Plan Review Details - Permit 22051469
Plan Review Stops For Permit 22051469
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-08-22 Cont ID  
Sent By rmcphers Date 2022-08-22 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2022-08-22 Time 16:37 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-19 Cont ID  
Sent By rmcphers Date 2022-08-19 Time 11:52 Rev Time 0.00
Received By rmcphers Date 2022-08-19 Time 11:52 Sent To  
Notes
2022-08-19 11:54:45MOCK UP
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) YOU WILL NEED TO PROVIDE A COPY OF THE GLAZING
 PRODUCT APPROVAL - - - PLEASE SHOW ALL GLAZING TYPE,
 SIZE ETC. AND MULL BAR SIZE AND ALL ATTACHMENTS OR
 PROVIDE COMPLETE (FRONT PAGES AND THE INSTALLATION
 INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE PRODUCT
 APPROVALS FOR THE WINDOW AND MULLBAR.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 16:39 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 16:33 Sent To  
Notes
2022-08-02 16:39:20MOCK UP
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW ALL GLAZING TYPE, SIZE ETC. AND MULL BAR
 SIZE AND ALL ATTACHMENTS OR PROVIDE COMPLETE (FRONT
 PAGES AND THE INSTALLATION INSTRUCTIONS) MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVALS FOR THE WINDOW AND
 MULLBAR.
  
 2) PLEASE SHOW THE WIND DESIGN DATA ON THE DRAWINGS -
 FBC 1603.1.4
  
 3) DRAWING A511 NEEDS TO BE ELECTRONICALLY SIGNED BY
 THE ARCHITECT. SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By rmcphers Date 2022-07-12 Time 09:18 Rev Time 0.00
Received By rmcphers Date 2022-07-12 Time 09:18 Sent To  
Notes
2022-07-12 09:48:06NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOOR, WINDOWS,
 ROOFING SYSTEM.
  
 2) PLEASE SHOW THE BUILDING USE PER FBC CHAPTER 3
  
 3) PLEASE PROVIDE ALL FRAMING DETAILS - EXTERIOR WALLS,
 FLOOR, ROOF.
  
 4) PLEASE SHOW THE EXTERIOR WALL CLADDING DETAILS -
 PLEASE SHOW ALL ATTACHMENT (TYPE, SIZE ON CENTER
 SPACING ETC.) FBC 1403
  
 5) PLEASE PROVIDE STAIR DETAILS FBC 107
  
 6) PLEASE SHOW STAIR HAND RAIL DETAILS - ATTACHMENTS,
 HEIGHT ETC FBC 1014
  
 7) PLEASE SHOW STAIR GUARD RAIL DETAILS - ATTACHMENTS,
 HEIGHT ETC. FBC 1015
  
 8) PLEASE SHOW THE EXTERIOR DOOR LANDING - FBC 1010.1.5
 FLOOR ELEVATION.
 THERE SHALL BE A FLOOR OR LANDING ON EACH SIDE OF A
 DOOR. SUCH FLOOR OR LANDING SHALL BE AT THE SAME
 ELEVATION ON EACH SIDE OF THE DOOR. LANDINGS SHALL BE
 LEVEL EXCEPT FOR EXTERIOR LANDINGS, WHICH ARE PERMITTED
 TO HAVE A SLOPE NOT TO EXCEED 0.25 UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE).
  
 9) PLEASE SHOW THE DOOR LANDING SIZE FBC 1010.1.6
 LANDINGS AT DOORS.
 LANDINGS SHALL HAVE A WIDTH NOT LESS THAN THE WIDTH OF
 THE STAIRWAY OR THE DOOR, WHICHEVER IS GREATER. DOORS
 IN THE FULLY OPEN POSITION SHALL NOT REDUCE A REQUIRED
 DIMENSION BY MORE THAN 7 INCHES (178 MM). WHERE A
 LANDING SERVES AN OCCUPANT LOAD OF 50 OR MORE, DOORS IN
 ANY POSITION SHALL NOT REDUCE THE LANDING TO LESS THAN
 ONE-HALF ITS REQUIRED WIDTH. LANDINGS SHALL HAVE A
 LENGTH MEASURED IN THE DIRECTION OF TRAVEL OF NOT LESS
 THAN 44 INCHES (1118 MM).
  
 10) PLEASE SHOW ON THE LOCATION OF THE BLDG ON THE SITE
 PLAN (SHOW SETBACKS FROM THE PROPERTY LINES). FBC WPB
 107.2.5
  
 11) PLEASE SHOW THE WIND DESIGN DATA ON THE DRAWINGS -
 FBC 1603.1.4
  
 12) PLEASE SHOW THE LOWEST FLOOR ELEVATION - THE
 PROPERTY IS IN A FLOOD ZONE (AE 6 OR AE7) DEPENDING ON
 THE LOCATION OF THE BLDG. LOWEST FLOOR ELEVATION WILL
 NEED TO BE 2 FEET ABOVE THE FEMA BASE FLOOD ELEVATION -
 CITY ORD: NO. 4729-17 SECTION 5 SEC. 18-3 (B) 1612.4.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2022-08-04 Cont ID  
Sent By jleahy Date 2022-08-04 Time 15:54 Rev Time 0.00
Received By jleahy Date 2022-08-04 Time 15:42 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-07-14 Cont ID  
Sent By jleahy Date 2022-07-14 Time 07:23 Rev Time 0.00
Received By jleahy Date 2022-07-14 Time 07:19 Sent To  
Notes
2022-07-14 07:26:08FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL PLAN TO REVIEW.
  
