Plan Review Details - Permit 22051247
Plan Review Stops For Permit 22051247
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2023-06-26 Cont ID  
Sent By jgomez Date 2023-06-27 Time 19:09 Rev Time 0.00
Received By jgomez Date 2023-06-26 Time 16:19 Sent To  
Notes
2023-06-26 19:09:27RESIDENTIAL (R3) ALTERATION, FIFTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051247
 522 28TH ST
  
 3- OK. WINDOW AND DOOR HURRICANE SHUTTERS UNDER PERMIT
 #23040271.
  
  
 PREVIOUS COMMENT:
 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER
 SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION
 (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF
 THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE
 PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY
 WILL BE APPLIED IF THAT IS THE INTENTION.
 PREVIOUS RESPONSE: REPEAT COMMENT. NOT ADDRESSED.
 CONTRACTOR'S RESPONSE LETTER STATES "SEE REVISED SHEET
 S1.0.". SHEET S1.0 WAS NOT REVISED. SAME SPECIFICATIONS
 ARE SHOWN. SINCE THE ATTIC IS NOT VENTED, IT LOOKS LIKE
 FOAM INSULATION WILL BE REQUIRED. REVISE INFORMATION ON
 SHEET S1.0. SPECIFY FOAM INSULATION AND R-VALUE.
 ALSO, NEED TO PROVIDE ICC EVALUATION REPORT (OR ANY
 OTHER APPROVED ENTITY) OF FOAM INSULATION TO SHOW
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 (NOTE: COORDINATE R-VALUE WITH ENERGY CALCULATIONS TO
 AVOID CONFLICTS/DELAYS).
  
 NEW RESPONSE:
 DETAIL F.2 ON SHEET S1.0 WAS REVISED SHOWING R-20
 ICYNENE SPRAY FOAM INSULATION BUT THE ENERGY
 CALCULATIONS WERE NOT REVISED:
 A) REVISE CEILING INSULATION R-VALUE TO MATCH REVISED
 PLANS.
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 B)REVISE CONCRETE BLOCK INSULATION R-VALUE TO MATCH
 REVISED PLANS.
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 C) REVISE ITEM #1 ON PAGE ONE OF ENERGY CALCULATIONS.
 THIS IS NOT AN ADDITION. THIS IS AN ALTERATION TO
 EXISTING BUILDING (GARAGE).
 SECTION R101.5.1.1.2 FBC-RESIDENTIAL.
  
 D)ICYNENE EVALUATION REPORT ESR-1826 SUBMITTED IS
 EXPIRED. IT HAD TO BE RENEWED ON 02/2018. SEE RIGHT TOP
 CORNER BELOW ESR-1826. PROVIDE CURRENT EVALUATION
 REPORT.
 SEC. SECTION R101.5.1.1.2 FBC-RESIDENTIAL. SEC. 107.2.1
 CITY AMENDMENTS.
  
 NEW COMMENTS BASED ON NEW INFORMATION SUBMITTED.
 7- DRAWING D1.0 SHOWS A NEW DECORATIVE GATE ELEVATION.
 NEED TO PROVIDE THE FOLLOWING FOR REVIEW:
 A)PROVIDE COMPLETE SIGNED AND SEALED SITE SPECIFIC
 ENGINEERING FOR THE CONSTRUCTION AND INSTALLATION OF
 THIS DOOR.
 NOTE: DESIGN PROFESSIONAL TO TAKE INTO CONSIDERATION
 THE INSTALLATION OF HURRICANE STORM PANELS (SEE
 SEPARATE PERMIT) TO AVOID CONFLICTS/DELAYS.
 FAC 61G20.3001. SEC. R301.2.1 FBC-RESIDENTIAL. SEC.
 107.2.1.2 CITY AMENDMENTS.
  
 B) SHOW LOCATION OF THE PROPOSED DOOR.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 8- UPDATE VALUATION TO INCLUDE THE ADDTIONAL DOOR .
 INCLUDE THE LABOR AND MATERIALS AND ENGINEERING. SEC.
 109.3 CITY AMENDMENTS.
  
 9- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 MASONRY WALL FLASHING AT ALL NEW EXTERIOR OPENINGS.
 SEC. R703.4 FBC-RESIDENTIAL.
 SHOW LOCATION OF PROPOSED DOOR.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 10- PROVIDE EXTERIOR DOOR AND WINDOW STRUCTURAL BUCK
 DETAIL SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 11- DOOR AND WINDOW WIND PRESSURES SPECIFIED UNDER WIND
 PRESSURE LOAD ON SHEET D1.0 ARE TOO LOW FOR EXPOSURE C.
 REVISE AS REQUIRED.
 SEC. R301.2.1 FBC-RESIDENTIAL.
 NOTE: WINDOW IS LOCATED IN END ZONE #5 NOT #4. SEE NOTE
 "A" ON FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 12- 67-1/2" WIDE DOUBLE FRENCH DOOR WILL BE INSPECTED
 ON SITE TO VERIFY 32" CLEAR OPENING OF AT LEAST ONE
 LEAF. VERIFY SIZE WITH MANUFACTURER TO AVOID DOOR
 REPLACEMENT. ALSO. REVISE SIZE OF MASONRY OPENING
 SPECIFIED ON THE STRUCTURAL DRAWING.
 SEC. 107.2.1 CITY AMENDMENTS
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2023-03-15 Cont ID  
Sent By jgomez Date 2023-03-15 Time 17:17 Rev Time 0.00
Received By jgomez Date 2023-03-15 Time 16:26 Sent To  
Notes
2023-03-15 17:17:20RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051247
 522 28TH ST
  
  
 PREVIOUS COMMENT:
 3.) FBC B 107.2.1, THE EXTERIOR WINDOW/DOOR ARE
 INDICATED AS NON-IMPACT WINDOWS/DOORS. PLEASE PROVIDE A
 CLARIFICATION AS TO THE METHOD OF IMPACT PROTECTION.
  
 RESPONSE:
 CONTRACTOR'S RESPONSE LETTER STATES "THERE WILL BE A
 SEPARATE PERMIT PULLED BY THE COMPANY THAT'LL BE
 INSTALLING HURRICANE SHUTTERS". PERMIT APPLICATION FOR
 SHUTTERS HAS NOT BEEN SUBMITTED YET. THIS ITEM WILL BE
 APPROVED WHEN CONTRACTOR APPLIES FOR SHUTTERS PERMIT
 AND PROVIDES COMPLETE INFORMATION FOR REVIEW.
  
  
 PREVIOUS COMMENT:
 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER
 SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION
 (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF
 THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE
 PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY
 WILL BE APPLIED IF THAT IS THE INTENTION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. CONTRACTOR'S RESPONSE
 LETTER STATES "SEE REVISED SHEET S1.0.". SHEET S1.0 WAS
 NOT REVISED. SAME SPECIFICATIONS ARE SHOWN. SINCE THE
 ATTIC IS NOT VENTED, IT LOOKS LIKE FOAM INSULATION WILL
 BE REQUIRED. REVISE INFORMATION ON SHEET S1.0. SPECIFY
 FOAM INSULATION AND R-VALUE.
 ALSO, NEED TO PROVIDE ICC EVALUATION REPORT (OR ANY
 OTHER APPROVED ENTITY) OF FOAM INSULATION TO SHOW
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
 (NOTE: COORDINATE R-VALUE WITH ENERGY CALCULATIONS TO
 AVOID CONFLICTS/DELAYS).
  
  
  
 10- DESIGNER OF RECORD NEEDS TO PROVIDE NAME AND
 SIGNATURE IN ALL DRAWINGS AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
  
  
 NOTE TO CONTRACTOR:
 67-1/2" WIDE DOUBLE FRENCH DOOR WILL BE INSPECTED ON
 SITE TO VERIFY 32" CLEAR OPENING OF AT LEAST ONE LEAF.
 VERIFY SIZE WITH MANUFACTURER TO AVOID DOOR
 REPLACEMENT. ALSO. REVISE SIZE OF MASONRY OPENING
 SPECIFIED ON THE STRUCTURAL DRAWING.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-02-22 Cont ID  
Sent By pvalenti Date 2023-02-22 Time 15:11 Rev Time 0.00
Received By pvalenti Date 2023-02-22 Time 11:01 Sent To  
Notes
2023-02-22 15:38:25PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC EC R 103.1.1.2, THE ENERGY CALCULATIONS ARE
 MISSING THE SIGNATURES BY THE OWNER/OWNER'S
 REPRESENTATIVE.
  
 3.) FBC B 107.2.1, THE EXTERIOR WINDOW/DOOR ARE
 INDICATED AS NON-IMPACT WINDOWS/DOORS. PLEASE PROVIDE A
 CLARIFICATION AS TO THE METHOD OF IMPACT PROTECTION.
  
 6.A.) FBC R 806.5 (UNVENTED ATTIC AND ENCLOSED RAFTER
 SPACES) PLAN SHEET S1.0 DETAIL F-2 THE ROOF INSULATION
 (R-30 PAPER BACK) DOES NOT APPEAR WITHIN ACCORDANCE OF
 THIS CODE SECTION. PLEASE CLARIFY BY CHANGING THE
 PRODUCT TO A FOAM SPRAY AND SHOWING HOW THE FOAM SPRAY
 WILL BE APPLIED IF THAT IS THE INTENTION.
  
 6.B.) FBC B 107.2.1, FOR THE WALL INSULATION (R-11
 PAPER BACK) WITHIN THE WOOD FRAMED WALL DETAIL F.1 ON
 PLAN SHEET S1.0, THIS DETAIL STILL INDICATES 2"X 4"
 WALL FRAMING. PLEASE CHANGE THE DETAIL TO INDICATE THE
 WALL FRAMING SIZE THAT WILL ACCOMODATE THE R-11 PAPER
 BACK INSULATION THICKNESS REQUIREMENT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-06 Cont ID  
Sent By jgomez Date 2022-10-06 Time 17:07 Rev Time 0.00
Received By jgomez Date 2022-10-06 Time 15:47 Sent To  
Notes
2022-10-06 17:07:20RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051247
 522 28TH ST
  
 NOTE:
 CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC.
 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING.
 ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND
 METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- DESIGNER OF RECORD TO PROVIDE ALL THE WIND DESIGN
 CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING
 EXPOSURE, BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE
 COMPONENTS AND CLADDING DESIGN PRESSURES. (DOORS,
 WINDOWS).
  
 RESPONSE:
 A)CLARIFY WHERE ARE THE WINDOW AND DOOR WIND PRESSURE
 LOADS TAKEN FROM? THEY ARE TOO LOW FOR A BUILDING IN
 EXPOSURE "C".
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
  
 B)WINDOW AND DOOR SCHEDULE SPECIFY D.P.R. PSI. WHAT IS
 THIS?.
 NOTE: DESIGN PRESSURES ARE GIVEN IN POUNDS PER SQUARE
 FEET NOT POUNDS PER SQUARE INCH. REVISE /CLARIFY. SEC.
 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 3- EGRESS DOOR. NEW HABITABLE ROOM NEEDS A SIDE HINGED
 DOOR LEADING DIRECTLY TO THE OUTSIDE. THE DOOR NEEDS TO
 PROVIDE A CLEAR WIDTH OPENING OF NOT LESS THAN 32
 INCHES. SEC. R311.2 FBC-RESIDENTIAL.
  
 RESPONSE:
 5'-0" DOUBLE HUNG DOESN'T COMPLY. NEED DOOR THAT
 PROVIDES AT LEAST 32" CLEAR WIDTH OPENING WHEN ONE LEAF
 IS OPEN.
  
