Plan Review Details - Permit 22051156
Plan Review Stops For Permit 22051156
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-09-29 Cont ID  
Sent By cpuell Date 2022-09-29 Time 11:35 Rev Time 0.00
Received By cpuell Date 2022-09-29 Time 11:34 Sent To  
Notes
2022-09-29 11:35:20AREA OF WORK IS FOR 1534 ELIZABETH AVE UPDATED PERMIT.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-09-22 Cont ID  
Sent By cpuell Date 2022-09-22 Time 15:26 Rev Time 0.00
Received By cpuell Date 2022-09-22 Time 15:26 Sent To  
Notes
2022-09-22 15:27:24SUITE 2710 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 PLEASE EMAIL TO [email protected] FOR FURTHER
 QUESTIONS YOU CAN ALSO CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-09-21 Cont ID  
Sent By pvalenti Date 2022-09-21 Time 13:39 Rev Time 0.00
Received By pvalenti Date 2022-09-21 Time 13:33 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-09-06 Cont ID  
Sent By pvalenti Date 2022-09-06 Time 10:12 Rev Time 0.00
Received By pvalenti Date 2022-09-06 Time 09:49 Sent To  
Notes
2022-09-06 10:12:57PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW:
  
 2ND REVIEW FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By pvalenti Date 2022-07-13 Time 15:02 Rev Time 0.00
Received By pvalenti Date 2022-07-13 Time 14:54 Sent To  
Notes
2022-07-13 15:10:19PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 ASBESTOS REVIEW:
  
 FAILED PLAN REVIEW, COMMERCIAL:
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-10-03 Cont ID  
Sent By pvalenti Date 2022-10-03 Time 07:00 Rev Time 0.00
Received By pvalenti Date 2022-10-03 Time 06:28 Sent To  
Notes
2022-10-03 06:50:49PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WIYH PROVISO:
  
 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE
 ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN.
 34" MAX.).
 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION
 PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT
 LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA
 BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS
 MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING
 FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2
 ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55
 OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED
 STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER
 PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS).
 THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO
 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1.
 APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD.
 PLEASE REVISE PLAN SHEET A???1 OCCUPANT LOADS
 (INCLUDING
 STANDING AREA BEHIND BAR), PLAN SHEET A???2 SHOWING A
 SEATING PLAN INDICATING UNCONCENTRATED TABLES AND
 CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS
 APPLICABLE.
 3.) FBC B 107.2.1, ON PLAN SHEET A???2 DOOR
 SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS
 A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN
 THE PRODUCT APPROVAL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-24 Cont ID  
Sent By pvalenti Date 2022-09-21 Time 13:33 Rev Time 0.00
Received By pvalenti Date 2022-09-21 Time 13:33 Sent To  
Notes
2022-09-22 17:08:57PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISOS:
  
 1.) FBC A 902.1, THE BAR HEIGHT MUST BE INCLUDED IN THE
 ACCESSIBLE REQUIREMENT FOR DINING SURFACES (28" MIN.
 34" MAX.).
 2.) FBC B TABLES 1004.5 & 2902.1, AT TIME OF INSPECTION
 PLANS MUST BE REVISED TO INCLUDE THE ACCURATE OCCUPANT
 LOADS FOR OUTDOOR SEATING AREAS AND STANDING AREA
 BEHIND THE BAR PER THE INDICATED SQUARE FOOTAGE. THIS
 MAY REQUIRE THE NEED FOR MORE BATHROOM/PLUMBING
 FIXTURES (FBC B TABLE 2902.1) AS IT APPEARS THE A2
 ASSEMBLY/OCCUPANCY NUMBER WILL GO FROM 816 S.F./55
 OCCUPANTS TO 1627 S.F./109 OCCUPANTS AND THE REQUIRED
 STANDING AREA BEHIND BAR WILL CHANGE FROM 15 S.F. PER
 PERSON TO=(3 PERSONS) TO 5 S.F. PER PERSON=(9 PERSONS).
 THIS NUMBER MAY BE ABLE TO BE INCREASED FROM FROM 5 TO
 7 S.F. PER PERSON=(7 PERSONS) AS PER FBC 1004.5.1.
 APPARENTLY THIS WILL INCREASE THE TOTAL OCCUPANT LOAD.
 PLEASE REVISE PLAN SHEET A-1 OCCUPANT LOADS (INCLUDING
 STANDING AREA BEHIND BAR), PLAN SHEET A-2 SHOWING A
 SEATING PLAN INDICATING UNCONCENTRATED TABLES AND
 CHAIRS AS APPLICABLE AND PLUMBING PLAN SHEETS AS
 APPLICABLE.
 3.) FBC B 107.2.1, ON PLAN SHEET A-2 DOOR
 SCHEDULE(REMARKS), PLEASE SHOW PANIC HARDWARE FOR DOORS
 A&E THAT WILL BE USED AND INDICATE THIS OPTION WITHIN
 THE PRODUCT APPROVAL.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By pvalenti Date 2022-09-06 Time 15:02 Rev Time 0.00
Received By pvalenti Date 2022-09-06 Time 09:49 Sent To  
Notes
2022-09-06 15:10:55PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 THE CHANGE IN DIRECTION AT RAMP LANDINGS MUST BE AT
 60"X60". SEE PLAN SHEET A-5 MINIMUM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By pvalenti Date 2022-07-13 Time 16:27 Rev Time 0.00
Received By pvalenti Date 2022-07-13 Time 15:53 Sent To  
Notes
2022-07-13 17:14:34PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 1.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVAL NUMBER
 AND PRODUCT APPROVAL COVER SHEET FOR STORE FRONT DOORS.
 ALSO, PROVIDE THE DESIGNER OF RECORD'S REVIEW STAMP
 APPROVAL ON PRODUCT APPROVAL.
 2.) FBC B 1010.1.2.1, THE DOORS MUST SWING IN THE
 DIRECTION OF EGRESS INCLUDING WINE TASTING ROOMS AND
 LOUNGE AREA BACK DOOR.
 3.) FBC B 1014.6, THE HANDRAIL DETAILS NEED TO SHOW THE
 12" EXTENSIONS WHERE TERMINATING.
 4.) FBC B 1607.8.1 & FBC B 1607.8.8.1, THE HANDRAIL
 DETAILS NEED TO INDICATE THAT THEY CAN RESIST LINEAR
 LOADS OF 50 POUNDS AND A CONCENTRATED LOAD OF 200
 POUNDS.
 5.) FBC B 1604.8.3 & FBC B 1607.4, THE DECK DETAILS
 NEED TO INDICATE THAT THE REQUIRED VERTICAL, LATERAL, &
 CONCENTRATED LIVE LOADS ARE BEING MET. SEE FBC B TABLE
 1607.1
 6.) FBC A 902.3, THE DINING SURFACE/BAR MUST SHOW
 COMPLIANCE WITH THE ACCESSIBILITY CODE.
 7.) FBC B 1012.6.4, THE RAMP LANDING AT THE CHANGE OF
 DIRECTION NEEDS TO INDICATE A MINIMUM SIZE OF 60" X
 60".
 8.) FBC B 2304.10, PROVIDE ON PLANS THE FASTENERS AND
 CONNECTORS THAT WILL BE USED FOR DECK CONSTRUCTION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-23 Cont ID  
Sent By fgiaquin Date 2022-08-23 Time 20:05 Rev Time 0.00
Received By fgiaquin Date 2022-08-23 Time 19:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By fgiaquin Date 2022-06-29 Time 23:37 Rev Time 0.00
Received By fgiaquin Date 2022-06-29 Time 22:51 Sent To  
Notes
2022-06-29 23:37:23ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2
  
 ALL THAT IS SHOWN IS THE REFERENCED CODE ARTICLE ON
 PLAN.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  
  
 PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-09-19 Cont ID  
Sent By cwalker Date 2022-09-19 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2022-08-18 Cont ID  
Sent By cwalker Date 2022-08-18 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-08-18 13:21:22FIRE REVIEW COMMENT:
  
 DOOR C, THE REAR PATIO DOOR, THE DOOR LEAF SWING IS
 ENCROACHING INTO THE MEANS OF EGRESS WIDTH.
  
 7.2.1.4.3* DOOR LEAF ENCROACHMENT.
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF
 EGRESS SHALL LEAVE NOT LESS THAN ONE-HALF OF THE
 REQUIRED WIDTH
 OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A LANDING
 UNOBSTRUCTED,
 UNLESS BOTH OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF
 EGRESS SHALL NOT PROJECT MORE THAN 7 IN. (180 MM) INTO
 THE
 REQUIRED WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY,
 OR A LANDING,
 UNLESS THE DOOR LEAF IS EQUIPPED WITH AN APPROVED
 SELF-CLOSING
 DEVICE AND IS NOT REQUIRED BY THE PROVISIONS OF
 7.2.1.4.2
 TO SWING IN THE DIRECTION OF EGRESS TRAVEL.
 7.2.1.4.3.3 SURFACE-MOUNTED LATCH RELEASE HARDWARE ON
 THE
 DOOR LEAF SHALL BE EXEMPT FROM BEING INCLUDED IN THE
 MAXIMUM
 7 IN. (180 MM) PROJECTION REQUIREMENT OF 7.2.1.4.3.1,
 PROVIDED THAT BOTH OF THE FOLLOWING CRITERIA ARE MET:
 (1) THE HARDWARE IS MOUNTED TO THE SIDE OF THE DOOR
 LEAF THAT
 FACES THE AISLE, CORRIDOR, PASSAGEWAY, OR LANDING WHEN
 THE
 DOOR LEAF IS IN THE OPEN POSITION.
 (2) THE HARDWARE IS MOUNTED NOT LESS THAN 34 IN. (865
 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-17 Cont ID  
Sent By cwalker Date 2022-06-17 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-06-17 10:22:24FIRE REVIEW COMMENTS:
  
 1.)ALL REQUIRED EXIT DOORS SHALL SWING IN THE DIRECTION
 OF EGRESS TRAVEL. NFPA 101 7.2.2.3.2
  
 2.)PROVIDE DETAIL OF EXIT DOOR LOCKING ARRANGEMENTS TO
 COMPLY WITH NFPA 101 7.2.1.5.5
  
 3.)PROVIDE STAIR AND LANDING DETAILS TO COMPLY WITH
 NFPA 101 7.2.2.3.2
  
 4.)PROVIDE HANDRAIL DETAILS TO COMPLY WITH NFPA 101
 7.2.2.4
  
 C. WALKER
  
 561-804-4762
  
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-10-03 Cont ID  
Sent By pvalenti Date 2022-10-03 Time 07:40 Rev Time 0.00
Received By pvalenti Date 2022-09-29 Time 13:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-21 Cont ID  
Sent By pvalenti Date 2022-09-21 Time 14:07 Rev Time 0.00
Received By pvalenti Date 2022-09-08 Time 12:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-06 Cont ID  
Sent By pvalenti Date 2022-09-06 Time 15:15 Rev Time 0.00
Received By pvalenti Date 2022-08-17 Time 14:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-13 Cont ID  
Sent By pvalenti Date 2022-07-13 Time 17:27 Rev Time 0.00
Received By pvalenti Date 2022-06-16 Time 15:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-09-29 Cont ID  
Sent By medwards Date 2022-09-29 Time 16:27 Rev Time 0.00
Received By medwards Date 2022-09-29 Time 16:27 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-09-16 Cont ID  
Sent By medwards Date 2022-09-16 Time 08:14 Rev Time 0.00
Received By medwards Date 2022-09-16 Time 08:14 Sent To  
Notes
2022-09-16 08:19:24PLEASE SEE BELOW, THE OUTDOOR AIR CALCULATIONS FOR THIS
 OCCUPANCY MUST BE CALCULATED BY USING FMC 403.3.1.1 AND
 TABLE 403.3.1.1
  
  
 OCCUPANCY CLASSIFICATION SQUARE
 FOOTAGE SQFT/1000 OCCUPANT DENSITY #/1000 FT2 (A) TOTAL
 OCCUPANTS PEOPLE OUTDOOR AIRFLOW RATE IN BREATHING
 ZONE,RP?? CFM/PERSON OUTDOOR AIRFLOW RATE IN BREATHING
 ZONE, CFM/PERSON AREA OUTDOOR AIRFLOW RATE IN
 BREATHING ZONE,RA?? CFM/FT2 (A) AREA OUTDOOR AIRFLOW
 RATE "TOTAL OUTDOOR AIR REQUIRED
 "
 BARS, COCKTAIL
 LOUNGES 144 0.144 100 15 7.5 112.5 0.18 25.92 138.42
 BARS, COCKTAIL
 LOUNGES 272 0.272 100 28 7.5 210 0.18 48.96 258.96
 KITCHENS (COOKING)
 (B) 92 0.092 20 2 7.5 15 0.12 11.04 26.04
 KITCHENS (COOKING)
 (B) 182 0.182 20 4 7.5 30 0.12 21.84 51.84
 MAIN ENTRY LOBBIES 245 0.245 10 3 5 15 0.06 14.7 29.7
 CORRIDORS 80 0.08 - 0 - 0 0.06 4.8 4.8
 TOTALS 1,015 510
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-18 Cont ID  
Sent By medwards Date 2022-08-18 Time 08:26 Rev Time 0.00
Received By medwards Date 2022-08-18 Time 08:26 Sent To  
Notes
2022-08-18 08:26:562ND REVIEW FMC
 PERMIT: 22051156
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE INFORMATION AS TO WHAT KINDS OF FOOD
 WILL BE SERVED IN THIS BAR. FBC 107.3.5
  
 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 FMC 403.3.1.1 AND TABLE 403.3.1.1 THE TABLE WILL
 PROVIDE THE OCCUPANT COUNT PER EACH USE OF SPACE.
 PLEASE DO NOT USE THE ARCHITECTURAL EGRESS COUNTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-06-21 Cont ID  
Sent By medwards Date 2022-06-21 Time 13:46 Rev Time 0.00
Received By medwards Date 2022-06-21 Time 13:46 Sent To  
Notes
2022-06-21 13:46:351ST REVIEW FMC
 PERMIT: 22051156
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IDENTIFY RTU?S ON THE DRAWING. FBC 107.2.1
  
 2) FRONT BATH EXHAUST FAN DOES NOT SHOW WHERE THE
 EXHAUST TERMINATION LOCATION WILL BE, REVISE PLAN TO
 SHOW THE TERMINATION LOCATION. FMC 501.3.1
  
 3) PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH USE OF
 SPACE IDENTIFIED WITH AN OCCUPANCY CLASSIFICATION FROM
 FMC TABLE 403.3.1.1; EXAMPLE- LOUNGE AREA AND TASTING
 ROOMS ARE NOT AN OCCUPANCY CLASSIFICATION FROM TABLE
 403.3.1.1
  
 4) REVISE PLAN TO SHOW THE REQUIRED EXHAUST FOR THE
 KITCHEN/FOOD PREP AREA. FMC TABLE 403.3.1.1
  
 5) PROVIDE A ROOF PLAN SHOWING THE LOCATION OF THE NEW
 RTU AND ANY GUARDS THAT MAY BE REQUIRED. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status N Date 2022-09-24 Cont ID  
Sent By pvalenti Date 2022-09-21 Time 14:05 Rev Time 0.00
Received By pvalenti Date 2022-09-21 Time 14:05 Sent To  
Notes
2022-09-21 15:25:50PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 NFIP REVIEW:
  
 THERE DOES NOT APPEAR TO BE A SUBSTANTIAL IMPROVEMENT
 AT THIS LOCATION CONSIDERING AN ASSESSED VALUE OF
 $1,742,833.00 (PER THE PROPERTY APPRAISERS SITE) AND A
 TOTAL VALUE OF IMPROVEMENTS THAT IS LESS THAN 50% OF
 THE ASSESSED VALUE FROM WITHIN THE LAST 5 YEARS.
  
 PLEASE SEE THE FOLLOWING 5 YEAR ACCRUAL BREAK DOWN OF
 IMPROVEMENTS:
  
 $150,000.00 PERMIT # 22051156, CURRENT RENOVATION IN
 APPLICATION.
 $ 10,000.00 PERMIT # 21071663, CAR CHARGER
 INSTALLATION.
 $ 44,980.00 PERMIT # 20050754, STOREFRONT REPLACEMENT.
 $ 23,862.00 PERMIT # 20021301, (2) NEW STAIRS.
 $ 700.00 PERMIT # 20010701, BACKFLOW.
 $ 3,230.00 PERMIT # 19111199, GAS LINES FOR HEATER.
 $ 1,000.00 PERMIT # 19111171, BACKFLOW.
 $ 25,000.00 PERMIT # 19110599, GREASE TRAP.
 $ 4,000.00 PERMIT # 19100903, SIGN.
 $ 1,100.00 PERMIT # 19100901, SIGN.
 $508,072.00 PERMIT # 19040126, TENANT BUILDOUT FOR
 SALON.
  
 TOTAL OF $771,944.00.
  
 THIS TOTAL IS LESS THAN 50% OF CURRENT ASSESSED VALUE
 OF $1,742,833.00 (50% OF VALUE=$871,416.50).
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2022-09-06 Cont ID  
Sent By pvalenti Date 2022-09-06 Time 15:14 Rev Time 0.00
Received By pvalenti Date 2022-09-06 Time 15:14 Sent To  
Notes
2022-09-06 15:15:01PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 2ND NFIP REVIEW DENIED:
  
 AS THIS PROPERTY APPEARS TO BE IN A FLOOD ZONE (A/E),
 PLEASE PROVIDE A COMPLETED ELEVATION CERTIFICATE AND A
 SURVEY SHOWING ELEVATIONS.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By pvalenti Date 2022-07-13 Time 17:22 Rev Time 0.00
Received By pvalenti Date 2022-07-13 Time 17:22 Sent To  
Notes
2022-07-13 17:24:31PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 NFIP REVIEW DENIED:
  
 AS THIS PROPERTY APPEARS TO BE IN A FLOOD ZONE (A/E),
 PLEASE PROVIDE A COMPLETED ELEVATION CERTIFICATE AND A
 SURVEY SHOWING ELEVATIONS.

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-09-30 Cont ID  
Sent By rwbrown Date 2022-09-30 Time 12:57 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-09-16 Cont ID  
Sent By rwbrown Date 2022-09-16 Time 11:47 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-08-18 Cont ID  
Sent By rwbrown Date 2022-08-18 Time 08:33 Rev Time 0.00
Received By rwbrown Date 2022-08-18 Time 08:30 Sent To  
Notes
2022-08-18 08:39:192ND PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. THE WATER DIAGRAM SHOULD REFLECT THE CHANGE. IT
 MIGHT BE HELPFUL TO ALSO INCLUDE A DETAIL OF THE WATER
 HEATER SO AS TO SHOW THE PROPER RETURN AND
 CONFIGURATION OF THE CIRCULATION LOOP. YOU COULD ALSO
 DETAIL THE CONNECTIONS AT THE LAVATORIES SHOWING THE
 COMPLIANCE WITH ASSE 1070 -------------2017 WPB AMENDS
 107.3.5.1.3(3) - PLEASE SUPPLY A WATER PIPING DIAGRAM.
 INCLUDE DETAILS OF HOT WATER PROTECTION AS WELL AS
 TEMPERED WATER PROTECTION IN COMPLIANCE WITH FPC
 607.1.1 AND 607.1.2.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-06-21 Cont ID  
Sent By rwbrown Date 2022-06-21 Time 14:16 Rev Time 0.00
Received By rwbrown Date 2022-06-21 Time 14:07 Sent To  
Notes
2022-06-21 14:16:441ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.3(3) - PLEASE SUPPLY A
 WATER PIPING DIAGRAM. INCLUDE DETAILS OF HOT WATER
 PROTECTION AS WELL AS TEMPERED WATER PROTECTION IN
 COMPLIANCE WITH FPC 607.1.1 AND 607.1.2.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-09-29 Cont ID  
Sent By medwards Date 2022-09-29 Time 16:33 Rev Time 0.00
Received By medwards Date 2022-09-29 Time 16:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-21 Cont ID  
Sent By pvalenti Date 2022-09-21 Time 13:55 Rev Time 0.00
Received By pvalenti Date 2022-09-21 Time 13:39 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-18 Cont ID  
Sent By medwards Date 2022-08-18 Time 08:28 Rev Time 0.00
Received By medwards Date 2022-08-18 Time 08:28 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-13 Cont ID  
Sent By pvalenti Date 2022-07-13 Time 16:19 Rev Time 0.00
Received By pvalenti Date 2022-07-13 Time 15:53 Sent To  
Notes
2022-07-13 16:25:08SIGNATURE REVIEW DENIED:
  
 PLEASE PROVIDE THE TITLE AND LICENSE NUMBER FOR THE
 DESIGN PROFESSIONAL AS A THIRD PARTY VERIFICATION OF
 DIGITAL SIGNATURES IS REQUIRED FOR PROFESSIONAL
 ENGINEERS.
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  