Plan Review Details - Permit 22051015
Plan Review Stops For Permit 22051015
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-11-04 Cont ID  
Sent By pvalenti Date 2022-11-04 Time 16:05 Rev Time 0.00
Received By pvalenti Date 2022-11-04 Time 15:45 Sent To  
Notes
2022-11-04 16:07:02PETER E VALENTI
 BUILDING PLANS EXAMINER II/INSPECTOR
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 THE GUARDS THAT ARE REQUIRED AT THE ROOF AREAS PER FBC
 B 1015 OF THE FLORIDA BUILDING CODE MUST BE INSTALLED
 AS INDICATED FROM PERMIT #21070167 PLAN SHEETS A-106 &
 A-500.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-10-17 Cont ID  
Sent By pvalenti Date 2022-10-17 Time 08:04 Rev Time 0.00
Received By pvalenti Date 2022-10-17 Time 06:30 Sent To  
Notes
2022-10-17 08:10:31PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 THE GUARDS THAT ARE REQUIRED AT THE ROOF AREAS PER FBC
 B 1015 OF THE FLORIDA BUILDING CODE MUST BE INSTALLED
 AS INDICATED FROM PERMIT #21070167 PLAN SHEETS A-106 &
 A-500.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 09:20 Rev Time 0.00
Received By shill Date 2022-09-06 Time 09:20 Sent To  
Notes
2022-09-06 09:20:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1015.6, IT APPEARS THAT THE EQUIPMENT IS
 PROPOSED LESS THAN 10' FROM THE ROOF EDGE. REVISE PLAN
 TO SHOW COMPLIANCE WITH THE REQUIREMENT FOR GUARDS.
  
 2ND REVIEW, A 32" HIGH PARAPET IS SHOWN. SEE FBC B
 1015.3, 42" IS REQUIRED TO SERVE AS A GUARD.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 13:28 Rev Time 0.00
Received By shill Date 2022-07-18 Time 13:28 Sent To  
Notes
2022-07-18 13:28:44****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1015.6, IT APPEARS THAT THE EQUIPMENT IS
 PROPOSED LESS THAN 10' FROM THE ROOF EDGE. REVISE PLAN
 TO SHOW COMPLIANCE WITH THE REQUIREMENT FOR GUARDS.
  
 2. S001, THE WIND DESIGN CRITERIA IS NOT CLEAR. IT
 APPEARS TO STATE THAT THE BUILDING IS EXPOSURE D,
 170MPH, THE PV IS C, 180MPH. CLARIFY, APPEARS THIS
 LOCATION IS EXPOSURE D.
  
 3. S001, CODE TABLE, REVISE TO STATE THE GOVERNING
 CODE(S) PER FS553. IBC IS NOT A GOVERNING CODE, THE
 RESIDENTIAL CODE IS NOT APPLICABLE FOR THIS PROJECT AS
 THIS IS NOT CONSIDERED A ONE OR TWO FAMILY DWELLING.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-11-02 Cont ID  
Sent By mpeterso Date 2022-11-02 Time 11:45 Rev Time 0.00
Received By mpeterso Date 2022-11-02 Time 11:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-09-14 Cont ID  
Sent By mpeterso Date 2022-09-14 Time 14:41 Rev Time 0.00
Received By mpeterso Date 2022-09-14 Time 14:41 Sent To  
Notes
2022-09-14 14:45:35ELECTRIC REVIEW FAILED
 1) PROVIDE CORRECT ELECTRIC LINE DIAGRAM (RECORDS
 INDICATE A 480 VOLT SERVICE), ELECTRICAL EQUIPMENT
 CLEARANCE DETAILS AND DETAILS ON CONDUIT RUN FROM ROOF
 TO ELECTRIC ROOM (CHASE DETAILS) FBC 107.2, NEC 110.26
 NEC 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-14 Cont ID  
Sent By mpeterso Date 2022-06-14 Time 14:34 Rev Time 0.00
Received By mpeterso Date 2022-06-14 Time 14:34 Sent To  
Notes
2022-06-14 14:46:59ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE A SITE, AND COMPLETE FLOOR PLAN
 DETAILING ALL LOCATIONS OF ELECTRICAL SERVICE
 EQUIPMENT. NEC 215.5 FBC 107.2
 2) PLEASE DETAIL USE OF 120/208, SECOND SERVICE AND
 PROVIDE RISER AS APPLICABLE NEC 230.2(A)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-10-26 Cont ID  
Sent By pleduc Date 2022-10-26 Time   Rev Time 0.00
Received By pleduc Date 2022-10-26 Time 11:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-26 Cont ID  
Sent By pleduc Date 2022-08-26 Time   Rev Time 0.00
Received By pleduc Date 2022-08-26 Time 11:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-07-19 Cont ID  
Sent By pleduc Date 2022-07-19 Time   Rev Time 0.00
Received By pleduc Date 2022-07-19 Time 11:16 Sent To  
Notes
2022-07-19 12:04:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE APPEAARS TO BE 2 DICONNECT BOXES, HOWEVER,
 THEY ARE CENTRALLY LOCATED AND COULD BE INACCESSIBLE IN
 AN EMERGENCY EVENT.
  
