| Plan Review Stops For Permit 22051015 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-11-04 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-11-04 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-11-04 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2022-11-04 16:07:02 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II/INSPECTOR | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | THE GUARDS THAT ARE REQUIRED AT THE ROOF AREAS PER FBC | | | B 1015 OF THE FLORIDA BUILDING CODE MUST BE INSTALLED | | | AS INDICATED FROM PERMIT #21070167 PLAN SHEETS A-106 & | | | A-500. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-10-17 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-10-17 |
Time |
06:30 |
Sent To |
|
|
| Notes |
| 2022-10-17 08:10:31 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | THE GUARDS THAT ARE REQUIRED AT THE ROOF AREAS PER FBC | | | B 1015 OF THE FLORIDA BUILDING CODE MUST BE INSTALLED | | | AS INDICATED FROM PERMIT #21070167 PLAN SHEETS A-106 & | | | A-500. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-09-06 |
Time |
09:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-09-06 |
Time |
09:20 |
Sent To |
|
|
| Notes |
| 2022-09-06 09:20:43 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1015.6, IT APPEARS THAT THE EQUIPMENT IS | | | PROPOSED LESS THAN 10' FROM THE ROOF EDGE. REVISE PLAN | | | TO SHOW COMPLIANCE WITH THE REQUIREMENT FOR GUARDS. | | | | | | 2ND REVIEW, A 32" HIGH PARAPET IS SHOWN. SEE FBC B | | | 1015.3, 42" IS REQUIRED TO SERVE AS A GUARD. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-18 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-18 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2022-07-18 13:28:44 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1015.6, IT APPEARS THAT THE EQUIPMENT IS | | | PROPOSED LESS THAN 10' FROM THE ROOF EDGE. REVISE PLAN | | | TO SHOW COMPLIANCE WITH THE REQUIREMENT FOR GUARDS. | | | | | | 2. S001, THE WIND DESIGN CRITERIA IS NOT CLEAR. IT | | | APPEARS TO STATE THAT THE BUILDING IS EXPOSURE D, | | | 170MPH, THE PV IS C, 180MPH. CLARIFY, APPEARS THIS | | | LOCATION IS EXPOSURE D. | | | | | | 3. S001, CODE TABLE, REVISE TO STATE THE GOVERNING | | | CODE(S) PER FS553. IBC IS NOT A GOVERNING CODE, THE | | | RESIDENTIAL CODE IS NOT APPLICABLE FOR THIS PROJECT AS | | | THIS IS NOT CONSIDERED A ONE OR TWO FAMILY DWELLING. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-02 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-02 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-09-14 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-09-14 |
Time |
14:41 |
Sent To |
|
|
| Notes |
| 2022-09-14 14:45:35 | ELECTRIC REVIEW FAILED | | | 1) PROVIDE CORRECT ELECTRIC LINE DIAGRAM (RECORDS | | | INDICATE A 480 VOLT SERVICE), ELECTRICAL EQUIPMENT | | | CLEARANCE DETAILS AND DETAILS ON CONDUIT RUN FROM ROOF | | | TO ELECTRIC ROOM (CHASE DETAILS) FBC 107.2, NEC 110.26 | | | NEC 215.5 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-06-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-14 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-14 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2022-06-14 14:46:59 | ELECTRIC REVIEW FAILED | | | 1) PLEASE PROVIDE A SITE, AND COMPLETE FLOOR PLAN | | | DETAILING ALL LOCATIONS OF ELECTRICAL SERVICE | | | EQUIPMENT. NEC 215.5 FBC 107.2 | | | 2) PLEASE DETAIL USE OF 120/208, SECOND SERVICE AND | | | PROVIDE RISER AS APPLICABLE NEC 230.2(A) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-10-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-10-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-10-26 |
Time |
11:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-08-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-08-26 |
Time |
11:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-07-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-07-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-07-19 |
Time |
11:16 |
Sent To |
|
|
| Notes |
| 2022-07-19 12:04:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE APPEAARS TO BE 2 DICONNECT BOXES, HOWEVER, | | | THEY ARE CENTRALLY LOCATED AND COULD BE INACCESSIBLE IN | | | AN EMERGENCY EVENT. | | | | | | 11.12 PHOTOVOLTAIC SYSTEMS. | | | | | | 11.12.1 PHOTOVOLTAIC SYSTEMS SHALL BE IN ACCORDANCE | | | WITH SEC TION 11.12 AND NFPA 70 | | | | | | 11.12.2.1* MARKING. PHOTOVOLTAIC SYSTEMS SHALL BE | | | PERMANENTLY MARKED AS SPECIFIED IN THIS SUBSECTION | | | | | | 11.12.2.1.1 RAPID SHUTDOWN MARKING. BUILDINGS WITH A PV | | | SYSTEM SHALL BE PROVIDED WITH PERMANAENT LABLES AS | | | DESCRIBED IN 11.12.2.1.1.1 THROUGH 11.12.2.1.1.7. | | | | | | PLEASE REVIEW AND RELOCATE A SINGLE(1) DISCONNECT FOR | | | THE ENTIRE ROOF AT/NEAR THE EXIT FROM THE ROOF | | | STAIRWELL. | | | | | | | | | | | | 2) THERE ARE INDICATIONS OF 2 FDC'S ALONG THE 4' FIRE | | | PATH, HOWEVER, THE REQUIRMENT OF THE CODE STATES 4' | | | CLEAR AROUND THE STANDPIPE. | | | | | | 11.12.2.2.3.2 PATHWAYS. PATHWAYS SHALL BE ESTABLISHED | | | AS FOLLOWS: | | | (1) PATHWAYS SHALL BE OVER AREAS CAPABLE OF SUPPORTING | | | THE LIVE | | | LOAD OF FIRE FIGHTERS ACCESSING THE ROOF. | | | (2) CENTERLINE AXIS PATHWAYS SHALL BE PROVIDED IN BOTH | | | AXES OF | | | THE ROOF. | | | (3) CENTERLINE AXIS PATHWAYS SHALL RUN WHERE THE ROOF | | | STRUC TURE IS CAPABLE OF SUPPORTING THE LIVE LOAD OF | | | FIRE FIGHTERS | | | ACCESSING THE ROOF. | | | (4) PATHWAYS SHALL BE IN A STRAIGHT LINE NOT LESS THAN | | | 4 FT | | | (1219 MM) CLEAR TO SKYLIGHTS, VENTILATION HATCHES, AND | | | ROOF STANDPIPES. | | | (5) PATHWAYS SHALL PROVIDE NOT LESS THAN 4 FT (1219 MM) | | | CLEAR | | | AROUND ROOF ACCESS HATCHES WITH AT LEAST ONE NOT LESS | | | THAN | | | 4 FT (1219 MM) CLEAR PATHWAY TO THE PARAPET OR ROOF | | | EDGE | | | | | | PLEASE REVIEW AND AND PROVIDE A 4' RADUIS AT EACH FDC. | | | | | | | | | | | | 3) THERE ARE INDICATIONS OF PATHWAYS AROUND THE ROOF | | | LINE AND OTHER AREAS, HOWEVER, IT IS NOT CLEAR THE | | | DIMENSION OF ALL AREAS. | | | | | | 11.12.2.2.3.1 ACCESS. A MINIMUM 4 FT (1219 MM) WIDE | | | CLEAR | | | PERIMETER SHALL BE PROVIDED AROUND THE EDGES OF THE | | | ROOF FOR | | | BUILDINGS WITH A LENGTH OR WIDTH OF 250 FT (76.2 M) OR | | | LESS ALONG | | | EITHER AXIS. A MINIMUM 6 FT (1829 MM) WIDE CLEAR | | | PERIMETER | | | SHALL BE PROVIDED AROUND THE EDGES OF THE ROOF FOR | | | BUILDINGS | | | HAVING LENGTH OR WIDTH GREATER THAN 250 FT (76.2 M) | | | ALONG | | | EITHER AXIS | | | | | | PLEASE REVIEW AND CORRECT/PROVIDE DETAIALED DIMENSIONS. | | | | | | 4) THERE ARE INDICATIONS OF ELECTRICAL CONDUIT/CABLING | | | THROUGHOUT THE ROOF/PANEL STRUCTURES, HOWEVER, THERE | | | ARE NO CLEAR INDICATIONS OF THE LOCATION/ROUTING OF THE | | | ELECTIRCAL SYSTEM COMPONENTS. | | | | | | 11.12.2.1.3* CONDUIT, RACEWAY, ENCLOSURE, CABLE | | | ASSEMBLY, | | | AND JUNCTION BOX MARKINGS. MARKING SHALL BE REQUIRED ON | | | ALL | | | INTERIOR AND EXTERIOR DC CONDUITS, RACEWAYS, | | | ENCLOSURES, CABLE | | | ASSEMBLIES, AND JUNCTION BOXES. | | | (1) EXPOSED RACEWAYS... | | | (2) COVERSOR ENCLOSURES OF PULL/JUNCTION BOXS | | | (3) CONDUIT BODIES IN WHICH ANY OF THE AVAILABLE | | | CONDUIT OPENINGS ARE UNUSED. | | | | | | 11.12.2.1.3.1 MARKING LOCATIONS. MARKING SHALL BE | | | PLACED ON..... | | | ALL DC CONDUITS, RACEWAYS, ENCLOSURES, AND CABLE | | | ASSEMBLIES EVERY 10 FT (3048 MM), AT TURNS, AND ABOVE | | | AND BELOW PENETRA TIONS. MARKING SHALL BE PLACED ON ALL | | | DC COMBINER AND JUNC TION BOXES. | | | | | | PLEASE REVIEW AND PROVIDE. | | | | | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-11-04 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-11-04 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-10-25 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-09-14 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-08-25 |
Time |
13:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-19 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-07-19 |
Time |
12:31 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-05-24 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-11-02 |
Time |
11:52 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-11-02 |
Time |
11:50 |
Sent To |
|
|
| Notes |
| 2022-11-02 11:53:16 | ALL PLANS PASSED SIGNATURE REVIEW. MP |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-09-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-09-06 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-09-06 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-06-14 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-14 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-14 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2022-06-14 14:50:02 | ALL PLANS PASSED SIGNATURE REVIEW |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-11-03 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-11-03 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-11-03 |
Time |
15:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-09-01 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-09-01 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-09 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-06-09 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-06-09 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2022-06-09 16:16:46 | 1. FLAT ROOFS?HEIGHT. ON FLAT ROOFS, THE HIGHEST POINT | | | OF THE SYSTEM SHALL BE PERMITTED TO EXCEED THE | | | DISTRICT'S HEIGHT LIMIT BY A MAXIMUM OF SIX FEET ABOVE | | | THE ROOFTOP TO WHICH IT IS ATTACHED. | | | | | | - PLEASE PROVIDE HEIGHT OR DIMENSIONED ELEVATIONS OF | | | THE ROOF WITH THE SOLAR SYSTEM OR SOLAR PANEL/UNITS. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | [email protected] 822-1426 |
|
|