| | 22051265 300 PEMBROKE PL |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | RESPONSE AND/OR CORRECTIONS IN RESPONSE TO THE FIRST |
| | REVIEW WERE NOT PROVIDED BY THE DESIGN PROFESSIONAL(S). |
| | IN ADDITION TO THE ORIGINAL COMMENTS, NEW COMMENTS HAVE |
| | BEEN ADDED. IT IS IMPORTANT THAT ALL COMMENTS ARE |
| | RESPONDED TO, AND CORRECTIONS MADE FOR APPROVAL. PLEASE |
| | BE SURE TO PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| | COMMENT, NOTING THE PLAN PAGE SHOWING THE CORRECTIONS. |
| | |
| | A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | |
| | 1. SECOND REQUEST: PLEASE NOTE FBC ACC 202.4.1, |
| | DISPROPORTIONATE COST: ALTERATIONS MADE TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO THE ALTERED AREA WILL BE |
| | DEEMED DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN |
| | THE COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO |
| | THE PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS |
| | EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF |
| | TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING |
| | AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE |
| | ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING |
| | RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, |
| | ENLARGING TOILET STALLS, INSULATING PIPES, OR |
| | INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS |
| | ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH |
| | AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT, |
| | INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT |
| | TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING |
| | AN INACCESSIBLE DRINKING FOUNTAIN. |
| | TO BE CLEAR, A RESPONSE IS REQUIRED. |
| | |
| | ***A) PER WPB FBC 107.2.1, PROVIDE DIMENSIONED PLAN AND |
| | ELEVATION VIEW OF EXISTING MEN AND WOMEN TOILET ROOMS |
| | SHOWING COMPLIANCE WITH FBC ACC CHAPTERS 2, 3 AND 6 AS |
| | FOLLOWS: |
| | *****1) THE WATER CLOSET SHALL BE POSITIONED WITH A |
| | WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE |
| | CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| | MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| | PARTITION PER FBC ACC 604.2 |
| | *****2) CLEARANCE AROUND A WATER CLOSET SHALL BE 60 |
| | INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES DEEP MINIMUM FOR WALL HUNG WATER |
| | CLOSETS AND 59 INCHES DEEP MINIMUM FOR FLOOR MOUNTED |
| | WATER CLOSETS MEASURED PERPENDICULAR TO THE REAR WALL |
| | PER FBC ACC 604.3.1 AND 604.8.1.1 |
| | *****3) THE SIDE WALL GRAB BAR SHALL BE 42 INCHES LONG |
| | MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM THE |
| | REAR WALL AND EXTENDING 54 INCHES MINIMUM FROM THE REAR |
| | WALL PER FBC ACC 604.5.1 |
| | *****4) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2 |
| | *****5) FLUSH CONTROLS SHALL BE HAND OPERATED OR |
| | AUTOMATIC. HAND OPERATED FLUSH CONTROLS SHALL COMPLY |
| | WITH 309. FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN |
| | SIDE OF THE WATER CLOSET PER FBC ACC 604.6 |
| | *****6) PER FBC ACC 604.8, TOILET PAPER DISPENSERS |
| | SHALL COMPLY WITH 309.4 AND SHALL BE 7 INCHES MINIMUM |
| | AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET |
| | MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET |
| | OF THE DISPENSER SHALL BE 15 INCHES MINIMUM AND 48 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR AND SHALL NOT BE |
| | LOCATED BEHIND GRAB BARS. |
| | *****7) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE |
| | FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 |
| | INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE |
| | SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED |
| | POSITION PER FBC ACC 604.4. |
| | *****8) PER FBC ACC 609.4, GRAB BARS SHALL BE INSTALLED |
| | IN A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE |
| | TOP (NOT THE CENTER) OF THE GRIPPING SURFACE. |
| | *****9) LAVATORIES AND SINKS SHALL BE INSTALLED WITH |
| | THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE |
| | 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER |
| | FBC ACC 606.3, ADDITIONALLY SHOW TOE AND KNEE CLEARANCE |
| | AS REQUIRED BY FBC ACC 306.2 AND 306.3 |
| | *****10) PER FBC 606.5 EXPOSED PIPES AND SURFACES. |
| | WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT. |
| | *****11) UNITS SHALL HAVE A CLEAR FLOOR OR GROUND SPACE |
| | COMPLYING WITH 305 POSITIONED FOR A FORWARD APPROACH |
| | AND CENTERED ON THE UNIT. KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED PER FBC ACC 602.2. |
| | *****12) MIRRORS LOCATED ABOVE LAVATORIES OR |
| | COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF |
| | THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. MIRRORS NOT LOCATED ABOVE |
| | LAVATORIES OR COUNTERTOPS SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 35 INCHES (890 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND PER FBC |
| | ACC 603.3. |
| | TO BE CLEAR, PLEASE CLARIFY ON PLANS THAT DIMENSION IS |
| | TO THE REFLECTING SURFACE OF THE MIRROR. |
| | *****13) SHOW TURNING SPACE COMPLYING WITH FBC ACC |
| | 304.3.1 OR 304.3.2. |
| | *****14) PER FBC 606.5 EXPOSED PIPES AND SURFACES. |
| | WATER SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS |
| | SHALL BE INSULATED OR OTHERWISE CONFIGURED TO PROTECT |
| | AGAINST CONTACT. |
| | AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED. |
| | ***B) PLEASE NOTE THE DRINKING FOUNTAIN ON PLAN SHEET |
| | A-01, P-01 AND THE REQUIREMENTS OF FBC ACC 211.1, |
| | 211.2; WHERE DRINKING FOUNTAINS ARE PROVIDED, NO FEWER |
| | THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. ONE |
| | DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| | AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.7. PER |
| | WPB FBC 107.2.1, AN ELEVATION AND PLAN DETAIL OF THE |
| | UPGRADED FIXTURE(S) IS REQUIRED. |
| | AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED. |
| | ***C) PER WPB FBC 107.2.1, PROVIDE ELEVATION AND PLAN |
| | DETAIL FOR WASHER(S) AND DRYER(S) SHOWING COMPLIANCE |
| | WITH FBC ACC 214 AND 611. TOP LOADING MACHINES SHALL |
| | HAVE THE DOOR TO THE LAUNDRY COMPARTMENT LOCATED 36 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR. FRONT LOADING |
| | MACHINES SHALL HAVE THE BOTTOM OF THE OPENING TO THE |
| | LAUNDRY COMPARTMENT LOCATED 15 INCHES MINIMUM AND 36 |
| | INCHES MAXIMUM ABOVE THE FINISH FLOOR. |