 11.12 PHOTOVOLTAIC SYSTEMS.
  
 11.12.1 PHOTOVOLTAIC SYSTEMS SHALL BE IN ACCORDANCE
 WITH SEC TION 11.12 AND NFPA 70
  
 11.12.2.1* MARKING. PHOTOVOLTAIC SYSTEMS SHALL BE
 PERMANENTLY MARKED AS SPECIFIED IN THIS SUBSECTION
  
 11.12.2.1.1 RAPID SHUTDOWN MARKING. BUILDINGS WITH A PV
 SYSTEM SHALL BE PROVIDED WITH PERMANAENT LABLES AS
 DESCRIBED IN 11.12.2.1.1.1 THROUGH 11.12.2.1.1.7.
  
 PLEASE REVIEW AND RELOCATE A SINGLE(1) DISCONNECT FOR
 THE ENTIRE ROOF AT/NEAR THE EXIT FROM THE ROOF
 STAIRWELL.
  
  
  
 2) THERE ARE INDICATIONS OF 2 FDC'S ALONG THE 4' FIRE
 PATH, HOWEVER, THE REQUIRMENT OF THE CODE STATES 4'
 CLEAR AROUND THE STANDPIPE.
  
 11.12.2.2.3.2 PATHWAYS. PATHWAYS SHALL BE ESTABLISHED
 AS FOLLOWS:
 (1) PATHWAYS SHALL BE OVER AREAS CAPABLE OF SUPPORTING
 THE LIVE
 LOAD OF FIRE FIGHTERS ACCESSING THE ROOF.
 (2) CENTERLINE AXIS PATHWAYS SHALL BE PROVIDED IN BOTH
 AXES OF
 THE ROOF.
 (3) CENTERLINE AXIS PATHWAYS SHALL RUN WHERE THE ROOF
 STRUC TURE IS CAPABLE OF SUPPORTING THE LIVE LOAD OF
 FIRE FIGHTERS
 ACCESSING THE ROOF.
 (4) PATHWAYS SHALL BE IN A STRAIGHT LINE NOT LESS THAN
 4 FT
 (1219 MM) CLEAR TO SKYLIGHTS, VENTILATION HATCHES, AND
 ROOF STANDPIPES.
 (5) PATHWAYS SHALL PROVIDE NOT LESS THAN 4 FT (1219 MM)
 CLEAR
 AROUND ROOF ACCESS HATCHES WITH AT LEAST ONE NOT LESS
 THAN
 4 FT (1219 MM) CLEAR PATHWAY TO THE PARAPET OR ROOF
 EDGE
  
 PLEASE REVIEW AND AND PROVIDE A 4' RADUIS AT EACH FDC.
  
  
  
 3) THERE ARE INDICATIONS OF PATHWAYS AROUND THE ROOF
 LINE AND OTHER AREAS, HOWEVER, IT IS NOT CLEAR THE
 DIMENSION OF ALL AREAS.
  
 11.12.2.2.3.1 ACCESS. A MINIMUM 4 FT (1219 MM) WIDE
 CLEAR
 PERIMETER SHALL BE PROVIDED AROUND THE EDGES OF THE
 ROOF FOR
 BUILDINGS WITH A LENGTH OR WIDTH OF 250 FT (76.2 M) OR
 LESS ALONG
 EITHER AXIS. A MINIMUM 6 FT (1829 MM) WIDE CLEAR
 PERIMETER
 SHALL BE PROVIDED AROUND THE EDGES OF THE ROOF FOR
 BUILDINGS
 HAVING LENGTH OR WIDTH GREATER THAN 250 FT (76.2 M)
 ALONG
 EITHER AXIS
  
 PLEASE REVIEW AND CORRECT/PROVIDE DETAIALED DIMENSIONS.
  
 4) THERE ARE INDICATIONS OF ELECTRICAL CONDUIT/CABLING
 THROUGHOUT THE ROOF/PANEL STRUCTURES, HOWEVER, THERE
 ARE NO CLEAR INDICATIONS OF THE LOCATION/ROUTING OF THE
 ELECTIRCAL SYSTEM COMPONENTS.
  
 11.12.2.1.3* CONDUIT, RACEWAY, ENCLOSURE, CABLE
 ASSEMBLY,
 AND JUNCTION BOX MARKINGS. MARKING SHALL BE REQUIRED ON
 ALL
 INTERIOR AND EXTERIOR DC CONDUITS, RACEWAYS,
 ENCLOSURES, CABLE
 ASSEMBLIES, AND JUNCTION BOXES.
 (1) EXPOSED RACEWAYS...
 (2) COVERSOR ENCLOSURES OF PULL/JUNCTION BOXS
 (3) CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE
 CONDUIT OPENINGS ARE UNUSED.
  
 11.12.2.1.3.1 MARKING LOCATIONS. MARKING SHALL BE
 PLACED ON.....
 ALL DC CONDUITS, RACEWAYS, ENCLOSURES, AND CABLE
 ASSEMBLIES EVERY 10 FT (3048 MM), AT TURNS, AND ABOVE
 AND BELOW PENETRA TIONS. MARKING SHALL BE PLACED ON ALL
 DC COMBINER AND JUNC TION BOXES.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-11-04 Cont ID  
Sent By pvalenti Date 2022-11-04 Time 16:09 Rev Time 0.00
Received By pvalenti Date 2022-10-25 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-14 Cont ID  
Sent By mpeterso Date 2022-09-14 Time 14:45 Rev Time 0.00
Received By mpeterso Date 2022-08-25 Time 13:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-19 Cont ID  
Sent By lmarchan Date 2022-07-19 Time 12:31 Rev Time 0.00
Received By lmarchan Date 2022-05-24 Time 07:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-11-02 Cont ID  
Sent By mpeterso Date 2022-11-02 Time 11:52 Rev Time 0.00
Received By mpeterso Date 2022-11-02 Time 11:50 Sent To  
Notes
2022-11-02 11:53:16ALL PLANS PASSED SIGNATURE REVIEW. MP

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-09-06 Cont ID  
Sent By shill Date 2022-09-06 Time 09:21 Rev Time 0.00
Received By shill Date 2022-09-06 Time 09:21 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-14 Cont ID  
Sent By mpeterso Date 2022-06-14 Time 14:49 Rev Time 0.00
Received By mpeterso Date 2022-06-14 Time 14:49 Sent To  
Notes
2022-06-14 14:50:02ALL PLANS PASSED SIGNATURE REVIEW

Review Stop Z ZONING
Rev No 3 Status P Date 2022-11-03 Cont ID  
Sent By ckimmerl Date 2022-11-03 Time 15:09 Rev Time 0.00
Received By ckimmerl Date 2022-11-03 Time 15:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-09-01 Cont ID  
Sent By ckimmerl Date 2022-09-01 Time 14:17 Rev Time 0.00
Received By ckimmerl Date 2022-09-01 Time 14:17 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-09 Cont ID  
Sent By ckimmerl Date 2022-06-09 Time 16:16 Rev Time 0.00
Received By ckimmerl Date 2022-06-09 Time 16:14 Sent To  
Notes
2022-06-09 16:16:461. FLAT ROOFS?HEIGHT. ON FLAT ROOFS, THE HIGHEST POINT
 OF THE SYSTEM SHALL BE PERMITTED TO EXCEED THE
 DISTRICT'S HEIGHT LIMIT BY A MAXIMUM OF SIX FEET ABOVE
 THE ROOFTOP TO WHICH IT IS ATTACHED.
  
 - PLEASE PROVIDE HEIGHT OR DIMENSIONED ELEVATIONS OF
 THE ROOF WITH THE SOLAR SYSTEM OR SOLAR PANEL/UNITS.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822-1426