 ORIGINAL COMMENT:
 4- PROVIDE PRODUCT APPROVAL FOR EXTERIOR SWING DOOR.
 SEE ITEM #2 ABOVE.
 SEC. 61G20.3.001 F.A.C.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 5- NEED TO SPECIFY FIRE RATED DOOR SHOWING COMPLIANCE
 WITH SEC. R311.2 FBC-RESIDENTIAL FOR DOOR LEADING FROM
 THE GARAGE TO THE HABITABLE ROOM.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 6- DESIGNER OF RECORD NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE. NEED TO SPECIFY INSULATION MATERIALS
 AND THEIR R-VALUES AT ROOF, WALLS, ETC. AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 STRUCTURAL DRAWING S1.0:
 A)DETAIL F.2 SHOWS R-30 PAPER BACK ROOF INSULATION.
 DETAIL IS NOT CLEAR HOW THE INSULATION IS INSTALLED.
 R-30 PAPER BACK INSULATION IS +/- 9-1/2" THICK. THIS
 INSULATION WILL COMPLETELY FILL THE 2X10 EXISTING ROOF
 JOIST.
 THEREFORE, THE DETAIL IS INCORRECT. DESIGNER OF RECORD
 TO SPECIFY IF THE ATTIC IS VENTED OR UNVENTED. IF
 VENTED, THEN THE INSULATION DOESN'T PROVIDE CROSS
 VENTILATION. THEREFORE IT DOESN'T WORK. IF NOT VENTED,
 THEN PROVIDE COMPLETE DETAIL SPECIFICATIONS FOR TYPE OF
 INSULATION SHOWING COMPLIANCE WITH SEC. R806.5
 FBC-RESIDENTIAL.
 NOTE: IF SPECIFYING SPRAY FOAM INSULATION, THEN PROVIDE
 ICC EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
  
 B)DETAIL F.1: R19 PAPER BACK INSULATION IS +/- 6-1/4"
 THICK. THEREFORE IT DOESN'T FIT ON A 2X4 WALL. REVISE
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 C)EXTERIOR WALL SPECIFICATIONS ON DETAIL F.2 DON'T
 SPECIFY INSULATION R-VALUE. ALSO, PROVIDE ICC
 EVALUATION REPORT FOR THE FOAM INSULATION TO VERIFY
 COMPLIANCE WITH SEC. R316 FBC-RESIDENTIAL.
  
 ORIGINAL COMMENT:
 7- PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING
 COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENT BASED ON NEW INFORMATION SUBMITTED:
 8- STRUCTURAL DETAILS ON SHEET S1.0 ARE NOT CLEAR AND
 ARE INCOMPLETE. SPECIFICATIONS FOR VERTICAL
 REINFORCEMENT AT THE END OF EACH OPENING IS NOT CLEAR.
 CLARIFY WHY DON'T SPECIFYING CONTINUOUS REINFORCEMENT
 FROM TOP TO BOTTOM. OVERLAP OF REBARS IS NOT SPECIFIED.
 THERE ARE NO SPECS SHOWING HOW THE END COLUMNS ARE
 FILLED.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 9- NEW HABITABLE ROOM NEEDS TO HAVE HEATING AS REQUIRED
 BY SEC. R303.10 FBC-RESIDENTIAL.
  
 10- DESIGNER OF RECORD NEEDS TO PROVIDE NAME AND
 SIGNATURE IN ALL DRAWINGS AS REQUIRED BY SEC. 107.2.1
 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By jgomez Date 2022-07-22 Time 19:27 Rev Time 0.00
Received By jgomez Date 2022-07-22 Time 17:46 Sent To  
Notes
2022-07-22 19:27:22RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22051247 522 28TH ST
  
 NOTE:
 CHANGE OF OCCUPANCY SEC. 605 AND SEC. 1001.2.1, SEC.
 604 AND SEC. 901.2, SEC. 801.3 FBC-EXISTING BUILDING.
 ALL NEW WORK SHALL COMPLY WITH THE MATERIALS AND
 METHODS REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- DESIGNER OF RECORD TO PROVIDE ALL THE WIND DESIGN
 CRITERIA AS REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL.
 SPECIFY THE ULTIMATE AND NOMINAL WIND LOAD, BUILDING
 EXPOSURE, BUILDING MEAN ROOF HEIGHT. ALSO, SPECIFY THE
 COMPONENTS AND CLADDING DESIGN PRESSURES. (DOORS,
 WINDOWS).
  
 3- EGRESS DOOR. NEW HABITABLE ROOM NEEDS A SIDE HINGED
 DOOR LEADING DIRECTLY TO THE OUTSIDE. THE DOOR NEEDS TO
 PROVIDE A CLEAR WIDTH OPENING OF NOT LESS THAN 32
 INCHES. SEC. R311.2 FBC-RESIDENTIAL.
  
