Plan Review Details - Permit 22051083
Plan Review Stops For Permit 22051083
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-10-13 Cont ID  
Sent By cthroop Date 2022-10-13 Time 09:35 Rev Time 0.00
Received By cthroop Date 2022-10-13 Time 09:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-01 Cont ID  
Sent By cthroop Date 2022-10-01 Time 11:30 Rev Time 0.00
Received By cthroop Date 2022-10-01 Time 10:38 Sent To  
Notes
2022-10-01 11:52:572ND BUILDING REVIEW
 RESULTS: CORRECTIONS NEEDED
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT:
  
 NOTICE: ORIGINAL ROOF DESIGN UNDER MASTER PERMIT
 20111187 IS A WOOD DECK OVER MANUF. WOOD TRUSSES WITH
 R-20 ICYNENE SPRAY FOAM INSULATION.
 NOA19-0424.06 SPECIFIES POLYGLASS MODIFIED BITUMEN ROOF
 SYSTEM OVER LIGHTWEIGHT CONCRETE. IF THE ROOF DESIGN
 WILL BE CHANGED, PROVIDE A REVISION TO PLAN PAGE S-3
 UNDER MASTER PERMIT 20111187. DESIGNER SHALL
 RE-EVALUATE THE DEAD LOAD ON THE MANUF. WOOD TRUSSES.
  
 1. FL5259-R28 (UNDERLAYMENT) HAS EXPIRED.
 PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA FOR
 THE PROPOSED ROOFING UNDERLAYMENT TO BE INSTALLED.
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 NOTE: NOA???S DO NOT HAVE COVER SHEETS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. IDENTIFY THE SYSTEM TO BE INSTALLED FOR NOA
 19-0424.06.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. IDENTIFY THE SYSTEM TO BE INSTALLED FOR NOA
 20-0902.19.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
 NOTICE: NOTE # 7 UNDER GENERAL CONSITIONS MAY APPLY.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By cthroop Date 2022-07-18 Time 11:51 Rev Time 0.00
Received By shill Date 2022-07-18 Time 11:51 Sent To  
Notes
2022-07-18 11:56:07****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, SCOPE NOT CLEAR. THE REVISION FORM STATES
 THAT THE FLAT DECK AND TILE ROOF ARE BEING REVISED.
 FLAT DECK PRODUCT APPROVAL WAS NOT SUBMITTED, ONLY TILE
 AND UNDERLAYMENT FOR TILE.
  
 2. FOR THE UNDERLAYMENT, INDICATE WHICH ASSEMBLY IS
 PROPOSED, FBC R 301.
  
 3. PROVIDE A COMPLETE TILE PRODUCT APPROVAL IN ONE PDF.
 THIS SHOULD INCLUDE THE COVER SHEET SHOWING THE PRODUCT
 CODE VERSION AND STATUS, THE EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS. INDICATE METHOD OF
 FASTENING.
  
 ONLY A COVER SHEET WAS UPLOADED, AND THE STATUS IS
 "AFFIRMATION". THIS SHOULD STATE "APPROVED". FBC R 301.
  
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-10-06 Cont ID  
Sent By amhamilt Date 2022-10-06 Time 15:06 Rev Time 0.00
Received By amhamilt Date 2022-10-06 Time 15:06 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2022-06-07 Cont ID  
Sent By fmittner Date 2022-06-07 Time 13:36 Rev Time 0.00
Received By amhamilt Date 2022-06-07 Time 13:36 Sent To  
Notes
2022-06-07 13:37:55THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PRODUCT APPROVAL DOES NOT HAVE SUFFICIENT
 INFORMATION--WHAT IS THE PROFILE OF THE ROOF TILE?
 PLEASE SHOW AN IMAGE OR DRAWING OF THE PROPOSED ROOF
 TILE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-13 Cont ID  
Sent By cthroop Date 2022-10-13 Time 09:35 Rev Time 0.00
Received By cthroop Date 2022-10-13 Time 09:06 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-10-11 Cont ID  
Sent By aoliver Date 2022-10-11 Time 09:30 Rev Time 0.00
Received By aoliver Date 2022-09-07 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 11:56 Rev Time 0.00
Received By shill Date 2022-05-27 Time 16:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-09-19 Cont ID  
Sent By rmcdouga Date 2022-09-19 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2022-09-19 Time 09:30 Sent To  
Notes
***NONE***