Plan Review Details - Permit 22051361
Plan Review Stops For Permit 22051361
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 11:07 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 11:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-19 Cont ID  
Sent By rmcphers Date 2022-09-19 Time 11:48 Rev Time 0.00
Received By rmcphers Date 2022-09-19 Time 11:45 Sent To  
Notes
2022-09-19 11:48:23NEW OFFICE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PRODUCT APPROVALS PROVIDED FOR THE GLAZED COMPONENTS
 (GLAZING IN DOORS AND WINDOWS) DO NOT MEET IMPACT
 REQUIREMENTS - PROVIDE SHUTTER PRODUCT APPROVALS - FBC
 1609.1.2
  
 2) PLEASE PROVIDE THE FRONT PAGES FOR THE FLORIDA STATE
 PRODUCT APPROVALS - FOR THE SINGLE HUNG AND FIXED
 WINDOWS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By rmcphers Date 2022-08-29 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2022-08-29 Time 09:20 Sent To  
Notes
2022-08-29 10:31:59NEW OFFICE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE EXTERIOR WALL STUD TO FLOOR JOIST
 CONNECTION - THERE SHOULD BE A STRAP OR HURRICANE
 ANCHOR AT THE BOTTOM OF THE WALL STUD - FBC 1604.8.1
 GENERAL.
 ANCHORAGE OF THE ROOF TO WALLS AND COLUMNS, AND OF
 WALLS AND COLUMNS TO FOUNDATIONS, SHALL BE PROVIDED TO
 RESIST THE UPLIFT AND SLIDING FORCES THAT RESULT FROM
 THE APPLICATION OF THE PRESCRIBED LOADS.
  
 2) PRODUCT APPROVALS PROVIDED FOR THE GLAZED COMPONENTS
 (GLAZING IN DOORS AND WINDOWS) NEED TO MEET IMPACT
 REQUIREMENTS - OR PROVIDE SHUTTER PRODUCT APPROVALS -
 FBC 1609.1.2
  
 3) PLEASE PROVIDE THE FRONT PAGES FOR THE FLORIDA STATE
 PRODUCT APPROVALS.
  
 4) ROOF SHEATHING ATTACHMENT SHOULD BE NAILS - SEE FBC
 2304.10.1 - 8D COMMON OR DEFORMED (21/2? ? 0.131?)
 (ROOF) OR RSRS-01 (23/8? ? 0.113?) NAIL (ROOF)D

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By rmcphers Date 2022-07-21 Time 13:11 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 11:11 Sent To  
Notes
2022-07-21 11:57:26NEW OFFICE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS SHOW OCCUPANCY CLASSIFICATION TYPE AS "B" -
 DRAWING SHOWS "OFFICE" ? - BUILDING PERMIT APPLICATION
 SAYS "SHED" WHICH WOULD BE A "U" OCCUPANCY
 CLASSIFICATION - BUILDING PERMIT APPLICATION AND
 DRAWING OCCUPANCY CLASSIFICATION SHOULD MATCH.
  
 2) PLEASE SHOW AN ACCESSIBLE ENTRANCE TO THE OFFICE
 BUILDING - FBC A 206
  
 3) PLEASE SHOW WIND DESIGN DATA RISK CATEGORY II WITH
 WIND SPEEDS AT 170MPH FOR AN OFFICE BUILDING - FBC
 1604.5 AND FBC WPB SECTION 120
  
 4) PLEASE SHOW THE EXTERIOR WALL STUD TO FLOOR JOIST
 CONNECTION - FBC 1604.8
  
 5) PLEASE SHOW THE ROOF SHEATHING THICKNESS AND TYPE -
 FBC 2304.8
  
 6) PLEASE SHOW THE INSULATION TYPE - BATT INSULATION
 WILL NOT WORK WITH THE R VALUES SHOWN AND THE WIDTH OF
 THE ROOF, FLOOR AND WALL FRAMING - IT WILL BE
 COMPRESSED AND NOT GIVE THE R VALUE SHOWN. FBC ENERGY
 C303
  
 7) PLEASE PROVIDE THE PORCH DETAILS/DRAWINGS - FBC WPB
 107.2
  
 8) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS AND
 ROOFING SYSTEM. ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND MARKED APPROVED BY THE BUILDING DESIGNER
 OF RECORD FBC WPB 107.3.4