| | AS INDICATED IN FBC ACC 202.4.1, UPGRADE AS REQUIRED. |
| | ***D) COST OF SUGGESTED UPGRADES IN EXCESS OF 20% OF |
| | THE COST OF THE ALTERATION TO THE PRIMARY FUNCTION AREA |
| | SHALL BE DEEMED DISPROPORTIONATE. |
| | |
| | 2. SECOND REQUEST: WHERE SINKS ARE PROVIDED, AT LEAST 5 |
| | PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED |
| | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606 |
| | PER FBC ACC 212.3. PER WPB FBC 107.2.1, IDENTIFY |
| | ACCESSIBLE DORMITORY UNIT(S) AND PROVIDE ELEVATION AND |
| | PLAN DETAILS FOR NEW SINK SHOWING COMPLIANCE. |
| | |
| | 3. SECOND REQUEST: PER FBC ACC 213.2, WHERE BATHING |
| | ROOMS ARE PROVIDED, EACH BATHING ROOM SHALL COMPLY WITH |
| | 603. PER WPB FBC 107.2.1, IDENTIFY ACCESSIBLE DORMITORY |
| | UNIT(S) AND PROVIDE ELEVATION AND PLAN DETAILS FOR NEW |
| | BATHING ROOM(S) SHOWING COMPLIANCE WITH FBC ACC 603. |
| | NEW COMMENT: SEE FBC ACC 809.4 FOR ADDED CLARIFICATION |
| | WHICH CLEARLY INDICATES REQUIREMENTS IN RESIDENTIAL |
| | DWELLING UNIT(S) |
| | 213.3.2WATER CLOSETS. |
| | WHERE WATER CLOSETS ARE PROVIDED, AT LEAST ONE SHALL |
| | COMPLY WITH 604. |
| | 213.3.4LAVATORIES. |
| | WHERE LAVATORIES ARE PROVIDED, AT LEAST ONE SHALL |
| | COMPLY WITH 606 AND SHALL NOT BE LOCATED IN A TOILET |
| | COMPARTMENT. |
| | 213.3.5MIRRORS. |
| | WHERE MIRRORS ARE PROVIDED, AT LEAST ONE SHALL COMPLY |
| | WITH 603.3. |
| | 213.3.6BATHING FACILITIES. |
| | WHERE BATHTUBS OR SHOWERS ARE PROVIDED, AT LEAST ONE |
| | BATHTUB COMPLYING WITH 607 OR AT LEAST ONE SHOWER |
| | COMPLYING WITH 608 SHALL BE PROVIDED. |
| | |
| | 4. SECOND REQUEST: PLAN SHEET A-0/APPLICABLE CODES: PER |
| | WPB FBC 107.2.1, PLEASE ADD 2020 FLORIDA PLUMBING CODE |
| | 7TH EDITION AND 2020 FLORIDA MECHANICAL CODE 7TH |
| | EDITION TO THE LIST OF APPLICABLE CODES. |
| | |
| | 5. SECOND REQUEST: PLAN SHEET A-0/APPLICABLE CODES: PER |
| | FBC 310.4, THE OCCUPANCY FOR THIS FACILITY IS R-2 |
| | RESIDENTIAL. |
| | |
| | 6. SECOND REQUEST: PLAN SHEET A-01, A-02/CONSTRUCTION |
| | NOTE 4: PER WPB FBC 107.2.1, 107.3.5.1.3 AND 107.3.5.3, |
| | PLUMBING FIXTURE SPACING SHALL COMPLY WITH FLORIDA |
| | PLUMBING CODE 2020 7TH EDITION, NOT THE FLORIDA |
| | RESIDENTIAL CODE 2020 7TH EDITION |
| | ADDITIONALLY, AS NOTED IN COMMENT 3, COMPLY WITH FBC |
| | ACC 213.2 AND 809.4. |
| | |
| | 7. SECOND REQUEST: PER WPB FBC 107.2.1, PLEASE IDENTIFY |
| | AND TAG ALL NEW PLUMBING FIXTURES ON PLUMBING FLOOR |
| | PLANS AND ISOMETRICS. TAG AND ID SHALL MATCH PLUMBING |
| | FIXTURE SCHEDULE ON P-05. |
| | |
| | 8. SECOND REQUEST:P-05/PLUMBING NOTES: PER WPB FBC |
| | 107.2.1, REVISE THE FOLLOWING |
| | ***A) NOTES 6 & 7 "PVC DRAINAGE (DWV) SCHEDULE 40 PIPE |
| | AND FITTINGS" |
| | ***B) NOTE 13 "COPPER WATER PIPING JOINTS TO BE MADE |
| | WITH LEAD FREE SOLDER" |
| | ***C) NOTE 14 "VALVES TO BE LEAD FREE" |
| | ***D) NOTE 16 "HOT WATER PIPING TO BE INSULATED IN |
| | ACCORDANCE WITH FBC EC C404.4 (A-E) AND TABLE |
| | C403.2.10" |
| | PROVIDE A SPEC THAT COMPLIES |
| | ***E) NOTE 19 "IN ACCORDANCE WITH FBC PL 604.9, PROVIDE |
| | WATER HAMMER ARRESTORS AT EACH FIXTURE GROUP CONFORMING |
| | TO ASSE 1010" |
| | ***F) ADD NOTE "ALL COMPONENTS IN THE DOMESTIC WATER |
| | SYSTEM SHALL BE LEAD FREE IN ACCORDANCE WITH FBC PL |
| | 605.2 AND 605.2.1" |
| | |
| | 9. SECOND REQUEST: P-05/PLUMBING FIXTURE SCHEDULE: PER |
| | WPB FBC 107.2.1, PROVIDE SPEC AND ID/TAG FOR SHOWER. |
| | INCLUDE DRAIN, SHOWER CONTROL VALVE AND TRIM. PER FBC |
| | PL 412.3, INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION |
| | VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR |
| | COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT |
| | CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME |
| | A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND |
| | SHALL BE INSTALLED AT THE POINT OF USE. |
| | |
| | 10. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A |
| | CROSS-SECTION SHOWER WALL/FLOOR/DRAIN AND THRESHOLD |
| | DETAIL |
| | ***A) DETAIL SHALL INCLUDE ALL COMPONENTS OF FBC PL |
| | 421.5.2 AS FOLLOWS |
| | LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2 |
| | INCHES ABOVE THE FINISHED THRESHOLD LEVEL |
| | LINERS SHALL BE RECESSED AND FASTENED TO AN APPROVED |
| | BACKING |
| | LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY POINT |
| | LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD |
| | LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL IN 12 |
| | UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE SLOPED |
| | TOWARD THE FIXTURE DRAIN |
| | LINERS SHALL BE SECURELY FASTENED TO THE WASTE OUTLET |
| | AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT JOINT |
| | BETWEEN THE LINER AND THE OUTLET |
| | FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS SHALL BE |
| | LAID ON, AND SUPPORTED BY, A SMOOTH AND STRUCTURALLY |
| | SOUND BASE. |
| | ***B) LINER MATERIAL (SPECIFY LINER MATERIAL COMPLYING |
| | WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1, |
| | 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR |
| | 421.5.2.6.) NOTE THAT FBC PL 421.5.2.1 PLASTICIZED |
| | POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE |
| | REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED. |
| | ***C) FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS |
| | SHALL BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND |
| | NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET |
| | ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| | ABOVE THE DRAIN OF THE SHOWER. |
| | |
| | 11. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE PIPE |
| | HANGER DETAIL WITH A NOTE STATING, "HORIZONTAL PIPE |
| | SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE |
| | 308.5." |
| | |
| | 12. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE A SLAB |
| | REPAIR DETAIL ON THE PLANS. SHOW THE WIDTH OF THE |
| | REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE |
| | TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER), |
| | MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR |
| | DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT |
| | OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER |
| | WELL COMPACTED SOIL. A COPY OF THE TERMITE CERTIFICATE |
| | SHALL BE ONSITE FOR FINAL INSPECTION. |
| | |
| | 13. SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE |
| | APPLICABLE RATED WALL/FLOOR DETAILS FOR PLUMBING |