 4- PROVIDE PRODUCT APPROVAL FOR EXTERIOR SWING DOOR.
 SEE ITEM #2 ABOVE.
 SEC. 61G20.3.001 F.A.C.
  
 5- NEED TO SPECIFY FIRE RATED DOOR SHOWING COMPLIANCE
 WITH SEC. R311.2 FBC-RESIDENTIAL FOR DOOR LEADING FROM
 THE GARAGE TO THE HABITABLE ROOM.
  
 6- DESIGNER OF RECORD NEEDS TO DEPICT THE BUILDING
 THERMAL ENVELOPE. NEED TO SPECIFY INSULATION MATERIALS
 AND THEIR R-VALUES AT ROOF, WALLS, ETC. AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
  
 7- PROVIDE SWING DOOR STRUCTURAL BUCK DETAIL SHOWING
 COMPLIANCE WITH SEC. R609.7.2.1 FBC-RESIDENTIAL.
 SPECIFY STRUCTURAL BUCK SIZE AND FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-05-26 Cont ID  
Sent By mpeterso Date 2023-05-26 Time 13:40 Rev Time 0.00
Received By mpeterso Date 2023-05-26 Time 13:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-05 Cont ID  
Sent By mpeterso Date 2022-10-05 Time 12:37 Rev Time 0.00
Received By mpeterso Date 2022-10-05 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-09 Cont ID  
Sent By mpeterso Date 2022-06-09 Time 10:27 Rev Time 0.00
Received By mpeterso Date 2022-06-09 Time 10:22 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2023-06-12 Cont ID  
Sent By fmittner Date 2023-06-12 Time 15:41 Rev Time 0.00
Received By fmittner Date 2023-06-12 Time 15:41 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2023-04-07 Cont ID  
Sent By amhamilt Date 2023-04-07 Time 11:01 Rev Time 0.00
Received By amhamilt Date 2023-04-07 Time 11:01 Sent To  
Notes
2023-04-07 11:02:55THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PROPOSED PLANS APPEAR TO INDICATE FRENCH DOOR RATHER
 THAN DOOR MAINTAINING APPEARANCE OF GARAGE. HISTORIC
 REQUIREMENT IS THAT A GARAGE DOOR APPEARANCE IS
 MAINTAINED.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By fmittner Date 2022-06-07 Time 12:12 Rev Time 0.00
Received By fmittner Date 2022-06-07 Time 12:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-06-26 Cont ID  
Sent By jgomez Date 2023-06-26 Time 19:10 Rev Time 0.00
Received By jgomez Date 2023-05-22 Time 16:44 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-04-10 Cont ID  
Sent By aoliver Date 2023-04-10 Time 07:58 Rev Time 0.00
Received By aoliver Date 2023-03-10 Time 12:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-02-22 Cont ID  
Sent By pvalenti Date 2023-02-22 Time 15:38 Rev Time 0.00
Received By pvalenti Date 2023-02-03 Time 12:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-06 Cont ID  
Sent By jgomez Date 2022-10-06 Time 17:09 Rev Time 0.00
Received By jgomez Date 2022-09-20 Time 08:08 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-17 Cont ID  
Sent By aoliver Date 2022-08-17 Time 06:57 Rev Time 0.00
Received By aoliver Date 2022-05-26 Time 07:16 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2023-06-26 Cont ID  
Sent By jgomez Date 2023-06-26 Time 19:09 Rev Time 0.00
Received By jgomez Date 2023-06-26 Time 19:09 Sent To  
Notes
2023-06-26 19:10:05PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected].
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-10-06 Cont ID  
Sent By jgomez Date 2022-10-06 Time 17:07 Rev Time 0.00
Received By jgomez Date 2022-10-06 Time 17:07 Sent To  
Notes
2022-10-06 17:07:50PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected].
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By shill Date 2022-07-22 Time 15:59 Rev Time 0.00
Received By shill Date 2022-07-22 Time 15:59 Sent To  
Notes
2022-07-22 15:59:27PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE EMAIL THE RECEIPT
 TO [email protected].
  