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By jleahy Date 2022-07-19 Time 15:29 Rev Time 0.00
Received By jleahy Date 2022-07-19 Time 12:48 Sent To  
Notes
2022-07-19 15:30:30NO ELECTRICAL WORK SHOWN ON PLANS JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-09-01 Cont ID  
Sent By pleduc Date 2022-09-01 Time   Rev Time 0.00
Received By pleduc Date 2022-09-01 Time 12:57 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-15 Cont ID  
Sent By pleduc Date 2022-08-15 Time   Rev Time 0.00
Received By pleduc Date 2022-08-15 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By pleduc Date 2022-05-31 Time   Rev Time 0.00
Received By pleduc Date 2022-05-31 Time 13:45 Sent To  
Notes
2022-05-31 13:52:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE APPLICATION SHEET FOR
 A SHED.
  
 THE SUBMITTED PLAN SHEET INDICATES PROPOSED OFFICE
 AREA.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE WHAT IN INTENT
 OF THIS BUILDING IS AND THE APPLICABLE OCCUPANCY
 CLASSIFICATION PER THE FLORIDA FIRE PREVENTION CODE.
  
  
 2) THERE ARE 2 SETS OF DOUBLE DOORS INDICATED BUT NO
 DOOR SCHEDULE INDICATING THE LOCKS/HARDWARE/LATCHES.
  
 ALL DOORS LOCKS/LATCHES SHALL COMPLY WITH THE
 REQUIERMENTS OF NFPA 101 OCCUPANCY CHAPTER AND NFPA 101
 CH 7 MEANS OF EGRESS.
  
 PLEASE PROVIDE THE DOOR SCHEDULE AND APPLICABLE DOOR
 HARDWARE.
  
  
  
 3) THE APPLICATION SHEET INDICATES 328 N LAKESIDE CT;
 HOWEVER, THE TITLE BLOCK OF THE SUBMITTED SHEET
 INDICATES 1700 N DIXIE HWY, PALM BEACH.
  
 PLEASE REVIEW AND CORRECT THE APPLICABLE CORRECT
 ADDRESS AND CITY.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 07:52 Rev Time 0.00
Received By medwards Date 2023-01-23 Time 08:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-12-29 Cont ID  
Sent By medwards Date 2022-12-29 Time 15:49 Rev Time 0.00
Received By medwards Date 2022-12-17 Time 18:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-11-15 Cont ID  
Sent By medwards Date 2022-11-15 Time 17:13 Rev Time 0.00
Received By medwards Date 2022-10-26 Time 15:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-19 Cont ID  
Sent By rmcphers Date 2022-09-19 Time 11:50 Rev Time 0.00
Received By rmcphers Date 2022-08-31 Time 14:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-29 Cont ID  
Sent By rmcphers Date 2022-08-29 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2022-08-12 Time 09:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-21 Cont ID  
Sent By rmcphers Date 2022-07-21 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2022-05-27 Time 09:04 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2023-01-17 Cont ID  
Sent By aoliver Date 2023-01-17 Time 16:40 Rev Time 0.00
Received By aoliver Date 2023-01-17 Time 16:40 Sent To  
Notes
2023-01-17 13:36:25RECEIPT MU-2023-002073-0000 - $654.80 PAID AO
2022-12-29 15:53:3412/29/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By rmcphers Date 2022-07-21 Time 13:11 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 13:11 Sent To  
Notes
2022-07-21 13:12:05PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 07:51 Rev Time 0.00
Received By medwards Date 2023-01-31 Time 07:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2022-12-29 Cont ID  
Sent By medwards Date 2022-12-29 Time 15:47 Rev Time 0.00
Received By medwards Date 2022-12-29 Time 15:43 Sent To  
Notes
2022-12-29 15:47:001) PLEASE REFERENCE THE 2020 FLORIDA MECHANICAL CODE
 SECTION 403.3.1.1 AND TABLE 403.3.1.1 AS WE DO NOT USE
 THE IMC.
  
 2) I DO NOT SEE THE OUTDOOR AIR CALCULATIONS REQUESTED,
 PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS BUILDING.
 FMC 403.3.1.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2022-11-15 Cont ID  
Sent By medwards Date 2022-11-15 Time 17:09 Rev Time 0.00
Received By medwards Date 2022-11-15 Time 17:08 Sent To  
Notes
2022-11-15 17:11:494TH ATTEMPT...
  
  
 PLEASE ADDRESS 1ST CYCLE REVIEW COMMENTS BELOW:
  
 PROVIDE THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND A MECHANICL DESIGN.
 THE MECHANICAL DRAWING SUBMITTED THIS CYCLE DOES NOT
 SHOW THE REQUIRED OUTDOOR AIR CALCULATION OR HOW IT
 WILL INTRODUCED INTO THE SPACE. PLEASE SUBMIT THIS WITH
 THE REQUIRED DESIGN.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-09-14 Cont ID  
Sent By medwards Date 2022-09-14 Time 06:23 Rev Time 0.00
Received By medwards Date 2022-09-14 Time 06:23 Sent To  
Notes
2022-09-14 06:24:433RD ATTEMPT TO TRY TO GET THE INFORMATION I NEED TO
 REVIEW THE MECHANICAL DESIGN OF THE OFFICE SPACE.
  
 PLEASE ADDRESS 1ST CYCLE REVIEW COMMENTS BELOW:
  
 PROVIDE THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND A MECHANICL DESIGN
 INCLUDING A MECHANICAL DRAWING FOR THIS NEW OFFICE
 STRUCTURE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-26 Cont ID  
Sent By medwards Date 2022-08-26 Time 07:12 Rev Time 0.00
Received By medwards Date 2022-08-26 Time 07:11 Sent To  
Notes
2022-08-26 07:12:34PLEASE ADDRESS 1ST CYCLE REVIEW COMMENTS BELOW:
  
 PROVIDE THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND A MECHANICL DESIGN
 INCLUDING A MECHANICAL DRAWING FOR THIS NEW OFFICE
 STRUCTURE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By medwards Date 2022-07-19 Time 08:12 Rev Time 0.00
Received By medwards Date 2022-07-19 Time 08:10 Sent To  
Notes
2022-07-19 08:12:30PROVIDE THE ENERGY CALCULATIONS, THE MECHANICAL
 EQUIPMENT SIZING CALCULATIONS AND A MECHANICL DESIGN
 INCLUDING A MECHANICAL DRAWING FOR THIS NEW OFFICE
 STRUCTURE. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By rwbrown Date 2022-07-19 Time 10:27 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-07-19 10:27:54NO PLUMBING SHOWN

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-09-19 Cont ID  
Sent By rmcphers Date 2022-09-19 Time 11:48 Rev Time 0.00
Received By rmcphers Date 2022-09-19 Time 11:48 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By rmcphers Date 2022-08-29 Time 10:32 Rev Time 0.00
Received By rmcphers Date 2022-08-29 Time 10:32 Sent To  
Notes
2022-08-29 10:32:34SEE BUILDING PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By rmcphers Date 2022-07-21 Time 11:27 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 11:27 Sent To  
Notes
2022-07-21 11:28:03SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-01-31 Cont ID  
Sent By medwards Date 2023-01-31 Time 07:52 Rev Time 0.00
Received By medwards Date 2023-01-31 Time 07:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status F Date 2022-12-29 Cont ID  
Sent By medwards Date 2022-12-29 Time 15:48 Rev Time 0.00
Received By medwards Date 2022-12-29 Time 15:48 Sent To  
Notes
2022-12-29 15:49:32THE ENGINEERS CERTIFICATE FOR THE DIGITAL SIGNATURE HAS
 EXPIRED. PLEASE UPDATE AND SUBMIT THE CORRECTED DIGITAL
 SIGNATURES ON EACH DRAWING. FS 471/481

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-11-14 Cont ID  
Sent By rmcphers Date 2022-11-14 Time 11:08 Rev Time 0.00
Received By rmcphers Date 2022-11-14 Time 11:08 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-19 Cont ID  
Sent By rmcphers Date 2022-09-19 Time 11:50 Rev Time 0.00
Received By rmcphers Date 2022-09-19 Time 11:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-29 Cont ID  
Sent By rmcphers Date 2022-08-29 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2022-08-29 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-07-21 Cont ID  
Sent By rmcphers Date 2022-07-21 Time 13:12 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 13:12 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-09-06 Cont ID  
Sent By asangele Date 2022-09-06 Time 16:37 Rev Time 0.00
Received By asangele Date 2022-09-06 Time 16:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-23 Cont ID  
Sent By asangele Date 2022-08-23 Time 12:19 Rev Time 0.00
Received By asangele Date 2022-08-23 Time 12:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By asangele Date 2022-06-03 Time 12:29 Rev Time 0.00
Received By asangele Date 2022-06-03 Time 12:29 Sent To  
Notes
***NONE***