| Plan Review Stops For Permit 22051156 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-09-29 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-09-29 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2022-09-29 11:35:20 | AREA OF WORK IS FOR 1534 ELIZABETH AVE UPDATED PERMIT. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-09-22 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-09-22 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2022-09-22 15:27:24 | SUITE 2710 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE | | | PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR. | | | PLEASE EMAIL TO [email protected] FOR FURTHER | | | QUESTIONS YOU CAN ALSO CALL 561-805-6659 |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
3 |
Status |
P |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-21 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-21 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
F |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-06 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-06 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2022-09-06 10:12:57 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ASBESTOS REVIEW: | | | | | | 2ND REVIEW FAILED PLAN REVIEW, COMMERCIAL: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-07-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-13 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-13 |
Time |
14:54 |
Sent To |
|
|
| Notes |
| 2022-07-13 15:10:19 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ASBESTOS REVIEW: | | | | | | FAILED PLAN REVIEW, COMMERCIAL: | | | | | | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-10-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-10-03 |
Time |
07:00 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-10-03 |
Time |
06:28 |
Sent To |
|
|
| Notes |
| 2022-10-03 06:50:49 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WIYH PROVISO: | | | | | | 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE | | | ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN. | | | 34" MAX.). | | | 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION | | | PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT | | | LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA | | | BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS | | | MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING | | | FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2 | | | ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55 | | | OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED | | | STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER | | | PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS). | | | THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO | | | 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1. | | | APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD. | | | PLEASE REVISE PLAN SHEET A???1 OCCUPANT LOADS | | | (INCLUDING | | | STANDING AREA BEHIND BAR), PLAN SHEET A???2 SHOWING A | | | SEATING PLAN INDICATING UNCONCENTRATED TABLES AND | | | CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS | | | APPLICABLE. | | | 3.) FBC B 107.2.1, ON PLAN SHEET A???2 DOOR | | | SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS | | | A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN | | | THE PRODUCT APPROVAL. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-21 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-21 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2022-09-22 17:08:57 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISOS: | | | | | | 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE | | | ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN. | | | 34" MAX.). | | | 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION | | | PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT | | | LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA | | | BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS | | | MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING | | | FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2 | | | ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55 | | | OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED | | | STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER | | | PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS). | | | THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO | | | 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1. | | | APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD. | | | PLEASE REVISE PLAN SHEET A-1 OCCUPANT LOADS (INCLUDING | | | STANDING AREA BEHIND BAR), PLAN SHEET A-2 SHOWING A | | | SEATING PLAN INDICATING UNCONCENTRATED TABLES AND | | | CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS | | | APPLICABLE. | | | 3.) FBC B 107.2.1, ON PLAN SHEET A-2 DOOR | | | SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS | | | A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN | | | THE PRODUCT APPROVAL. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-06 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-06 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2022-09-06 15:10:55 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | THE CHANGE IN DIRECTION AT RAMP LANDINGS MUST BE AT | | | 60"X60". SEE PLAN SHEET A-5 MINIMUM. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-13 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-13 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2022-07-13 17:14:34 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVAL NUMBER | | | AND PRODUCT APPROVAL COVER SHEET FOR STORE FRONT DOORS. | | | ALSO, PROVIDE THE DESIGNER OF RECORD'S REVIEW STAMP | | | APPROVAL ON PRODUCT APPROVAL. | | | 2.) FBC B 1010.1.2.1, THE DOORS MUST SWING IN THE | | | DIRECTION OF EGRESS INCLUDING WINE TASTING ROOMS AND | | | LOUNGE AREA BACK DOOR. | | | 3.) FBC B 1014.6, THE HANDRAIL DETAILS NEED TO SHOW THE | | | 12" EXTENSIONS WHERE TERMINATING. | | | 4.) FBC B 1607.8.1 & FBC B 1607.8.8.1, THE HANDRAIL | | | DETAILS NEED TO INDICATE THAT THEY CAN RESIST LINEAR | | | LOADS OF 50 POUNDS AND A CONCENTRATED LOAD OF 200 | | | POUNDS. | | | 5.) FBC B 1604.8.3 & FBC B 1607.4, THE DECK DETAILS | | | NEED TO INDICATE THAT THE REQUIRED VERTICAL, LATERAL, & | | | CONCENTRATED LIVE LOADS ARE BEING MET. SEE FBC B TABLE | | | 1607.1 | | | 6.) FBC A 902.3, THE DINING SURFACE/BAR MUST SHOW | | | COMPLIANCE WITH THE ACCESSIBILITY CODE. | | | 7.) FBC B 1012.6.4, THE RAMP LANDING AT THE CHANGE OF | | | DIRECTION NEEDS TO INDICATE A MINIMUM SIZE OF 60" X | | | 60". | | | 8.) FBC B 2304.10, PROVIDE ON PLANS THE FASTENERS AND | | | CONNECTORS THAT WILL BE USED FOR DECK CONSTRUCTION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-08-23 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-23 |
Time |
20:05 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-08-23 |
Time |
19:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-06-29 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-06-29 |
Time |
23:37 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-06-29 |
Time |
22:51 |
Sent To |
|
|
| Notes |
| 2022-06-29 23:37:23 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT | | | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 | | | | | | ALL THAT IS SHOWN IS THE REFERENCED CODE ARTICLE ON | | | PLAN. | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | | | | | | | | | | PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS | | | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT | | | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-08-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-18 13:21:22 | FIRE REVIEW COMMENT: | | | | | | DOOR C, THE REAR PATIO DOOR, THE DOOR LEAF SWING IS | | | ENCROACHING INTO THE MEANS OF EGRESS WIDTH. | | | | | | 7.2.1.4.3* DOOR LEAF ENCROACHMENT. | | | 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS | | | OF | | | EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE | | | REQUIRED WIDTH | | | OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING | | | UNOBSTRUCTED, | | | UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET: | | | (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN | | | EXISTING | | | BUILDING. | | | (2) THE DOOR OPENING MEETS THE REQUIREMENT OF | | | 7.2.1.4.3.2. | | | 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS | | | OF | | | EGRESS SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO | | | THE | | | REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, | | | OR A LANDING, | | | UNLESS THE DOOR LEAF IS EQUIPPED WITH AN APPROVED | | | SELF-CLOSING | | | DEVICE AND IS NOT REQUIRED BY THE PROVISIONS OF | | | 7.2.1.4.2 | | | TO SWING IN THE DIRECTION OF EGRESS TRAVEL. | | | 7.2.1.4.3.3 SURFACE-MOUNTED LATCH RELEASE HARDWARE ON | | | THE | | | DOOR LEAF SHALL BE EXEMPT FROM BEING INCLUDED IN THE | | | MAXIMUM | | | 7 IN. (180 MM) PROJECTION REQUIREMENT OF 7.2.1.4.3.1, | | | PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET: | | | (1) THE HARDWARE IS MOUNTED TO THE SIDE OF THE DOOR | | | LEAF