| | PENETRATIONS COMPLYING WITH THE REQUIREMENTS OF FBC |
| | CHAPTER 7. |
| | |
| | 14. SECOND REQUEST: PER WPB FBC 107.2.1, TO SHOW |
| | COMPLIANCE WITH FBC PL 704.1, PROVIDE NOTE STATING |
| | "HORIZONTAL DRAINAGE PIPING LESS THAN 3 INCH DIAMETER |
| | SHALL HAVE A MINIMUM SLOPE OF 1/4 INCH PER FOOT. 3 INCH |
| | TO 6 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF 1/8 |
| | INCH PER FOOT". |
| | |
| | 15. SECOND REQUEST: P-07/RISER DIAGRAM: PER FBC PL |
| | 606.1(6) PROVIDE A FULL OPEN VALVE TO EACH HOT AND COLD |
| | WATER SUPPLY TO EACH NEW UNIT. THE LAVATORIES SHALL BE |
| | INSTALLED DOWNSTREAM OF SAID VALVES. |
| | |
| | 16. SECOND REQUEST: P-07/RISER DIAGRAM: PER WPB FBC |
| | 107.2.1, IDENTIFY THE WATER HAMMER ARRESTORS (TAG WHA) |
| | ON THE WATER RISER DIAGRAMS. |
| | |
| | 17. SECOND REQUEST: PER FBC PL 604.1, THE DESIGN OF THE |
| | WATER DISTRIBUTION SYSTEM SHALL CONFORM TO ACCEPTED |
| | ENGINEERING PRACTICE. METHODS UTILIZED TO DETERMINE |
| | PIPE SIZES SHALL BE APPROVED. PER WPB FBC 107.2.1 AND |
| | 107.3.5.1.3, PROVIDE CALCULATIONS FOR SIZING OF WATER |
| | DISTRIBUTION. FBC PL APPENDIX E, SIZING OF WATER PIPING |
| | SYSTEM IS AN APPROVED METHOD. |
| | |
| | 18. SECOND REQUEST: P-01/EXISTING FLOOR DRAIN: PER WPB |
| | FBC 107.2.1, CONFIRM THAT THE EXISTING FLOOR DRAIN IN |
| | THE NEW BATHROOM HAS A TRAP PRIMER AND INDICATE ON THE |
| | PLAN HOW IT IS PROVIDED. IF NOT, THEN PER FBC PL |
| | 1002.4.1, PROVIDE TRAP SEAL PROTECTION IN ACCORDANCE |
| | WITH ONE OF THE METHODS IN SECTIONS 1002.4.1.1 THROUGH |
| | 1002.4.1.4. ADDITIONALLY, PROVIDE A SCHEMATIC DETAIL. |
| | |
| | 19. SECOND REQUEST: P-05/SANITARY RISER DIAGRAM: PER |
| | FBC PL 909.1, EACH FIXTURE TRAP SHALL HAVE A PROTECTING |
| | VENT LOCATED SO THAT THE SLOPE AND THE DEVELOPED LENGTH |
| | IN THE FIXTURE DRAIN FROM THE TRAP WEIR TO THE VENT |
| | FITTING ARE WITHIN THE REQUIREMENTS SET FORTH IN TABLE |
| | 909.1. THE WATER CLOSETS AND SHOWERS ON THE FIRST, |
| | SECOND AND THIRD FLOORS DO NOT COMPLY. PER WPB FBC |
| | 107.2.1, VENT EACH OF THE WATER CLOSETS AND SHOWERS IN |
| | ACCORDANCE WITH ONE OF THE PRESCRIBED METHODS IN |
| | CHAPTER 9. |
| | |
| | 20. SECOND REQUEST: P-05/SANITARY RISER SERVICING ONLY |
| | FLOORS 2 THROUGH 4: PER FBC PL 912.1.1, THE SHOWER |
| | DRAIN ON THE FOURTH FLOOR SHALL CONNECT TO THE STACK AT |
| | OR ABOVE THE WATER CLOSET ELEVATION. PLEASE NOTE ALSO |
| | THAT ANY TIME A WATER CLOSET AND OTHER BATHROOM GROUP |
| | FIXTURES ARE CONNECTED TO ANY VERTICAL WET VENT, THE |
| | OTHER FIXTURES SHALL CONNECT AT OR ABOVE THE ELEVATION |
| | WITH THE WATER CLOSET AS NOTED IN 912.1.1. |
| | |
| | 21. SECOND REQUEST: P-05/SANITARY RISER GROUND FLOOR: |
| | THE BRANCH BETWEEN THE FLOOR DRAIN AND THE CONNECTION |
| | RECEIVING THE BATHROOM GROUPS DISCHARGE IS INCORRECTLY |
| | TAGGED VTR. PER WPB FBC 107.2.1, PLEASE CORRECT. |
| | |
| | 22. SECOND REQUEST: P-05/SANITARY RISER WITH GROUND |
| | FLOOR BATHROOM: WATER CLOSET FIXTURE DRAIN SHALL BE 3 |
| | INCH MINIMUM SIZE PER FBC PL 704.2, TABLE 709.1(D) AND |
| | 710.1(2)-A |
| | |
| | 23. SECOND REQUEST: PER WPB FBC 107.2.1, ID/TAG THE |
