| Plan Review Stops For Permit 22051093 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2022-07-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-07-15 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-07-15 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2022-07-15 11:43:50 | ADDRESS CHANGED FROM 7001 S FLAGLER DR TO 100 BEVERLY | | | RD |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-15 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-06-15 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-06-15 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2022-06-15 11:58:53 | NEW ADDRESS NEEDS TO BE ASSIGNED TO THE BUILDING AND | | | PARCEL DUE TO THE ENTRANCE OF THE BUILDING FACING | | | BEVERLY RD. PLEASE HAVE OWNER CONTACT | | | [email protected] OR CALL 561-805-6659 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-10-07 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-10-07 |
Time |
11:43 |
Sent To |
|
|
| Notes |
| 2022-10-07 11:48:13 | SEPARATE PERMIT REQUIRED FOR - POOL - SITE WALLS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-29 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-29 |
Time |
08:49 |
Sent To |
|
|
| Notes |
| 2022-09-29 09:09:28 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PROPOSED ELEVATION CERTIFICATE LINE B9 = ELEVATION | | | CERTIFICATE PROVIDED SHOWS THE BASE FLOOD ELEVATION AT | | | 8.00 THE BUILDINGS LOWEST FLOOR (LIVING SPACE) WILL | | | NEED TO BE 2 FEET ABOVE THE BASE FLOOD ELEVATION PER | | | CITY ORDINANCE. (PLEASE VERIFY THE BASE FLOOD | | | ELEVATION) | | | | | | 2) ELEVATION CERTIFICATE A9(B) SHOWS 3 FLOOD VENTS - | | | DRAWING SHOWS 4. (ELEVATION CERTIFICATE SHOULD MATCH | | | THE DRAWINGS) | | | | | | 3) ELEVATION CERTIFICATE A9(C) - FOR 650 SQUARE FEET OF | | | GARAGE SPACE - 650 SQUARE INCHES OF FLOOD VENTS ARE | | | REQUIRED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-31 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-31 |
Time |
08:57 |
Sent To |
|
|
| Notes |
| 2022-08-31 09:22:34 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | | FBC WPB 107.3.5.3 | | | | | | 2) PLEASE SHOW THE LOCATION OF THE DRAFT STOP WITHIN | | | THE FLOOR TRUSSES - TYPE AND LOCATION - FBC R302.12 | | | | | | 3) PLEASE SHOW THE ROOF SLOPE DIMENSION - FBC R905.9.1 | | | SLOPE. | | | BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS | | | THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL | | | (2-PERCENT SLOPE) FOR DRAINAGE, | | | | | | 4) PLEASE PROVIDE THE SMART VENT CERTIFICATION - ICC | | | EVALUATION OR MIAMI DADE NOA OR FLORIDA STATE PRODUCT | | | APPROVAL. | | | | | | 5) YOU WILL NEED TO APPLY FOR A SEPARATE PERMIT AND | | | PROVIDE PLANS UNDER THE SEPARATE PERMIT FOR - POOL, | | | SITE WALLS, POOL BARRIER, FENCES, EXISTING BUILDING | | | DEMO. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-25 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-22 |
Time |
15:43 |
Sent To |
|
|
| Notes |
| 2022-07-25 09:42:21 | NEW SFR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE REQUIRED FLOOD VENTS FOR THE GARAGE | | | - FBC R322.2.2 | | | | | | 2) PLEASE PROVIDE A PROPOSED ELEVATION CERTIFICATE - | | | FBC WPB 107.3.5.3 | | | | | | 3) PLEASE SHOW THE DRAFT STOP WITHIN THE FLOOR TRUSSES | | | - TYPE AND LOCATION - FBC R302.12 | | | | | | 4) PLEASE SHOW THE ROOF SLOPE DIMENSION AND MATERIAL | | | USED FOR THE ROOF SLOPE - FBC R905.9.1 SLOPE. | | | BUILT-UP ROOFS SHALL HAVE A DESIGN SLOPE OF NOT LESS | | | THAN ONE-FOURTH UNIT VERTICAL IN 12 UNITS HORIZONTAL | | | (2-PERCENT SLOPE) FOR DRAINAGE, | | | | | | 5) PRODUCT APPROVAL FOR THE FRENCH DOOR - FL22527 -10 - | | | THE FRONT PAGE OF THE PRODUCT APPROVAL "STATUS" SHOWS | | | "PENDING FBC APPROVAL" - THE STATUS MUST STATE | | | "APPROVED". PLEASE PROVIDE A PRODUCT APPROVAL WITH AN | | | APPROVED STATUS. | | | | | | 6) WINDOW AND DOOR SHOP DRAWINGS PROVIDED NEED TO BE | | | SIGNED AND SEALED BY THE DESIGNER AND REVIEWED AND | | | MARKED APPROVED BY THE BUILDING DESIGNER OF RECORD - | | | FBC WPB 107.3.4 | | | | | | 7) PRODUCT APPROVAL FOR THE FRONT DOOR (FL21891.13) IS | | | MISSING THE FRONT PAGES OF THE PRODUCT APPROVAL - IT | | | ALSO NEEDS TO BE REVIEWED AND MARKED APPROVED BY THE | | | BUILDING DESIGNER OF RECORD - FBC WPB 107.3.4 | | | | | | 8) PLEASE SHOW GARAGE CEILING TO COMPLY WITH FBC R302.6 | | | | | | 9) PLEASE SHOW DOOR FROM GARAGE TO LIVING AREA TO | | | COMPLY WITH FBC R302.5.1 | | | | | | 10 ) PLEASE SHOW ROOM UNDER STAIRWAY TO COMPLY WITH FBC | | | R302.7 UNDER-STAIR PROTECTION. | | | ENCLOSED SPACE UNDER STAIRS THAT IS ACCESSED BY A DOOR | | | OR ACCESS PANEL SHALL HAVE WALLS, UNDER-STAIR SURFACE | | | AND ANY SOFFITS PROTECTED ON THE ENCLOSED SIDE WITH | | | 1/2-INCH (12.7 MM) GYPSUM BOARD. | | | | | | 11) PLEASE SHOW CEILING HEIGHTS - FBC R305.1 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-08-31 |
Time |
23:00 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-08-31 |
Time |
20:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-07-04 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-07-04 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-07-04 |
Time |
11:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2022-10-13 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-10-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-10-13 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-10-13 12:10:53 | PASSED WITH PROVISO - NO CONSTRUCTION MAY OCCUR ALONG | | | WEST SIDE OF PROPERTY UNTIL THE OTHER MANHOLE NEAR THE | | | SOUTHWEST CORNER OF THE PROPERTY IS LOCATED AND SHOWN | | | ON SURVEY AND CONSTRUCTION PLANS. | | | | | | THANKS, | | | RICK ROSSANO, SENIOR PROJECT COORD., WPB ENG. SERVICES | | | DEPT., 561-494-1098, FAX: 561-494-1116 [email protected] | | | FOR 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-09-27 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-09-27 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-27 11:36:49 | PLEASE ADDRESS PUBLIC UTILITIES CUSTOMER SERVICE | | | COMMENT. |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-08-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-08-29 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-07-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-07-25 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-25 15:03:37 | CLEARLY SHOW UTILITY EASEMENTS ON CIVIL PLANS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-26 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2022-06-24 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-06-24 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-06-24 |
Time |
09:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-10-17 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-10-07 |
Time |
12:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-10-05 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-10-05 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-09-22 |
Time |
07:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-09-08 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-09-08 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-08-25 |
Time |
07:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-26 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-14 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-17 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-07 |
Time |
12:23 |
Sent To |
|
|
| Notes |
| 2022-10-14 14:33:10 | RECEIPT MU-2022-046539 - $12,071.20 PAID | | 2022-10-07 12:23:59 | 10/7/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-25 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-25 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2022-07-25 09:43:11 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-30 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-30 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-06-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-23 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-23 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2022-06-23 15:36:18 | 1ST REVIEW FMC | | | PERMIT: 22051093 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7 | | | | | | 2) PROVIDE CONDENSING UNIT TIE DOWN METHOD. FRC M1307.2 | | | | | | 3) PROVIDE THE CONDENSATE DRAIN PIPE AND TERMINATION | | | LOCATION FOR EACH AHU. FRC M1411.3 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
2 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-31 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-31 |
Time |
09:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
NFIP |
NFIP REVIEW ACTIVITY |
| Rev No |
1 |
Status |
F |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-25 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-25 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2022-07-25 09:44:46 | AE 7 | | | | | | PROPOSED LOWEST FLOOR = 9.00 NAVD | | | | | | GARAGE = 6.00 NAVD - FLOOD VENTS REQUIRED |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-26 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-26 |
Time |
10:55 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-06-24 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-06-24 |
Time |
09:32 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-06-24 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
rgathrig |
Date |
2022-10-17 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rgathrig |
Date |
2022-10-17 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2022-10-17 17:04:27 | PRIVATE PROVIDER INSPECTIONS ONLY | | | | | | TEW & TAYLOR | | | | | | RICHARD GATHRIGHT | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
3 |
Status |
N |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-17 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-17 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2022-10-17 12:29:17 | PER MHURLEY - SEE PU-CS RESULT | | | |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
2 |
Status |
F |
Date |
2022-09-08 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
2022-09-08 |
Time |
07:28 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-08 07:28:05 | -SITE PLAN (POOL) NEEDS REVISION TO SHOW WALLS AND | | | FENCES OUT OF 7.5 FOOT UTILITY EASEMENT. | | | | | | -ON DRAINAGE AND GRADING PLAN C1, THERE IS STILL A | | | RETAINING WALL CALLOUT IN UTILITY EASEMENT. ADJUST | | | CALLOUT AND LEADER LINE SO THAT IT IS NOT IN 7.5 FOOT | | | UTILITY EASEMENT. | | | | | | RESPECTFULLY, | | | | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU |
PUBLIC UTILITIES |
| Rev No |
1 |
Status |
F |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
2022-07-26 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-07-26 12:43:04 | SOME OF THE SUBMITTED PLANS CONFLICT WITH UTILITY | | | EASEMENT AT WEST SIDE OF PROPERTY WHERE THERE IS ALSO | | | AN ACTIVE SEWER MAIN. SHOW AND LABEL UTILITY EASEMENT | | | ON PLANS AND REVISE PLANS TO ENSURE THERE ARE NO | | | CONFLICTS SUCH AS STRUCTURES, FENCES, WALLS, CONCRETE | | | SLABS, PANELS, AND TREES IN THAT AREA. |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
3 |
Status |
P |
Date |
2022-10-07 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
2022-10-07 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
2 |
Status |
F |
Date |
2022-09-27 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
2022-09-27 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-27 09:20:38 | DRIVEWAY MAY NOT ENCROACH INTO UTILITY EASEMENT PER WPB | | | SANITARY COLLECTIONS. REVISE PLANS TO REFLECT THAT. | | | RESPECTFULLY, | | | MARK HURLEY [email protected] |
|
|
| Review Stop |
PU-CS |
PUBLIC UTILITIES CUSTOMER SRVC |
| Rev No |
1 |
Status |
F |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
mhurley |
Date |
2022-09-19 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
mhurley |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-09-19 11:40:26 | PER WPB SANITARY COLLECTIONS, DRIVEWAY AND TREES MAY | | | NOT BE INSTALLED OVER SEWER MAIN THAT IS LOCATED NEAR | | | WEST SIDE OF PROPERTY IN UTILITY EASEMENT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-31 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-31 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-25 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-25 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-29 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-29 |
Time |
09:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-08-31 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-31 |
Time |
09:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-07-25 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-25 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-25 |
Time |
09:53 |
Sent To |
|
|
| Notes |
| 2022-06-23 15:37:18 | MECHANICAL DIGITAL SIGNATURES NOT REQUIRED. ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-09-29 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-09-29 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-09-06 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-09-06 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
afowlkes |
Date |
2022-06-21 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
afowlkes |
Date |
2022-06-21 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2022-06-21 16:16:04 | 06/21/22 FAILED - THE MECHANICAL EQUIPMENT CANNOT | | | PROTRUDE MORE THAN 4 FT INTO ANY SETBACK, IN THIS CASE | | | IT WOULD NEED TO BE ROUGHLY 11 FT FROM THE PROPERTY | | | LINE. | | | | | | AND PLEASE NOTE THAT SEPERATE PERMITS ARE REQUIRED FOR | | | FENCES/WALLS, POOLS, LANDSCAPING, DRIVEWAYS, ETC | | | | | | ALEXANDER FOWLKES | | | [email protected] | | | 5618221431 |
|
|