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2023-06-27 Cont ID  
Sent By cmontell Date 2023-06-05 Time 13:31 Rev Time 0.00
Received By cmontell Date 2023-06-27 Time 14:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2023-03-13 Cont ID  
Sent By medwards Date 2023-03-13 Time 07:43 Rev Time 0.00
Received By medwards Date 2023-03-13 Time 07:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2023-02-06 Cont ID  
Sent By medwards Date 2023-02-06 Time 06:38 Rev Time 0.00
Received By medwards Date 2023-02-06 Time 06:38 Sent To  
Notes
2023-02-06 06:42:19THE ENERGY CLACULATION/MECHANICAL EQUIPMENT SIZING
 CALCULATIONS ARE SPECIFYING A DAIKIN HEAT PUMP
 MINI-SPLIT. THIS WOULD MEET THE HEATING REQUIREMENTS OF
 FRC R303.10
  
 PLEASE ADDRESS THE HET REQUIREMENT FROM PREVIOUS
 REVIEWS BELOW:
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE THROUGH THE WALL SYSTEM MUST COMPLY WITH FRC
 R303.10 FOR HEATING THE ROOM. IT MUST ALSO COMPLY WITH
 THE FEC FOR ENERGY CALCULATIONS101.5, MECHANICAL
 EQUIPMENT SIZING CALCULATIONS R403.7, AND SEER RATING
 FROM TABLE C403.2.3;3 FEC FORM R402-2020
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-09-21 Cont ID  
Sent By medwards Date 2022-09-21 Time 08:24 Rev Time 0.00
Received By medwards Date 2022-09-21 Time 08:24 Sent To  
Notes
2022-09-21 08:24:392ND REVIEW FMC
 PERMIT: 22051247
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE THROUGH THE WALL SYSTEM MUST COMPLY WITH FRC
 R303.10 FOR HEATING THE ROOM. IT MUST ALSO COMPLY WITH
 THE FEC FOR ENERGY CALCULATIONS101.5, MECHANICAL
 EQUIPMENT SIZING CALCULATIONS R403.7, AND SEER RATING
 FROM TABLE C403.2.3;3 FEC FORM R402-2020
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 08:54 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 08:54 Sent To  
Notes
2022-05-27 08:56:07PROVIDE MECHANICAL DRAWING, MECHANICAL EQUIPMENT SIZING
 AND ENERGY CALCULATIONS FOR THIS NEW CONDITIONED SPACE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-05-28 Cont ID  
Sent By rwbrown Date 2022-05-28 Time 08:16 Rev Time 0.00
Received By rwbrown Date 2022-05-28 Time 08:16 Sent To  
Notes
2022-05-28 08:17:24NO PLUMBING INDICATED ON THE PLANS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-05-26 Cont ID  
Sent By mpeterso Date 2023-05-26 Time 13:41 Rev Time 0.00
Received By mpeterso Date 2023-05-26 Time 13:41 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status N Date 2023-02-22 Cont ID  
Sent By pvalenti Date 2023-02-22 Time 15:11 Rev Time 0.00
Received By pvalenti Date 2023-02-22 Time 11:01 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-10-06 Cont ID  
Sent By jgomez Date 2022-10-06 Time 17:08 Rev Time 0.00
Received By jgomez Date 2022-10-05 Time 12:37 Sent To  
Notes
2022-10-06 17:08:39NO ARCHITECT OR ENGINEER ON THIS SUBMITTAL. JG.
2022-10-05 12:41:4910/5/22 CONTRACTOR ELECTRIC DRAWING NOT REQUIRED. MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-09 Cont ID  
Sent By mpeterso Date 2022-06-09 Time 10:28 Rev Time 0.00
Received By mpeterso Date 2022-06-09 Time 10:27 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status N Date 2023-04-07 Cont ID  
Sent By amhamilt Date 2023-04-07 Time 11:03 Rev Time 0.00
Received By amhamilt Date 2023-04-07 Time 11:03 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2022-08-16 Cont ID  
Sent By ahamilto Date 2022-08-16 Time 16:37 Rev Time 0.00
Received By amhamilt Date 2022-08-16 Time 16:37 Sent To  
Notes
***NONE***