| Plan Review Stops For Permit 22051247 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2023-06-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-27 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-06-26 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2023-06-26 19:09:27 | RESIDENTIAL (R3) ALTERATION, FIFTH BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22051247 | | | 522 28TH ST | | | | | | 3- OK. WINDOW AND DOOR HURRICANE SHUTTERS UNDER PERMIT | | | #23040271. | | | | | | | | | PREVIOUS COMMENT: | | | 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER | | | SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION | | | (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF | | | THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE | | | PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY | | | WILL BE APPLIED IF THAT IS THE INTENTION. | | | PREVIOUS RESPONSE: REPEAT COMMENT. NOT ADDRESSED. | | | CONTRACTOR'S RESPONSE LETTER STATES "SEE REVISED SHEET | | | S1.0.". SHEET S1.0 WAS NOT REVISED. SAME SPECIFICATIONS | | | ARE SHOWN. SINCE THE ATTIC IS NOT VENTED, IT LOOKS LIKE | | | FOAM INSULATION WILL BE REQUIRED. REVISE INFORMATION ON | | | SHEET S1.0. SPECIFY FOAM INSULATION AND R-VALUE. | | | ALSO, NEED TO PROVIDE ICC EVALUATION REPORT (OR ANY | | | OTHER APPROVED ENTITY) OF FOAM INSULATION TO SHOW | | | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. | | | (NOTE: COORDINATE R-VALUE WITH ENERGY CALCULATIONS TO | | | AVOID CONFLICTS/DELAYS). | | | | | | NEW RESPONSE: | | | DETAIL F.2 ON SHEET S1.0 WAS REVISED SHOWING R-20 | | | ICYNENE SPRAY FOAM INSULATION BUT THE ENERGY | | | CALCULATIONS WERE NOT REVISED: | | | A) REVISE CEILING INSULATION R-VALUE TO MATCH REVISED | | | PLANS. | | | SECTION R101.5.1.1.2 FBC-RESIDENTIAL. | | | | | | B)REVISE CONCRETE BLOCK INSULATION R-VALUE TO MATCH | | | REVISED PLANS. | | | SECTION R101.5.1.1.2 FBC-RESIDENTIAL. | | | | | | C) REVISE ITEM #1 ON PAGE ONE OF ENERGY CALCULATIONS. | | | THIS IS NOT AN ADDITION. THIS IS AN ALTERATION TO | | | EXISTING BUILDING (GARAGE). | | | SECTION R101.5.1.1.2 FBC-RESIDENTIAL. | | | | | | D)ICYNENE EVALUATION REPORT ESR-1826 SUBMITTED IS | | | EXPIRED. IT HAD TO BE RENEWED ON 02/2018. SEE RIGHT TOP | | | CORNER BELOW ESR-1826. PROVIDE CURRENT EVALUATION | | | REPORT. | | | SEC. SECTION R101.5.1.1.2 FBC-RESIDENTIAL. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | NEW COMMENTS BASED ON NEW INFORMATION SUBMITTED. | | | 7- DRAWING D1.0 SHOWS A NEW DECORATIVE GATE ELEVATION. | | | NEED TO PROVIDE THE FOLLOWING FOR REVIEW: | | | A)PROVIDE COMPLETE SIGNED AND SEALED SITE SPECIFIC | | | ENGINEERING FOR THE CONSTRUCTION AND INSTALLATION OF | | | THIS DOOR. | | | NOTE: DESIGN PROFESSIONAL TO TAKE INTO CONSIDERATION | | | THE INSTALLATION OF HURRICANE STORM PANELS (SEE | | | SEPARATE PERMIT) TO AVOID CONFLICTS/DELAYS. | | | FAC 61G20.3001. SEC. R301.2.1 FBC-RESIDENTIAL. SEC. | | | 107.2.1.2 CITY AMENDMENTS. | | | | | | B) SHOW LOCATION OF THE PROPOSED DOOR. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 8- UPDATE VALUATION TO INCLUDE THE ADDTIONAL DOOR . | | | INCLUDE THE LABOR AND MATERIALS AND ENGINEERING. SEC. | | | 109.3 CITY AMENDMENTS. | | | | | | 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR | | | MASONRY WALL FLASHING AT ALL NEW EXTERIOR OPENINGS. | | | SEC. R703.4 FBC-RESIDENTIAL. | | | SHOW LOCATION OF PROPOSED DOOR. | | | SEC. 107.2.1 CITY AMENDMENTS. | | | | | | 10- PROVIDE EXTERIOR DOOR AND WINDOW STRUCTURAL BUCK | | | DETAIL SHOWING COMPLIANCE WITH SEC. R609.7.2.1 | | | FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND | | | FASTENING. | | | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO | | | THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 | | | FBC-RESIDENTIAL. | | | | | | 11- DOOR AND WINDOW WIND PRESSURES SPECIFIED UNDER WIND | | | PRESSURE LOAD ON SHEET D1.0 ARE TOO LOW FOR EXPOSURE C. | | | REVISE AS REQUIRED. | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | NOTE: WINDOW IS LOCATED IN END ZONE #5 NOT #4. SEE NOTE | | | "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL. | | | | | | 12- 67-1/2" WIDE DOUBLE FRENCH DOOR WILL BE INSPECTED | | | ON SITE TO VERIFY 32" CLEAR OPENING OF AT LEAST ONE | | | LEAF. VERIFY SIZE WITH MANUFACTURER TO AVOID DOOR | | | REPLACEMENT. ALSO. REVISE SIZE OF MASONRY OPENING | | | SPECIFIED ON THE STRUCTURAL DRAWING. | | | SEC. 107.2.1 CITY AMENDMENTS | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2023-03-15 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-03-15 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-03-15 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2023-03-15 17:17:20 | RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22051247 | | | 522 28TH ST | | | | | | | | | PREVIOUS COMMENT: | | | 3.) FBC B 107.2.1, THE EXTERIOR WINDOW/DOOR ARE | | | INDICATED AS NON-IMPACT WINDOWS/DOORS. PLEASE PROVIDE A | | | CLARIFICATION AS TO THE METHOD OF IMPACT PROTECTION. | | | | | | RESPONSE: | | | CONTRACTOR'S RESPONSE LETTER STATES "THERE WILL BE A | | | SEPARATE PERMIT PULLED BY THE COMPANY THAT'LL BE | | | INSTALLING HURRICANE SHUTTERS". PERMIT APPLICATION FOR | | | SHUTTERS HAS NOT BEEN SUBMITTED YET. THIS ITEM WILL BE | | | APPROVED WHEN CONTRACTOR APPLIES FOR SHUTTERS PERMIT | | | AND PROVIDES COMPLETE INFORMATION FOR REVIEW. | | | | | | | | | PREVIOUS COMMENT: | | | 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER | | | SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION | | | (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF | | | THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE | | | PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY | | | WILL BE APPLIED IF THAT IS THE INTENTION. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. CONTRACTOR'S RESPONSE | | | LETTER STATES "SEE REVISED SHEET S1.0.". SHEET S1.0 WAS | | | NOT REVISED. SAME SPECIFICATIONS ARE SHOWN. SINCE THE | | | ATTIC IS NOT VENTED, IT LOOKS LIKE FOAM INSULATION WILL | | | BE REQUIRED. REVISE INFORMATION ON SHEET S1.0. SPECIFY | | | FOAM INSULATION AND R-VALUE. | | | ALSO, NEED TO PROVIDE ICC EVALUATION REPORT (OR ANY | | | OTHER APPROVED ENTITY) OF FOAM INSULATION TO SHOW | | | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. | | | (NOTE: COORDINATE R-VALUE WITH ENERGY CALCULATIONS TO | | | AVOID CONFLICTS/DELAYS). | | | | | | | | | | | | 10- DESIGNER OF RECORD NEEDS TO PROVIDE NAME AND | | | SIGNATURE IN ALL DRAWINGS AS REQUIRED BY SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | | | | | | | NOTE TO CONTRACTOR: | | | 67-1/2" WIDE DOUBLE FRENCH DOOR WILL BE INSPECTED ON | | | SITE TO VERIFY 32" CLEAR OPENING OF AT LEAST ONE LEAF. | | | VERIFY SIZE WITH MANUFACTURER TO AVOID DOOR | | | REPLACEMENT. ALSO. REVISE SIZE OF MASONRY OPENING | | | SPECIFIED ON THE STRUCTURAL DRAWING. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2023-02-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-02-22 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-02-22 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2023-02-22 15:38:25 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC EC R 103.1.1.2, THE ENERGY CALCULATIONS ARE | | | MISSING THE SIGNATURES BY THE OWNER/OWNER'S | | | REPRESENTATIVE. | | | | | | 3.) FBC B 107.2.1, THE EXTERIOR WINDOW/DOOR ARE | | | INDICATED AS NON-IMPACT WINDOWS/DOORS. PLEASE PROVIDE A | | | CLARIFICATION AS TO THE METHOD OF IMPACT PROTECTION. | | | | | | 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER | | | SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION | | | (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF | | | THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE | | | PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY | | | WILL BE APPLIED IF THAT IS THE INTENTION. | | | | | | 6.B.) FBC B 107.2.1, FOR THE WALL INSULATION (R-11 | | | PAPER BACK) WITHIN THE WOOD FRAMED WALL DETAIL F.1 ON | | | PLAN SHEET S1.0, THIS DETAIL STILL INDICATES 2"X 4" | | | WALL FRAMING. PLEASE CHANGE THE DETAIL TO INDICATE THE | | | WALL FRAMING SIZE THAT WILL ACCOMODATE THE R-11 PAPER | | | BACK INSULATION THICKNESS REQUIREMENT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-06 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-06 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2022-10-06 17:07:20 | RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW | | | COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22051247 | | | 522 28TH ST | | | | | | NOTE: | | | CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC. | | | 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING. | | | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND | | | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | ORIGINAL COMMENT: | | | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.5 FBC-ENERGY CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 2- DESIGNER OF RECORD TO PROVIDE ALL THE WIND DESIGN | | | CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. | | | SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING | | | EXPOSURE, BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE | | | COMPONENTS AND CLADDING DESIGN PRESSURES. (DOORS, | | | WINDOWS). | | | | | | RESPONSE: | | | A)CLARIFY WHERE ARE THE WINDOW AND DOOR WIND PRESSURE | | | LOADS TAKEN FROM? THEY ARE TOO LOW FOR A BUILDING IN | | | EXPOSURE "C". | | | SEC. R301.2.1 FBC-RESIDENTIAL. | | | | | | | | | B)WINDOW AND DOOR SCHEDULE SPECIFY D.P.R. PSI. WHAT IS | | | THIS?. | | | NOTE: DESIGN PRESSURES ARE GIVEN IN POUNDS PER SQUARE | | | FEET NOT POUNDS PER SQUARE INCH. REVISE /CLARIFY. SEC. | | | 107.2.1 CITY AMENDMENTS. | | | | | | ORIGINAL COMMENT: | | | 3- EGRESS DOOR. NEW HABITABLE ROOM NEEDS A SIDE HINGED | | | DOOR LEADING DIRECTLY TO THE OUTSIDE. THE DOOR NEEDS TO | | | PROVIDE A CLEAR WIDTH OPENING OF NOT LESS THAN 32 | | | INCHES. SEC. R311.2 FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | 5'-0" DOUBLE HUNG DOESN'T COMPLY. NEED DOOR THAT | | | PROVIDES AT LEAST 32" CLEAR WIDTH OPENING WHEN ONE LEAF | | | IS OPEN. | | | | | | ORIGINAL COMMENT: | | | 4- PROVIDE PRODUCT APPROVAL FOR EXTERIOR SWING DOOR. | | | SEE ITEM #2 ABOVE. | | | SEC. 61G20.3.001 F.A.C. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 5- NEED TO SPECIFY FIRE RATED DOOR SHOWING COMPLIANCE | | | WITH SEC. R311.2 FBC-RESIDENTIAL FOR DOOR LEADING FROM | | | THE GARAGE TO THE HABITABLE ROOM. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | ORIGINAL COMMENT: | | | 6- DESIGNER OF RECORD NEEDS TO DEPICT THE BUILDING | | | THERMAL ENVELOPE. NEED TO SPECIFY INSULATION MATERIALS | | | AND THEIR R-VALUES AT ROOF, WALLS, ETC. AS REQUIRED BY | | | SEC. R103.2 FBC-ENERGY CONSERVATION. | | | | | | RESPONSE: | | | STRUCTURAL DRAWING S1.0: | | | A)DETAIL F.2 SHOWS R-30 PAPER BACK ROOF INSULATION. | | | DETAIL IS NOT CLEAR HOW THE INSULATION IS INSTALLED. | | | R-30 PAPER BACK INSULATION IS +/- 9-1/2" THICK. THIS | | | INSULATION WILL COMPLETELY FILL THE 2X10 EXISTING ROOF | | | JOIST. | | | THEREFORE, THE DETAIL IS INCORRECT. DESIGNER OF RECORD | | | TO SPECIFY IF THE ATTIC IS VENTED OR UNVENTED. IF | | | VENTED, THEN THE INSULATION DOESN'T PROVIDE CROSS | | | VENTILATION. THEREFORE IT DOESN'T WORK. IF NOT VENTED, | | | THEN PROVIDE COMPLETE DETAIL SPECIFICATIONS FOR TYPE OF | | | INSULATION SHOWING COMPLIANCE WITH SEC. R806.5 | | | FBC-RESIDENTIAL. | | | NOTE: IF SPECIFYING SPRAY FOAM INSULATION, THEN PROVIDE | | | ICC EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY | | | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. | | | | | | B)DETAIL F.1: R19 PAPER BACK INSULATION IS +/- 6-1/4" | | | THICK. THEREFORE IT DOESN'T FIT ON A 2X4 WALL. REVISE | | | AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. | | | | | | C)EXTERIOR WALL SPECIFICATIONS ON DETAIL F.2 DON'T | | | SPECIFY INSULATION R-VALUE. ALSO, PROVIDE ICC | | | EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY | | | COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL. | | | | | | ORIGINAL COMMENT: | | | 7- PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING | | | COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL. | | | SPECIFY STRUCTURAL BUCK SIZE AND FASTENING. | | | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO | | | THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 | | | FBC-RESIDENTIAL. | | | | | | RESPONSE: | | | REPEAT COMMENT. NOT ADDRESSED. | | | | | | NEW COMMENT BASED ON NEW INFORMATION SUBMITTED: | | | 8- STRUCTURAL DETAILS ON SHEET S1.0 ARE NOT CLEAR AND | | | ARE INCOMPLETE. SPECIFICATIONS FOR VERTICAL | | | REINFORCEMENT AT THE END OF EACH OPENING IS NOT CLEAR. | | | CLARIFY WHY DON'T SPECIFYING CONTINUOUS REINFORCEMENT | | | FROM TOP TO BOTTOM. OVERLAP OF REBARS IS NOT SPECIFIED. | | | THERE ARE NO SPECS SHOWING HOW THE END COLUMNS ARE | | | FILLED. | | | SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 | | | FBC-RESIDENTIAL. | | | | | | 9- NEW HABITABLE ROOM NEEDS TO HAVE HEATING AS REQUIRED | | | BY SEC. R303.10 FBC-RESIDENTIAL. | | | | | | 10- DESIGNER OF RECORD NEEDS TO PROVIDE NAME AND | | | SIGNATURE IN ALL DRAWINGS AS REQUIRED BY SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-07-22 |
Time |
19:27 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-07-22 |
Time |
17:46 |
Sent To |
|
|
| Notes |
| 2022-07-22 19:27:22 | RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS | | | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. | | | PERMIT #22051247 522 28TH ST | | | | | | NOTE: | | | CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC. | | | 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING. | | | ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND | | | METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE. | | | | | | 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. | | | R101.5 FBC-ENERGY CONSERVATION. | | | NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL | | | REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID | | | CONFLICTS/DELAYS. | | | | | | 2- DESIGNER OF RECORD TO PROVIDE ALL THE WIND DESIGN | | | CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. | | | SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING | | | EXPOSURE, BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE | | | COMPONENTS AND CLADDING DESIGN PRESSURES. (DOORS, | | | WINDOWS). | | | | | | 3- EGRESS DOOR. NEW HABITABLE ROOM NEEDS A SIDE HINGED | | | DOOR LEADING DIRECTLY TO THE OUTSIDE. THE DOOR NEEDS TO | | | PROVIDE A CLEAR WIDTH OPENING OF NOT LESS THAN 32 | | | INCHES. SEC. R311.2 FBC-RESIDENTIAL. | | | | | | 4- PROVIDE PRODUCT APPROVAL FOR EXTERIOR SWING DOOR. | | | SEE ITEM #2 ABOVE. | | | SEC. 61G20.3.001 F.A.C. | | | | | | 5- NEED TO SPECIFY FIRE RATED DOOR SHOWING COMPLIANCE | | | WITH SEC. R311.2 FBC-RESIDENTIAL FOR DOOR LEADING FROM | | | THE GARAGE TO THE HABITABLE ROOM. | | | | | | 6- DESIGNER OF RECORD NEEDS TO DEPICT THE BUILDING | | | THERMAL ENVELOPE. NEED TO SPECIFY INSULATION MATERIALS | | | AND THEIR R-VALUES AT ROOF, WALLS, ETC. AS REQUIRED BY | | | SEC. R103.2 FBC-ENERGY CONSERVATION. | | | | | | 7- PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING | | | COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL. | | | SPECIFY STRUCTURAL BUCK SIZE AND FASTENING. | | | NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO | | | THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 | | | FBC-RESIDENTIAL. | | | | | | | | | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND | | | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE | | | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-05-26 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-05-26 |
Time |
13:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-10-05 |
Time |
12:37 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-10-05 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-06-09 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-09 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-09 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
3 |
Status |
P |
Date |
2023-06-12 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2023-06-12 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2023-06-12 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
2 |
Status |
F |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-04-07 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-04-07 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2023-04-07 11:02:55 | THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S) | | | | | | PROPOSED PLANS APPEAR TO INDICATE FRENCH DOOR RATHER | | | THAN DOOR MAINTAINING APPEARANCE OF GARAGE. HISTORIC | | | REQUIREMENT IS THAT A GARAGE DOOR APPEARANCE IS | | | MAINTAINED. | | | | | | ANNE HAMILTON | | | HISTORIC PRESERVATION PLANNER | | | [email protected] | | | 561.822.1428 | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-06-07 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-06-07 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-06-07 |
Time |
12:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2023-06-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-26 |
Time |
19:10 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-05-22 |
Time |
16:44 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2023-04-10 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2023-04-10 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2023-03-10 |
Time |
12:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2023-02-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-02-22 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-02-03 |
Time |
12:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-06 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-09-20 |
Time |
08:08 |
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-17 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-08-17 |
Time |
06:57 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-05-26 |
Time |
07:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
3 |
Status |
F |
Date |
2023-06-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2023-06-26 |
Time |
19:09 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2023-06-26 |
Time |
19:09 |
Sent To |
|
|
| Notes |
| 2023-06-26 19:10:05 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT | | | TO [email protected]. | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
F |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-06 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-06 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2022-10-06 17:07:50 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT | | | TO [email protected]. | | | | | | |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-22 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-22 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2022-07-22 15:59:27 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT | | | TO [email protected]. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2023-06-27 |
|
|
Cont ID |
|
| Sent By |
cmontell |
Date |
2023-06-05 |
Time |
13:31 |
Rev Time |
0.00 |
| Received By |
cmontell |
Date |
2023-06-27 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2023-03-13 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-03-13 |
Time |
07:43 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-03-13 |
Time |
07:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2023-02-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2023-02-06 |
Time |
06:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2023-02-06 |
Time |
06:38 |
Sent To |
|
|
| Notes |
| 2023-02-06 06:42:19 | THE ENERGY CLACULATION/MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS ARE SPECIFYING A DAIKIN HEAT PUMP | | | MINI-SPLIT. THIS WOULD MEET THE HEATING REQUIREMENTS OF | | | FRC R303.10 | | | | | | PLEASE ADDRESS THE HET REQUIREMENT FROM PREVIOUS | | | REVIEWS BELOW: | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE THROUGH THE WALL SYSTEM MUST COMPLY WITH FRC | | | R303.10 FOR HEATING THE ROOM. IT MUST ALSO COMPLY WITH | | | THE FEC FOR ENERGY CALCULATIONS101.5, MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS R403.7, AND SEER RATING | | | FROM TABLE C403.2.3;3 FEC FORM R402-2020 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-21 |
Time |
08:24 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-21 |
Time |
08:24 |
Sent To |
|
|
| Notes |
| 2022-09-21 08:24:39 | 2ND REVIEW FMC | | | PERMIT: 22051247 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE THROUGH THE WALL SYSTEM MUST COMPLY WITH FRC | | | R303.10 FOR HEATING THE ROOM. IT MUST ALSO COMPLY WITH | | | THE FEC FOR ENERGY CALCULATIONS101.5, MECHANICAL | | | EQUIPMENT SIZING CALCULATIONS R403.7, AND SEER RATING | | | FROM TABLE C403.2.3;3 FEC FORM R402-2020 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-27 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-27 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2022-05-27 08:56:07 | PROVIDE MECHANICAL DRAWING, MECHANICAL EQUIPMENT SIZING | | | AND ENERGY CALCULATIONS FOR THIS NEW CONDITIONED SPACE. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-28 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-05-28 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-05-28 |
Time |
08:16 |
Sent To |
|
|
| Notes |
| 2022-05-28 08:17:24 | NO PLUMBING INDICATED ON THE PLANS | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2023-05-26 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2023-05-26 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2023-05-26 |
Time |
13:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
N |
Date |
2023-02-22 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2023-02-22 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2023-02-22 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
N |
Date |
2022-10-06 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-10-06 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-10-05 |
Time |
12:37 |
Sent To |
|
|
| Notes |
| 2022-10-06 17:08:39 | NO ARCHITECT OR ENGINEER ON THIS SUBMITTAL. JG. | | 2022-10-05 12:41:49 | 10/5/22 CONTRACTOR ELECTRIC DRAWING NOT REQUIRED. MP |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
N |
Date |
2022-06-09 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-09 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-09 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
N |
Date |
2023-04-07 |
|
|
Cont ID |
|
| Sent By |
amhamilt |
Date |
2023-04-07 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2023-04-07 |
Time |
11:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
ahamilto |
Date |
2022-08-16 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
amhamilt |
Date |
2022-08-16 |
Time |
16:37 |
Sent To |
|
|
| Notes |
|
|