| | SANITARY AND WATER RISERS ON BOTH RISER DIAGRAMS AND |
| | FLOOR PLANS. ID/TAG SHALL MATCH ON THE CORRESPONDING |
| | DRAWINGS. SEE COMMENT 7 REGARDING THE FIXTURE SCHEDULE. |
| | |
| | 24. SECOND REQUEST: P-05/SANITARY RISER: BATHROOM |
| | GROUPS PER FBC PL TABLE 710.1, HAVE A FIXTURE UNIT |
| | VALUE OF 5 PER GROUP. WATER CLOSETS, PRIVATE, 1.6 GPF |
| | OR LESS HAVE A VALUE OF 3. SHOWERS HAVE A VALUE OF 2. |
| | PER WPB FBC 107.2.1, PLEASE REVIEW YOUR CALCULATIONS |
| | AND MODIFY AS IS APPROPRIATE. |
| | |
| | 25. PER WPB FBC 107.2.1, PLEASE INDICATE ON THE PLANS |
| | IF THE HOT WATER SYSTEM IS RECIRCULATED OR HEAT TRACED; |
| | PROVIDE THE TEMPERATURE OF THE HOT WATER. |
| | TO BE CLEAR, PER FBC PL 607.2, THE DEVELOPED LENGTH OF |
| | HOT OR TEMPERED WATER PIPING FROM THE SOURCE OF HOT |
| | WATER TO THE FIXTURE SHALL NOT EXCEED 50 FEET. |
| | RECIRCULATING SYSTEMS AND HEAT TRACED SYSTEMS ARE |
| | CONSIDERED TO BE SOURCES OF HOT OR TEMPERED WATER. |
| | PLEASE SHOW THAT THE HOT OR TEMPERED WATER FROM THE |
| | SOURCE TO THE FIXTURES DOES NOT EXCEED 50 FEET OR |
| | PROVIDE MEANS TO COMPLY. |
| | |
| | 26.NEW COMMENT: FBC ACC 611, PROVIDE THE MEASUREMENTS |
| | WITHIN THE LAUNDRY ROOMS TO SHOW COMPLIANCE WITH |
| | ACCESSIBLE REQUIREMENTS INCLUDING CLEAR FLOOR, WHEEL |
| | CHAIR APPROACH AND REACH REQUIREMENTS. |
| | |
| | 27. NEW COMMENT: IT APPEARS THAT THE PLUMBING FIXTURE |
| | SCHEDULE ON P-05 IS FROM THE ORIGINAL CONSTRUCTION AND |
| | IS NOT APPLICABLE TO THE NEW WORK; SOME PRODUCTS ARE |
| | DISCONTINUED. PER WPB FBC 107.2.1, PROVIDE AN |
| | APPLICABLE FIXTURE SCHEDULE; TAG TO MATCH DRAWINGS. SEE |
| | COMMENT 7 AND 23. |
| | |
| | 28. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CORRECT |
| | OCCUPANCY (PER FBC 310.4, R-2) AND THE OCCUPANT LOAD |
| | FOR THE BUILDING. |
| | |
| | 29. NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE A |
| | PLUMBING FIXTURE SCHEDULE FOR THE BUILDING SHOWING THE |
| | REQUIRED PLUMBING FIXTURES (SEE FBC PL TABLE 403.1) AND |
| | THE PROVIDED PLUMBING FIXTURES. THIS DOES NOT APPLY TO |
| | THE DWELLING UNITS. PLEASE NOTE THAT THE REQUIRED |
| | DRINKING FOUNTAIN QUANTITY FOR R-2 IS 1 PER 100 |
| | PERSONS. ADDITIONALLY, IN ACCORDANCE WITH FBC PL 410.3 |
| | AND FBC ACC 211.2, A BI-LEVEL DRINKING FOUNTAIN |
| | CONSTITUTES 2 DRINKING FOUNTAINS. |
| | |
| | 30. NEW COMMENT: IT APPEARS THAT THE PLUMBING FIXTURE |
| | SCHEDULE ON P-05 IS FROM THE ORIGINAL CONSTRUCTION AND |
| | IS NOT APPLICABLE TO THE NEW WORK; SOME PRODUCTS ARE |
| | DISCONTINUED. PER WPB FBC 107.2.1, PROVIDE AN |
| | APPLICABLE FIXTURE SCHEDULE; TAG TO MATCH DRAWINGS. SEE |
| | COMMENT 7 AND 23. |
| | |
| | 31. NEW COMMENT: PLAN SHEET A-0/APPLICABLE CODES: PER |
| | WPB FBC 107.2.1, PLEASE ADD 2020 FLORIDA BUILDING CODE, |
| | EXISTING BUILDING, 7TH EDITION AND PROVIDE THE |
| | APPLICABLE LEVEL OF OPERATION. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | PLEASE PROVIDE A DETAILED RESPONSE LETTER ADDRESING |
| | EACH ITEM/COMMENT. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| | AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER PX928 |
| | PLUMBING INSPECTOR BN2148 |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |