Plan Review Details - Permit 22051346
Plan Review Stops For Permit 22051346
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-10-28 Cont ID  
Sent By rmcphers Date 2022-10-28 Time 11:50 Rev Time 0.00
Received By rmcphers Date 2022-10-28 Time 11:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-09-08 Cont ID  
Sent By rmcphers Date 2022-09-08 Time 08:24 Rev Time 0.00
Received By rmcphers Date 2022-09-08 Time 08:24 Sent To  
Notes
2022-09-08 08:24:46REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A1.1.1 SHOWS DOOR 105D IN A FIRE WALL - ON
 THE DOOR SCHEDULE - PLEASE SHOW THE HOURLY FIRE RATING
 FOR DOOR 105 D - FBC 716.5
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-16 Cont ID  
Sent By rmcphers Date 2022-08-16 Time 10:53 Rev Time 0.00
Received By rmcphers Date 2022-08-16 Time 10:53 Sent To  
Notes
2022-08-16 10:56:36REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A1.1.1 SHOWS DOOR 105D IN A FIRE WALL - ON
 THE DOOR SCHEDULE - PLEASE SHOW THE HOURLY FIRE RATING
 FOR DOOR 105 D - FBC 716.5
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-22 Cont ID  
Sent By rmcphers Date 2022-06-22 Time 16:25 Rev Time 0.00
Received By rmcphers Date 2022-06-22 Time 16:13 Sent To  
Notes
2022-06-22 16:25:14REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING ALS1.1 AND A1.1.1 SHOW AN ADDED UTILITY ROOM
 WITH A DOOR THAT APPEARS TO ENCROACH ON THE EGRESS
 WIDTH - FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 2) DOORS MARKED 105 C AND 105 D NEED TO BE SHOWN ON THE
 DOOR SCHEDULE - SIZES, FIRE RATINGS, SELF CLOSING ETC.
  
 3) DOOR 105 D SHOWS TO BE PART OF A FIRE WALL - PLEASE
 SHOW THE HOURLY FIRE RATINGS AND SELF CLOSING/LATCHING
 - FBC 716.5 AND 716.5.9
  
 4) DRAWING A1.1.1 - MAYBE THE FIRE RATED WALL IS SHOWN
 INCORRECTLY FOR THE UTILITY ROOM IN UNIT 423.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 06:25 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 06:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By pleduc Date 2022-06-03 Time   Rev Time 0.00
Received By pleduc Date 2022-06-03 Time 14:54 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By rwbrown Date 2022-06-07 Time 06:03 Rev Time 0.00
Received By rwbrown Date 2022-06-07 Time 06:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-28 Cont ID  
Sent By rmcphers Date 2022-10-28 Time 11:52 Rev Time 0.00
Received By rmcphers Date 2022-10-17 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-08 Cont ID  
Sent By rmcphers Date 2022-09-08 Time 08:26 Rev Time 0.00
Received By rmcphers Date 2022-08-25 Time 15:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-16 Cont ID  
Sent By rmcphers Date 2022-08-16 Time 10:58 Rev Time 0.00
Received By rmcphers Date 2022-08-01 Time 10:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By lmarchan Date 2022-07-19 Time 07:18 Rev Time 0.00
Received By lmarchan Date 2022-06-02 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-06-15 Cont ID  
Sent By medwards Date 2022-06-15 Time 07:09 Rev Time 0.00
Received By medwards Date 2022-06-15 Time 07:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By rwbrown Date 2022-06-07 Time 06:03 Rev Time 0.00
Received By rwbrown Date 2022-06-07 Time 06:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-10-28 Cont ID  
Sent By rmcphers Date 2022-10-28 Time 11:51 Rev Time 0.00
Received By rmcphers Date 2022-10-28 Time 11:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-08 Cont ID  
Sent By rmcphers Date 2022-09-08 Time 08:26 Rev Time 0.00
Received By rmcphers Date 2022-09-08 Time 08:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-16 Cont ID  
Sent By rmcphers Date 2022-08-16 Time 10:57 Rev Time 0.00
Received By rmcphers Date 2022-08-16 Time 10:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-22 Cont ID  
Sent By rmcphers Date 2022-06-22 Time 16:33 Rev Time 0.00
Received By rmcphers Date 2022-06-22 Time 16:33 Sent To  
Notes
2022-06-15 07:09:46MECHANICAL DIGITAL SIGNATURE APPROVED ME
  
2022-06-10 06:26:26ELECTRICAL SIGNATURE APPROVED JLEAHY

Review Stop Z ZONING
Rev No 1 Status P Date 2022-07-18 Cont ID  
Sent By eschneid Date 2022-07-18 Time 14:41 Rev Time 0.50
Received By eschneid Date 2022-07-18 Time 10:53 Sent To  
Notes
***NONE***