| 2022-07-20 11:41:15 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2020 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 22051412 |
| | ADD: 525 S FLAGLER DR # GPH4 |
| | CONT: BATTEN CONSTRUCTION |
| | TEL: 561-820-00277 |
| | E-MAIL: [email protected] |
| | |
| | 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. JULY 20TH/ 2022 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A1 DEMO & PROPOSED FLOOR PLAN |
| | 1A) NEW SHOWER LOCATION AND FLOOR PENETRATION FOR |
| | SHOWER WASTE-WATER. |
| | POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS IF |
| | THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO BE |
| | REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR |
| | SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION |
| | CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 1B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| | FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| | WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| | THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| | ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| | A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| | ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| | HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| | NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| | PENETRATED. |
| | |
| | 1C) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| | A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| | AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| | MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| | ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| | RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| | FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| | INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| | THE MANUFACTURE?S RECOMMENDATIONS. |
| | |
| | 1D) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| | COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| | SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| | HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| | |
| | 2) THE DEMO AND PROPOSED FLOOR PLAN ARE SILENT WITH THE |
| | REMOVAL OF SOME WALLS IF ALL OF THE FLOOR FINISH IS TO |
| | BE REMOVED AND NEW FLOOR INSTALLED. IF A NEW FLOOR IS |
| | TO BE INSTALLED PLEASE IDENTIFY THE FINISH FLOOR |
| | MATERIAL. |
| | |
| | FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE, |
| | STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND |
| | WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND |
| | UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING |
| | STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH |
| | OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/ |
| | NO DROPPED CEILING: |
| | PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| | TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| | |
| | 2A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| | |
| | 2B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C1) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. (TILE |
| | & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED FLOOR |
| | AND SOLID DECKING WITHOUT INTERVENING AIRSPACE SHALL BE |
| | ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN |
| | 200. |
| | |
| | 2C2) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR |
| | LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT |
| | SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC |
| | 16 CFR PART 1630) OR WITH ASTM D2859. |
| | |
| | 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| | REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| | REVIEW CYCLE. |
| | |
| | |
| | MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ SEMI-RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |