Plan Review Details - Permit 22050891
Plan Review Stops For Permit 22050891
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-08-02 Cont ID  
Sent By cpuell Date 2022-08-02 Time 16:26 Rev Time 0.00
Received By cpuell Date 2022-08-02 Time 16:26 Sent To  
Notes
2022-08-02 16:27:53GROUND FLOOR AND APARTMENT ADDRESSES AGREED UPON AND
 ASSIGNED.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2022-08-31 Cont ID  
Sent By scwelter Date 2022-08-31 Time 10:35 Rev Time 0.00
Received By swelter Date 2023-05-16 Time 13:44 Sent To  
Notes
2023-05-16 13:44:03PUBLIC ART NEEDS TO BE PRESENTED TO ARTLIFE COMMITTEE
 AND CITY COMMISSION FOR FINAL APPROVAL - HOLD TCO AND
 CO
2022-08-31 10:41:411% FOR PUBLIC ART HAS BEEN ESCROWED BY 575 ROSEMARY
 APARTMENTS, LLC -

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2023-02-03 Cont ID  
Sent By rmcphers Date 2023-02-03 Time 11:03 Rev Time 0.00
Received By rmcphers Date 2023-02-03 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2023-01-05 Cont ID  
Sent By rmcphers Date 2023-01-05 Time 14:04 Rev Time 0.00
Received By rmcphers Date 2023-01-05 Time 14:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-12-06 Cont ID  
Sent By rmcphers Date 2022-12-06 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2022-12-06 Time 14:48 Sent To  
Notes
2022-12-06 15:17:47NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS APPEAR TO SHOW A DEAD END CORRIDOR ON THE
 SOUTH SIDE OF THE SOUTH STAIR ON THE 4TH FLOOR - PLEASE
 SHOW THE DEAD END CORRIDOR DIMENSIONS FOR THE 4TH FLOOR
 - FBC 1020.4
  
 2) TOILET REAR WALLS ARE SHOWN TO HAVE TILE - PLEASE
 SHOW THE WALL FINISH FOR THE SIDE WALLS WITHIN 2' OF
 TOILETS - PLEASE SHOW THE COMMON AREA RESTROOM WALL
 FINISH - (DRYWALL IS NOT CONSIDERED A HARD SURFACE) -
 FBC 1210.2.2
  
 3) BRIDGE RAMP HANDRAIL INSIDE OF BUILDING NEAR THE
 HALLWAY - DRAWING A704 - RAMP HAND RAIL EXTENSIONS
 INSIDE THE BUILDING APPEAR TO BE IN COLUMNS - PLEASE
 CLARIFY THE RAMP HAND RAIL EXTENSIONS - FBC FHA
 REQUIREMENT 2 ANSI 4.8.5
  
 4) DRAWINGS A106 AND LS103 DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  
 5) DRAWINGS SHOW UNIT FLOORING USING 1/4" SOUND PAD -
 THE FLOORING SYSTEM WILL NEED TO BE TESTED AFTER
 INSTALLATION OR PROVIDE THE FOLLOWING TEST REPORTS
 BEFORE INSTALLATION - PLEASE STATE ON THE DRAWINGS YOUR
 INTENTIONS. YOU CAN ADD THE FLOORING SYSTEM TEST
 REPORTS TO THE DEFERRED DOCUMENTS LIST ON THE DRAWINGS.
 THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED
 BEFORE FLOORING INSTALLATION OR A FIELD TEST AFTER
 INSTALLATION:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-10-24 Cont ID  
Sent By rmcphers Date 2022-10-24 Time 12:00 Rev Time 0.00
Received By rmcphers Date 2022-10-24 Time 11:43 Sent To  
Notes
2022-10-24 12:00:29NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE FIRE SERVICE ELEVATOR LOBBY
 DIMENSIONS PER FBC 3007.6.4
  
 2) PLEASE SHOW THE ELEVATOR HOIST WAY PROTECTION FOR
 THE 4TH FLOOR PER FBC 3006.3
  
 3) PLEASE SHOW THE DEAD END CORRIDOR DIMENSIONS FOR ALL
 FLOORS - FBC 1020.4
  
 4) DRAWING A125 HAS ARROWS POINTING TO - SINK,
 ELEVATOR, DOORS ETC. - AND NOT THE ACTUAL MECHANICAL
 CHASE AS NOTED.
  
 5) DRAWING A670 - STUDIO "A" AND "D" ROOM NOTATIONS NOT
 CORRECT - BATH IN THE KITCHEN, KITCHEN IN THE CLOSET -
 ETC.
  
 6) PLEASE SHOW THE POOL BARRIER - FBC 454.1.3.1.9
  
 7) PLEASE SHOW THE COMMON AREA RESTROOM WALL FINISH -
 (DRYWALL IS NOT CONSIDERED A HARD SURFACE) - FBC
 1210.2.2
  
 8) UNIT BATHROOMS - PLEASE SHOW THAT GRAB BAR BACKING
 AT SHOWERS AND BATH TUBS ARE REQUIRED ON ALL 3 WALLS -
 FBC FHA REQUIREMENT 6
  
 9) LEVEL 4 COMMON RESTROOM - PLEASE SHOW THE DOOR
 MANEUVERING CLEARANCE TO EXIT THE RESTROOM FBC FHA -
 ANSI 4.13.6
  
 10) LEVEL 4 - COMMON AREA BAR - PLEASE SHOW
 ACCESSIBILITY DETAILS - SINK FLOOR SPACE, BAR SEATING
 COUNTER HEIGHT ETC. FBC FHA REQUIREMENT 2
  
 11) KITCHEN G-1 AND G-5 - A 5 FOOT TURNING RADIUS IS
 REQUIRED - FBC FHA REQUIREMENT 7
  
 12) KITCHEN L-2 NEED 40 INCHES CLEARANCE BETWEEN THE
 REFRIGERATOR AND THE KITCHEN ISLAND - FBC FHA
 REQUIREMENT 7
  
 13) DRAWING A704 - RAMP HAND RAIL EXTENSIONS INSIDE THE
 BUILDING APPEAR TO BE IN COLUMNS - PLEASE CLARIFY THE
 HAND RAIL EXTENSIONS - FBC FHA REQUIREMENT 2 ANSI 4.8.5
  
 14) FLOORING - THE FOLLOWING ACUSTICAL TEST REPORTS ARE
 REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date   Cont ID  
Sent By rmcphers Date   Time   Rev Time 0.00
Received By rmcphers Date 2022-10-20 Time 14:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2023-01-06 Cont ID  
Sent By jleahy Date 2023-01-06 Time 07:54 Rev Time 0.00
Received By jleahy Date 2023-01-04 Time 09:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-12-01 Cont ID  
Sent By jleahy Date 2022-12-01 Time 16:39 Rev Time 0.00
Received By jleahy Date 2022-12-01 Time 08:23 Sent To  
Notes
2022-12-01 16:44:15FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PAGE E103A DETAIL OF MAIN SWITCH EAR ROOM METER RACK
 MB-2 IS SHOWN AT THE END OF THE MAIN SWITCH GEAR IS
 THIS THE FINAL PLACE FOR THIS OR IS IT A MISTAKE? IT
 SEEMS TO BE BLOCKING THE ENTRANCE TO THE BACK OF THE
 GEAR. THE BACK MAY NOT NEED ACCESS BUT JUST NEED A
 CLARIFICATION.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By jleahy Date 2022-10-20 Time 07:54 Rev Time 0.00
Received By jleahy Date 2022-10-13 Time 09:47 Sent To  
Notes
2022-10-17 17:10:38FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) E-102A MAIN ELECTRICAL ROOM LAYOUT
  
 110.26(C)(2)(A,B) EGRESS PATH CROSSING IN FRONT OF
 MS-R2 AT THE DOOR, YOU HAVE TO TRAVEL THROUGH THE
 REQUIRED WORKING SPACE IN ORDER TO EXIT THE ROOM.
 PLEASE PROVIDE A CLEAR UNOBSTRUCTED PATH.
  
 110.26(C)(2)(B) EXTRA WORKING SPACE. WHERE THE DEPTH OF
 THE WORKING SPACE IS TWICE THAT REQUIRED BY
 110.26(A)(1), A SINGLE ENTRANCE SHALL BE PERMITTED. IT
 SHALL BE LOCATED SUCH THAT THE DISTANCE FROM THE
 EQUIPMENT TO THE
 NEAREST EDGE OF THE ENTRANCE IS NOT LESS THAN THE
 MINIMUM CLEAR DISTANCE SPECIFIED IN TABLE 110.26(A)(1)
 FOR EQUIPMENT OPERATING AT THAT VOLTAGE AND IN THAT
 CONDITION.
  
 2) E-301, 302 LOAD CALCULATIONS LOAD CALCULATIONS SHOWN
 USE A DEMANDED LOAD CALCULATION AND THEN AGAIN DEMAND
 IT FOR A FINAL LOAD??? PLEASE SHOW HOW YOUR LOAD CALC
 COMPLIES WITH 220.84 OR WHATEVER YOU ARE USING.
  
 3) E-502 RISER DIAGRAM PLEASE SHOW COMPLIANCE WITH
 700.3(F) FOR BACKUP GENERATOR.
  
 700.3 (F) TEMPORARY SOURCE OF POWER FOR MAINTENANCE OR
 REPAIR OF THE ALTERNATE SOURCE OF POWER.
  
 4) THE FOLLOWING SYSTEMS SHALL BE REQUIRED TO GET
 SEPARATE PERMITS LIGHTNING PROTECTION, POOL, GENERATOR,
 FIRE ALARM, BDA, SECURITY, ACCESS CONTROL ECT. ECT.

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2022-10-13 Cont ID  
Sent By rrossano Date 2022-10-13 Time   Rev Time 0.00
Received By rrossano Date 2022-10-13 Time   Sent To  
Notes
2022-10-13 10:17:52PASSED WITH PROVISO: APPROVED ENG PLANS NEED TO BE
 UPLOADED TO THE BUILDING PERMIT.
  
 THANKS,
  
 RICK ROSSANO
 SENIOR PROJECT COORDINATOR
 CITY OF WPB ENGINEERING SERVICES
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-09-27 Cont ID  
Sent By rrossano Date 2022-09-27 Time   Rev Time 0.00
Received By rrossano Date 2022-09-27 Time   Sent To  
Notes
2022-09-27 12:14:50PROJECT IS PENDING ENGINEERING FINAL APPROVAL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-08-02 Cont ID  
Sent By rrossano Date 2022-08-02 Time   Rev Time  
Received By rrossano Date 2022-08-02 Time   Sent To  
Notes
2022-08-02 15:54:31UNDER REVIEW AS FORMAL ENG SUBMITTAL E21020003.

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-12-29 Cont ID  
Sent By pleduc Date 2022-12-29 Time   Rev Time 0.00
Received By pleduc Date 2022-12-29 Time 13:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-12-02 Cont ID  
Sent By pleduc Date 2022-12-02 Time   Rev Time 0.00
Received By pleduc Date 2022-11-30 Time 10:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-10-04 Cont ID  
Sent By pleduc Date 2022-10-04 Time   Rev Time 0.00
Received By pleduc Date 2022-09-29 Time 12:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-08-15 Cont ID  
Sent By pleduc Date 2022-08-15 Time   Rev Time 0.00
Received By pleduc Date 2022-07-27 Time 13:38 Sent To  
Notes
2022-08-12 11:20:01THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS NO INDICATION OF SMOKE CONTROL NOR A
 RATIONAL ANALYSIS DOCUMENT.
  
 PER NFPA 1
  
 11.8* SMOKE CONTROL.
 11.8.1 NEWLY INSTALLED SMOKE-CONTROL SYSTEMS SHALL BE
 IN SPECTED BY THE AHJ AND TESTED IN ACCORDANCE WITH THE
 CRITERIA
 ESTABLISHED IN THE APPROVED DESIGN DOCUMENTS, NFPA 204
 AND
 NFPA 92.
 11.8.2 SMOKE-CONTROL SYSTEMS SHALL HAVE AN APPROVED
 MAINTE NANCE AND TESTING PROGRAM TO ENSURE OPERATIONAL
 INTEGRITY IN
 ACCORDANCE WITH THIS SECTION. COMPONENTS OF SUCH
 SYSTEMS
 SHALL BE OPERATED, MAINTAINED, AND TESTED IN ACCORDANCE
 WITH
 THEIR OPERATION AND MAINTENANCE MANUALS.
 11.8.2.1 TESTING. OPERATIONAL TESTING OF THE
 SMOKE-CONTROL SYS TEM SHALL BE IN ACCORDANCE WITH NFPA
 92, AND SHALL INCLUDE ALL
 EQUIPMENT RELATED TO THE SYSTEM INCLUDING, BUT NOT
 LIMITED TO,
 INITIATING DEVICES, FANS, DAMPERS, CONTROLS, DOORS, AND
 WINDOWS.
 11.8.2.1.1 AN APPROVED WRITTEN SCHEDULE FOR SUCH
 OPERATIONAL
 TESTS SHALL BE ESTABLISHED.
 11.8.2.2 TEST RECORDS SHALL BE MAINTAINED ON THE
 PREMISE
 AND MUST INDICATE THE DATE OF SUCH TESTING, THE
 QUALIFIED SER VICE PERSONNEL, AND ANY CORRECTIVE
 MEASURES NEEDED OR TAKEN
  
