Plan Review Details - Permit 22051282
Plan Review Stops For Permit 22051282
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2022-06-23 Time   Rev Time 0.00
Received By aoliver Date 2022-06-21 Time 07:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-06-10 Time   Rev Time 0.00
Received By cdecoeur Date 2022-06-09 Time 09:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-06-23 Cont ID  
Sent By ccole Date 2022-06-23 Time 14:12 Rev Time 0.00
Received By ccole Date 2022-06-23 Time 07:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-10 Cont ID  
Sent By ccole Date 2022-06-10 Time 16:24 Rev Time 0.00
Received By ccole Date 2022-06-10 Time 15:47 Sent To  
Notes
2022-06-10 16:25:531ST REVIEW FBC-2020 PLUMBING/MECHANICAL REVIEW
 PERMIT- 22051282
 6/10/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE WATER METERS, VALVES, AND OTHER COMPONENT
 SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE
 BUILDING ENGINEER OR ARCHITECT OF RECORD- SEC. 107.3.4
 WPB. PLEASE RESUBMIT STAMPED COPIES.
  
 2) SHEETS P-01- P-09: INDICATE THE MAKES AND MODEL
 NUMBERS OF THE METERS AND VALVES ON THE PLAN- SEC.
 107.2.1 WPB.
  
 3) P-01- P-09: CLARIFY IF THE NEW METERS AND VALVES ARE
 BEING INSTALLED IN PLENUM SPACES, AND VERIFY THE METER
 ASSEMBLIES ARE PLENUM RATED- SEC. 602.2.1- 602.2.1.8
 FBC M.
  
 4) SUBMIT MANUFACTURER?S SPECIFICATIONS INDICATING THE
 VALVES CONFORM TO ONE OF THE STANDARDS LISTED IN TABLE
 605.7 FBC P.
  
 5) THE SUBMITTED PLANS SHALL BEAR THE PRINTED NAME,
 SIGNATURE, AND THE LICENSE NUMBER OF THE CONTRACTOR OR
 QUALIFIER WHO PREPARED THE DRAWINGS- SEC. 107.1 AND FL.
 STATUTES 471.003(2)(H) & 471.025.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-23 Cont ID  
Sent By ccole Date 2022-06-23 Time 14:12 Rev Time 0.00
Received By ccole Date 2022-06-23 Time 11:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2022-06-10 Time   Rev Time 0.00
Received By ccole Date 2022-06-10 Time 15:47 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved