Plan Review Details - Permit 22051128
Plan Review Stops For Permit 22051128
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-05-26 Cont ID  
Sent By cpuell Date 2022-05-26 Time 11:45 Rev Time 0.00
Received By cpuell Date 2022-05-26 Time 11:45 Sent To  
Notes
2022-05-26 11:46:17ADDRESS APPROPRIATE FOR PROJECT.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By mpeterso Date 2023-05-31 Time 09:27 Rev Time 0.00
Received By mpeterso Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-25 Cont ID  
Sent By mpeterso Date 2023-01-25 Time 13:30 Rev Time 0.00
Received By mpeterso Date 2023-01-25 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-30 Cont ID  
Sent By mpeterso Date 2022-06-30 Time 10:50 Rev Time 0.00
Received By mpeterso Date 2022-06-30 Time 10:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-14 Cont ID  
Sent By mpeterso Date 2022-06-14 Time 13:34 Rev Time 0.00
Received By mpeterso Date 2022-06-14 Time 13:34 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2023-04-14 Cont ID  
Sent By eschneid Date 2023-04-14 Time 13:51 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2023-04-14 13:51:40ENGINEERING REVIEW UNDER WCF ROW 21120228

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-06-17 Cont ID  
Sent By eschneid Date 2022-06-17 Time 15:13 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2022-06-17 15:13:47ENGINEERING REVIEW UNDER WCF ROW 21120228

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2023-06-29 Cont ID  
Sent By aoliver Date 2023-06-29 Time 08:20 Rev Time 0.00
Received By aoliver Date 2023-05-19 Time 16:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-04-14 Cont ID  
Sent By aoliver Date 2023-04-14 Time 13:59 Rev Time 0.00
Received By aoliver Date 2023-01-18 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-28 Cont ID  
Sent By lmarchan Date 2022-07-28 Time 16:35 Rev Time 0.00
Received By lmarchan Date 2022-06-21 Time 08:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-17 Cont ID  
Sent By aoliver Date 2022-06-17 Time 16:15 Rev Time 0.00
Received By aoliver Date 2022-05-24 Time 06:06 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2023-05-31 Cont ID  
Sent By mpeterso Date 2023-05-31 Time 09:32 Rev Time 0.00
Received By mpeterso Date 2023-05-31 Time 09:32 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-01-25 Cont ID  
Sent By mpeterso Date 2023-01-25 Time 13:32 Rev Time 0.00
Received By mpeterso Date 2023-01-25 Time 13:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-30 Cont ID  
Sent By mpeterso Date 2022-06-30 Time 10:51 Rev Time 0.00
Received By mpeterso Date 2022-06-30 Time 10:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-14 Cont ID  
Sent By mpeterso Date 2022-06-14 Time 13:34 Rev Time 0.00
Received By mpeterso Date 2022-06-14 Time 13:34 Sent To  
Notes
2022-06-14 13:35:29ALL PLANS PASSED SIGNATURE REVIEW

Review Stop Z ZONING
Rev No 4 Status P Date 2023-06-28 Cont ID  
Sent By eschneid Date 2023-06-28 Time 16:30 Rev Time 0.25
Received By eschneid Date 2023-06-28 Time 16:30 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2023-04-14 Cont ID  
Sent By eschneid Date 2023-04-14 Time 13:51 Rev Time 0.25
Received By eschneid Date 2023-04-14 Time 13:51 Sent To  
Notes
2023-04-14 13:52:17FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY (21120228) MUST BE APPROVED
 PRIOR TO THIS PERMIT BEING APPROVED. THIS SUBMITTED
 PERMIT HAS BEEN UPDATED SINCE THE WCF ROW PERMIT. BOTH
 PLANS WILL NEED TO REFLECT THE SAME, CODE COMPLIANT
 CONDITIONS. THE COMMENTS BELOW ALSO APPLY TO THE WCF
 ROW PERMIT.
  
 2) SHEETS C-3, E-2 AND E3 SHOW A 28-FOOT-TALL POLE. THE
 REMAINING PLANS SHOW OR CALL OUT A 32-FOOT-TALL POLE.
 ALL PLANS NEED TO SHOW THE SAME CONDITIONS. BOTH POLE
 HEIGHTS ARE LOWER THAN SURROUNDING UTILITY POLES.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2022-07-28 Cont ID  
Sent By eschneid Date 2022-07-28 Time 15:50 Rev Time 0.75
Received By eschneid Date 2022-07-28 Time 15:50 Sent To  
Notes
2022-07-28 15:51:10FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY (21120228) MUST BE APPROVED
 PRIOR TO THIS PERMIT BEING APPROVED. THIS SUBMITTED
 PERMIT HAS BEEN UPDATED SINCE THE WCF ROW PERMIT. BOTH
 PLANS WILL NEED TO REFLECT THE SAME, CODE COMPLIANT
 CONDITIONS. THE COMMENTS BELOW ALSO APPLY TO THE WCF
 ROW PERMIT.
  
 2) THIS LOCATION IS WITHIN A HISTORIC DISTRICT. PLEASE
 PROVIDE A COPY OF THE STATE HISTORIC PRESERVATION
 OFFICE APPROVAL OF THIS LOCATION. THE APPROVAL NEEDS TO
 BE THE OFFICIAL STATE APPROVAL ON THEIR LETTERHEAD, NOT
 A TABLE ON A SHEET WITH VERIZON'S LOGO ON THE TOP AS
 THE DOCUMENT PROVIDED IS.
  
 3) SHEET C-1, SITE PLAN WITH AERIAL, SHOWS THE POLE
 SOUTH OF THE HOUSE ON THE LOT WEST OF THE PROPOSED POLE
 LOCATION, WHICH COMPLIES WITH CODE. HOWEVER; THE
 OVERLAY LINES DO NOT ALIGN WITH THE BASE AERIAL. STAFF
 IS CONCERNED THAT ALIGNING THE OVERLAY LINES WITH THE
 BASE AERIAL WILL PUSH THE PROPOSED ANTENNA INTO THE
 FRONT OF THE HOUSE WHICH IS NOT PERMITTED. PLEASE MAKE
 SURE THAT THE OVERLAY LINES MATCH THE BASE AERIAL AND
 THAT THE PROPOSED POLE IS CLEARLY SHOWN SOUTH OF THE
 HOUSE. STAFF HAS PROVIDED CHRISTINA WARR WITH A SNIP OF
 THIS AREA.
  
 4) SHEET P-1 SHOWS THE EXCAVATION BOX FOR THE HANDHOLE
 ADJACENT TO THE UTILITY POLE PROVIDING THE POWER
 EXTENDING PAST THE EDGE OF THE SIDEWALK, WHICH PUTS IT
 ON TO PRIVATE PROPERTY, WHICH IS NOT PERMITTED. ALL
 WORK MUST BE ONLY IN THE RIGHT-OF-WAY. *** THIS WAS NOT
 UPDATED FROM THE WCF ROW PERMIT COMMENT.
  
 5) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-17 Cont ID  
Sent By eschneid Date 2022-06-17 Time 15:13 Rev Time 0.25
Received By eschneid Date 2022-06-17 Time 14:49 Sent To  
Notes
2022-06-17 15:12:59FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY (21120228) MUST BE APPROVED
 PRIOR TO THIS PERMIT BEING APPROVED. THE PLANS ON THIS
 ELECTRIC PERMIT AND THE ONES ULTIMATELY RESUBMITTED
 WITH THE WCF ROW PERMIT NEED TO MATCH. THESE COMMENTS
 MIRROR THOSE PROVIDED FOR THE WCF ROW PERMIT.
  
 2) THIS LOCATION IS WITHIN A HISTORIC DISTRICT. PLEASE
 PROVIDE A COPY OF THE STATE HISTORIC PRESERVATION
 OFFICE APPROVAL OF THIS LOCATION.
  
 3) THE BORE PIT NOTES ON SHEET P-1 STATE THAT THE
 SIDEWALK WILL BE RESTORED; HOWEVER, BOTH PARKWAY AND
 SIDEWALKS WILL NEED RESTORATION. PLEASE UPDATE THE
 NOTATIONS ACCORDINGLY.
  
 4) SHEET P-1 DOES NOT LABEL WHAT THE NORTHEAST
 EXCAVATIONS ENTAILS. IS THIS ONLY A BORE PIT OR ALSO A
 HANDHOLE?
  
 5) SHEET P-1 SHOWS THE EXCAVATION BOX FOR THE HANDHOLE
 ADJACENT TO THE UTILITY POLE PROVIDING THE POWER
 EXTENDING PAST THE EDGE OF THE SIDEWALK, WHICH PUTS IT
 ON TO PRIVATE PROPERTY, WHICH IS NOT PERMITTED. ALL
 WORK MUST BE ONLY IN THE RIGHT-OF-WAY.
  
 6) PROVIDE A CROSS SECTION OF THE UNDERGROUND ELECTRIC
 WHICH VERIFIES THAT THERE ARE NO CONFLICTS WITH
 EXISTING UTILITIES.
  
 7) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  