Plan Review Details - Permit 22050938
Plan Review Stops For Permit 22050938
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 16:04 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 16:04 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 14:56 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 14:56 Sent To  
Notes
2022-06-29 14:57:15PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 16:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 14:57 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 14:57 Sent To  
Notes
2022-06-29 15:01:32CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE TYPE OF FLOORING TO BE INSTALLED IN
 EACH ROOM -
  
 2) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO VERIFY
 THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING TO
 PROJECTDOX ( [email protected] )
  
 3) PLEASE PROVIDE A NOTE ON THE DRAWINGS PERTAINING TO
 THE FIRE CLASSIFICATION FOR THE CEILING FINISHES FBC
 803.11
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 13:57 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 13:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-10 Cont ID  
Sent By mpeterso Date 2022-06-10 Time 14:40 Rev Time 0.00
Received By mpeterso Date 2022-06-10 Time 14:40 Sent To  
Notes
2022-06-10 14:52:57ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE SWITCH LOCATIONS FOR ALL LED STRIP
 LIGHTING. FBC 107.2
 2) PLEASE PROVIDE SPECIFICATIONS FOR STRIP LIGHTING,
 ASSOCIATED DRIVERS AND MOTORIZED SHADES. FBC 107.2
 3) PLEASE PROVIDE A NOTE STATING ELECTRICAL CONTRACTOR
 IS TO ENSURE SPACING AND CIRCUIT REQUIREMENTS FOR
 BATHROOM AND KITCHEN RECEPTACLES ADHERE TO
 2017 NEC CODE REQUIREMENTS. NEC 210.52 AND FBC 107.2
 4) PLEASE PROVIDE A NOTE REQUIRING NEW WIRING TO ADHERE
 TO, 2017 NEC GROUND FAULT, ARC FAULT AND TAMPER
 RESISTANT REQUIREMENTS AS APPLICABLE.. NEC 210.12, NEC
 406.4, NEC 406.12, NEC 406.4(D)(5) AND NEC 210.8107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-24 Cont ID  
Sent By cwalker Date 2022-05-24 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 13:57 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 16:28 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 15:02 Rev Time 0.00
Received By rmcphers Date 2022-05-24 Time 05:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 14:51 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 14:51 Sent To  
Notes
2022-05-27 14:51:58NO MECHANICAL WORK IN THE SCOPE OF THIS PROJECT.ME

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-28 Cont ID  
Sent By rwbrown Date 2022-05-28 Time 08:53 Rev Time 0.00
Received By rwbrown Date 2022-05-28 Time 08:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-02 Cont ID  
Sent By rmcphers Date 2022-08-02 Time 16:03 Rev Time 0.00
Received By rmcphers Date 2022-08-02 Time 16:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 15:02 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 15:02 Sent To  
Notes
***NONE***