THAT | | | FACES THE AISLE, CORRIDOR, PASSAGEWAY, OR LANDING WHEN | | | THE | | | DOOR LEAF IS IN THE OPEN POSITION. | | | (2) THE HARDWARE IS MOUNTED NOT LESS THAN 34 IN. (865 | | | MM), | | | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-06-17 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-06-17 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-17 10:22:24 | FIRE REVIEW COMMENTS: | | | | | | 1.)ALL REQUIRED EXIT DOORS SHALL SWING IN THE DIRECTION | | | OF EGRESS TRAVEL. NFPA 101 7.2.2.3.2 | | | | | | 2.)PROVIDE DETAIL OF EXIT DOOR LOCKING ARRANGEMENTS TO | | | COMPLY WITH NFPA 101 7.2.1.5.5 | | | | | | 3.)PROVIDE STAIR AND LANDING DETAILS TO COMPLY WITH | | | NFPA 101 7.2.2.3.2 | | | | | | 4.)PROVIDE HANDRAIL DETAILS TO COMPLY WITH NFPA 101 | | | 7.2.2.4 | | | | | | C. WALKER | | | | | | 561-804-4762 | | | | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-10-03 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-10-03 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-29 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-21 |
Time |
14:07 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-08 |
Time |
12:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-06 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-17 |
Time |
14:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-13 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-06-16 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-29 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-29 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-16 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-16 |
Time |
08:14 |
Sent To |
|
|
| Notes |
| 2022-09-16 08:19:24 | PLEASE SEE BELOW, THE OUTDOOR AIR CALCULATIONS FOR THIS | | | OCCUPANCY MUST BE CALCULATED BY USING FMC 403.3.1.1 AND | | | TABLE 403.3.1.1 | | | | | | | | | OCCUPANCY CLASSIFICATION SQUARE | | | FOOTAGE SQFT/1000 OCCUPANT DENSITY #/1000 FT2 (A) TOTAL | | | OCCUPANTS PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING | | | ZONE,RP?? CFM/PERSON OUTDOOR AIRFLOW RATE IN BREATHING | | | ZONE, CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN | | | BREATHING ZONE,RA?? CFM/FT2 (A) AREA OUTDOOR AIRFLOW | | | RATE "TOTAL OUTDOOR AIR REQUIRED | | | " | | | BARS, COCKTAIL | | | LOUNGES 144 0.144 100 15 7.5 112.5 0.18 25.92 138.42 | | | BARS, COCKTAIL | | | LOUNGES 272 0.272 100 28 7.5 210 0.18 48.96 258.96 | | | KITCHENS (COOKING) | | | (B) 92 0.092 20 2 7.5 15 0.12 11.04 26.04 | | | KITCHENS (COOKING) | | | (B) 182 0.182 20 4 7.5 30 0.12 21.84 51.84 | | | MAIN ENTRY LOBBIES 245 0.245 10 3 5 15 0.06 14.7 29.7 | | | CORRIDORS 80 0.08 - 0 - 0 0.06 4.8 4.8 | | | TOTALS 1,015 510 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-18 |
Time |
08:26 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-18 |
Time |
08:26 |
Sent To |
|
|
| Notes |
| 2022-08-18 08:26:56 | 2ND REVIEW FMC | | | PERMIT: 22051156 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE INFORMATION AS TO WHAT KINDS OF FOOD | | | WILL BE SERVED IN THIS BAR. FBC 107.3.5 | | | | | | 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON | | | FMC 403.3.1.1 AND TABLE 403.3.1.1 THE TABLE WILL | | | PROVIDE THE OCCUPANT COUNT PER EACH USE OF SPACE. | | | PLEASE DO NOT USE THE ARCHITECTURAL EGRESS COUNTS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-21 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-21 |
Time |
13:46 |
Sent To |
|
|
| Notes |
| 2022-06-21 13:46:35 | 1ST REVIEW FMC | | | PERMIT: 22051156 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IDENTIFY RTU?S ON THE DRAWING. FBC 107.2.1 | | | | | | 2) FRONT BATH EXHAUST FAN DOES NOT SHOW WHERE THE | | | EXHAUST TERMINATION LOCATION WILL BE, REVISE PLAN TO | | | SHOW THE TERMINATION LOCATION. FMC 501.3.1 | | | | | | 3) PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH USE OF | | | SPACE IDENTIFIED WITH AN OCCUPANCY CLASSIFICATION FROM | | | FMC TABLE 403.3.1.1; EXAMPLE- LOUNGE AREA AND TASTING | | | ROOMS ARE NOT AN OCCUPANCY CLASSIFICATION FROM TABLE | | | 403.3.1.1 | | | | | | 4) REVISE PLAN TO SHOW THE REQUIRED EXHAUST FOR THE | | | KITCHEN/FOOD PREP AREA. FMC TABLE 403.3.1.1 | | | | | | 5) PROVIDE A ROOF PLAN SHOWING THE LOCATION OF THE NEW | | | RTU AND ANY GUARDS THAT MAY BE REQUIRED. FBC 107.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
3 |
Status |
N |
Date |
2022-09-24 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-21 |
Time |
14:05 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-21 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2022-09-21 15:25:50 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | NFIP REVIEW: | | | | | | THERE DOES NOT APPEAR TO BE A SUBSTANTIAL IMPROVEMENT | | | AT THIS LOCATION CONSIDERING AN ASSESSED VALUE OF | | | $1,742,833.00 (PER THE PROPERTY APPRAISERS SITE) AND A | | | TOTAL VALUE OF IMPROVEMENTS THAT IS LESS THAN 50% OF | | | THE ASSESSED VALUE FROM WITHIN THE LAST 5 YEARS. | | | | | | PLEASE SEE THE FOLLOWING 5 YEAR ACCRUAL BREAK DOWN OF | | | IMPROVEMENTS: | | | | | | $150,000.00 PERMIT # 22051156, CURRENT RENOVATION IN | | | APPLICATION. | | | $ 10,000.00 PERMIT # 21071663, CAR CHARGER | | | INSTALLATION. | | | $ 44,980.00 PERMIT # 20050754, STOREFRONT REPLACEMENT. | | | $ 23,862.00 PERMIT # 20021301, (2) NEW STAIRS. | | | $ 700.00 PERMIT # 20010701, BACKFLOW. | | | $ 3,230.00 PERMIT # 19111199, GAS LINES FOR HEATER. | | | $ 1,000.00 PERMIT # 19111171, BACKFLOW. | | | $ 25,000.00 PERMIT # 19110599, GREASE TRAP. | | | $ 4,000.00 PERMIT # 19100903, SIGN. | | | $ 1,100.00 PERMIT # 19100901, SIGN. | | | $508,072.00 PERMIT # 19040126, TENANT BUILDOUT FOR | | | SALON. | | | | | | TOTAL OF $771,944.00. | | | | | | THIS TOTAL IS LESS THAN 50% OF CURRENT ASSESSED VALUE | | | OF $1,742,833.00 (50% OF VALUE=$871,416.50). | | | | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
F |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-06 |
Time |
15:14 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-06 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2022-09-06 15:15:01 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | 2ND NFIP REVIEW DENIED: | | | | | | AS THIS PROPERTY APPEARS TO BE IN A FLOOD ZONE (A/E), | | | PLEASE PROVIDE A COMPLETED ELEVATION CERTIFICATE AND A | | | SURVEY SHOWING ELEVATIONS. |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2022-07-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-13 |
Time |
17:22 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-13 |
Time |
17:22 |
Sent To |
|
|
| Notes |
| 2022-07-13 17:24:31 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | NFIP REVIEW DENIED: | | | | | | AS THIS PROPERTY APPEARS TO BE IN A FLOOD ZONE (A/E), | | | PLEASE PROVIDE A COMPLETED ELEVATION CERTIFICATE AND A | | | SURVEY SHOWING ELEVATIONS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-09-30 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-30 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-16 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-18 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-18 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2022-08-18 08:39:19 | 2ND PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. THE WATER DIAGRAM SHOULD REFLECT THE CHANGE. IT | | | MIGHT BE HELPFUL TO ALSO INCLUDE A DETAIL OF THE WATER | | | HEATER SO AS TO SHOW THE PROPER RETURN AND | | | CONFIGURATION OF THE CIRCULATION LOOP. YOU COULD ALSO | | | DETAIL THE CONNECTIONS AT THE LAVATORIES SHOWING THE | | | COMPLIANCE WITH ASSE 1070 -------------2017 WPB AMENDS | | | 107.3.5.1.3(3) - PLEASE SUPPLY A WATER PIPING DIAGRAM. | | | INCLUDE DETAILS OF HOT WATER PROTECTION AS WELL AS | | | TEMPERED WATER PROTECTION IN COMPLIANCE WITH FPC | | | 607.1.1 AND 607.1.2. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-06-21 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-06-21 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2022-06-21 14:16:44 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.3.5.1.3(3) - PLEASE SUPPLY A | | | WATER PIPING DIAGRAM. INCLUDE DETAILS OF HOT WATER | | | PROTECTION AS WELL AS TEMPERED WATER PROTECTION IN | | | COMPLIANCE WITH FPC 607.1.1 AND 607.1.2. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-29 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-29 |
Time |
16:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-21 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-21 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-18 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-18 |
Time |
08:28 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-18 |
Time |
08:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-07-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-07-13 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-07-13 |
Time |
15:53 |
Sent To |
|
|
| Notes |
| 2022-07-13 16:25:08 | SIGNATURE REVIEW DENIED: | | | | | | PLEASE PROVIDE THE TITLE AND LICENSE NUMBER FOR THE | | | DESIGN PROFESSIONAL AS A THIRD PARTY VERIFICATION OF | | | DIGITAL SIGNATURES IS REQUIRED FOR PROFESSIONAL | | | ENGINEERS. | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|