBC RES. | | | | | | 3) P101: PROVIDE AN EQUIPMENT SCHEDULE FOR THE NEW | | | TANKLESS WATER HEATER- TABLE C404.2 FBC EC. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-25 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-25 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2022-08-25 15:21:39 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ROOFING REVIEW APPROVED WITH PROVISO: | | | | | | FBC R 905.3, IN ACCORDANCE WITH NOA 17-0727.07 & THE | | | FRSA/TRI CONCRETE & CLAY TILE INSTALLATION GUIDE, | | | PLEASE IDENTIFY THE OPTION OF UNDERLAYMENT THAT WILL BE | | | USED (EXAMPLE: HOT MOP/SELF ADHERING). ALSO, IDENTIFY | | | THE METHOD OF ROOF TILE ANCHORING (EXAMPLE: MECHANICAL | | | FASTENING/FOAM ADHESIVE). THE METHODS CHOSEN MUST MEET | | | THE WIND LOAD REQUIREMENTS AS PER THE NOTED CODE | | | REQUIREMENTS. | | | | | | A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ANY ROOFING | | | WORK. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-16 |
Time |
11:19 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-16 |
Time |
06:09 |
Sent To |
|
|
| Notes |
| 2022-08-16 08:45:51 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ROOFING REVIEW DENIED: | | | | | | FBC R 905.3, IN ACCORDANCE WITH NOA 17-0727.07 & THE | | | FRSA/TRI CONCRETE & CLAY TILE INSTALLATION GUIDE, | | | PLEASE IDENTIFY THE OPTION OF UNDERLAYMENT THAT WILL BE | | | USED (EXAMPLE: HOT MOP/SELF ADHERING). ALSO, IDENTIFY | | | THE METHOD OF ROOF TILE ANCHORING (EXAMPLE: MECHANICAL | | | FASTENING/FOAM ADHESIVE). THE METHODS CHOSEN MUST MEET | | | THE WIND LOAD REQUIREMENTS AS PER THE NOTED CODE | | | REQUIREMENTS. | | | | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-25 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-25 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2022-07-25 11:31:37 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ROOF REVIEW DENIED: | | | | | | FBC R 905.3.3, PROVIDE UNDERLAYMENT DETAILS AND SUBMIT | | | PRODUCT APPROVAL FOR CLAY TILE ROOFING UNDERLAYMENT. | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
6 |
Status |
P |
Date |
2022-10-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-10-03 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-10-03 |
Time |
17:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
F |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-21 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-21 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2022-09-21 13:04:27 | SIGNATURE REVIEW DENIED: | | | | | | PLAN SHEETS A-110 THROUGH A-117 STILL NEED 3RD PARTY | | | VERIFIABLE SIGNATURES. | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-19 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-19 |
Time |
09:37 |
Sent To |
|
|
| Notes |
| 2022-09-19 10:28:31 | 4TH SIGNATURE REVIEW DENIED: | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-08-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-25 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-25 |
Time |
15:44 |
Sent To |
|
|
| Notes |
| 2022-08-25 15:45:24 | 3RD SIGNATURE REVIEW DENIED: | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-10 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-10 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-10 |
Time |
12:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-25 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-25 |
Time |
11:29 |
Sent To |
|
|
| Notes |
| 2022-07-25 11:29:35 | SIGNATURE REVIEW DENIED: | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-08-24 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-08-24 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-08-24 |
Time |
11:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-08-11 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-08-11 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2022-08-11 13:52:18 | STILL NEED SURVEY |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-07-22 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-07-22 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2022-07-22 16:26:36 | SITE PLAN REQUIRES DETAILED DIMENSIONS AND SURVEY TO BE | | | SUBMITTED. |
|
|