 NOTED LIGHT FIXTURES SHOWN ON PLANS, PLEASE SUBMIT AN
 ELECTRICAL DRAWING SHOWING LOCATION OF POWER SOURCE AND
 BRANCH CIRCUIT WIRING. 215.5

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-12 Cont ID  
Sent By pleduc Date 2022-08-12 Time   Rev Time 0.00
Received By pleduc Date 2022-08-12 Time 10:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-26 Cont ID  
Sent By pleduc Date 2022-07-26 Time   Rev Time 0.00
Received By pleduc Date 2022-07-26 Time 11:45 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-03 Cont ID  
Sent By pleduc Date 2022-06-03 Time   Rev Time 0.00
Received By pleduc Date 2022-06-03 Time 14:37 Sent To  
Notes
2022-06-03 14:45:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE DOES NOT APPEAR TO BE AN INDICATION ON THE
 SITE PLAN OF WHERE THIS MOCK-UP WILL BE INSTALLED.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE LOCATION OF
 THE MOCK-UP ON THE SITE PLAN.
  
  
 2) IT IS ASSUMED THAT THE MOCK-UP CAN BE ENTERED AND
 EXITED; HOWEVER, THERE IS NO DETAIL INDICATED FOR THE
 STAIRS AND RAILINGS THAT MEET THE REQUIRMENTS OF NFPA
 101.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
 3) THERE IS A SWING DOOR INDICATED BUT NO
 SPECIFICATIONS DETAILS, NOR DOOR HARDWARE.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-22 Cont ID  
Sent By rmcphers Date 2022-08-22 Time 16:37 Rev Time 0.00
Received By rmcphers Date 2022-08-11 Time 07:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-10 Cont ID  
Sent By aoliver Date 2022-08-10 Time 06:47 Rev Time 0.00
Received By aoliver Date 2022-07-25 Time 11:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-14 Cont ID  
Sent By rmcphers Date 2022-07-14 Time 07:26 Rev Time 0.00
Received By jleahy Date 2022-06-01 Time 06:35 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status N Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 16:39 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 16:39 Sent To  
Notes
2022-08-02 16:40:17NOT AN ENCLOSED BUILDING

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By rmcphers Date 2022-07-12 Time 09:48 Rev Time 0.00
Received By rmcphers Date 2022-07-12 Time 09:48 Sent To  
Notes
2022-07-12 09:49:16AE 6 OR 7 DEPENDING ON BLDG. PLACEMENT.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status N Date 2022-05-31 Cont ID  
Sent By shill Date 2022-05-31 Time 08:32 Rev Time 0.00
Received By shill Date 2022-05-31 Time 08:32 Sent To  
Notes
2022-05-31 08:33:20NOT PRIVATE PROVIDER, OWNER SENT REVISED APPLICATION
 REMOVING THE PRIVATE PROVIDER DESIGNATION, PRIVATE
 PROVIDER SENT CLARIFICATION EMAIL
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 16:40 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 16:40 Sent To  
Notes
2022-08-02 16:41:14NO LONGER AN ENCLOSED BUILDING

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By rmcphers Date 2022-07-12 Time 09:57 Rev Time 0.00
Received By rmcphers Date 2022-07-12 Time 09:57 Sent To  
Notes
2022-07-12 09:57:46SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-19 Cont ID  
Sent By rmcphers Date 2022-08-19 Time 11:55 Rev Time 0.00
Received By rmcphers Date 2022-08-19 Time 11:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 16:44 Sent To  
Notes
2022-08-02 16:45:02SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A 511 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-12 Cont ID  
Sent By rmcphers Date 2022-07-12 Time 09:54 Rev Time 0.00
Received By rmcphers Date 2022-07-12 Time 09:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-08-19 Cont ID  
Sent By ckimmerl Date 2022-08-19 Time 16:20 Rev Time 0.00
Received By ckimmerl Date 2022-08-19 Time 16:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-09 Cont ID  
Sent By aaponte Date 2022-08-09 Time 10:50 Rev Time 0.00
Received By aaponte Date 2022-08-09 Time 10:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-09 Cont ID  
Sent By aaponte Date 2022-06-09 Time 14:06 Rev Time 0.00
Received By aaponte Date 2022-06-09 Time 14:06 Sent To  
Notes
2022-06-09 14:07:38PROVISO: MOCK UP TO BE CONSTRUCTED WITHIN THE FENCED IN
 CONSTRUCTION SITE.