 PLEASE PROVIDE THE PROPOSED DOCUMENTS REGARDING THE
 BUILDINGS' SMOKE CONTROL FOR REVIEW.
  
  
 2) THERE IS AN INDICATION OF A COMMAND CENTER BUT NO
 INDICATION OF WHAT EQUIPMENT/LIFE SAFETY MONIOTRING
 WILL BE INCLUDED WITHIN THE COMMAND CENTER
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE
 DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL
 BE APPROVED BY THE FIRE DEPARTMENT.
  
 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER
 HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1
 HOUR.
  
 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A
 MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF
 10 FT (3050 MM).
  
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND CENTER.
 (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE.
 (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES
 OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY
 COMMAND CENTER.
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT.
 (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION
 OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 NFPA 101
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT OF
 COMPLIANCE.
  
  
 3) IT APPEARS THAT THE FIRE PUMP IS ELECTRIC, BUT THERE
 IS NO DETAILED BACKUP POWER SOURCE NOR THE FUEL SUPPLY
 OF THE BACKUP POWER SOURCE.
  
 PER NFPA 70 AND NFPA 20
  
 NFPA 20
  
 9.3 ALTERNATE POWER.
 9.3.1 EXCEPT FOR AN ARRANGEMENT DESCRIBED IN 9.3.3, AT
 LEAST
 ONE ALTERNATE SOURCE OF POWER SHALL BE PROVIDED WHERE
 THE
 HEIGHT OF THE STRUCTURE IS BEYOND THE PUMPING CAPACITY
 OF THE
 FIRE DEPARTMENT APPARATUS.
 9.3.2* OTHER SOURCES. EXCEPT FOR AN ARRANGEMENT
 DESCRIBED IN
 9.3.3, AT LEAST ONE ALTERNATE SOURCE OF POWER SHALL BE
 PROVIDED
 WHERE THE NORMAL SOURCE IS NOT RELIABLE.
 9.3.3 AN ALTERNATE SOURCE OF POWER FOR THE PRIMARY FIRE
 PUMP
 SHALL NOT BE REQUIRED WHERE A BACKUP ENGINE-DRIVEN FIRE
 PUMP,
 BACKUP STEAM TURBINE-DRIVEN FIRE PUMP, OR BACKUP
 ELECTRIC
 MOTOR?DRIVEN FIRE PUMP WITH INDEPENDENT POWER SOURCE
 MEET ING 9.2.2 IS INSTALLED IN ACCORDANCE WITH THIS
 STANDARD.
 9.3.4 WHERE PROVIDED, THE ALTERNATE SOURCE OF POWER
 SHALL BE
 SUPPLIED FROM ONE OF THE FOLLOWING SOURCES:
 (1) A GENERATOR INSTALLED IN ACCORDANCE WITH SECTION
 9.6
 (2) ONE OF THE SOURCES IDENTIFIED IN 9.2.2(1),
 9.2.2(2), 9.2.2(3),
 OR 9.2.2(5) WHERE THE POWER IS PROVIDED INDEPENDENT OF
 THE
 NORMAL SOURCE OF POWER
 9.3.5 WHERE PROVIDED, THE ALTERNATE SUPPLY SHALL BE
 ARRANGED
 SO THAT THE POWER TO THE FIRE PUMP IS NOT DISRUPTED
 WHEN OVER
  
 NFPA 70
  
 ARTICLE 695 FIRE PUMPS
  
 695.3 POWER SOURCE(S) FOR ELECTRIC MOTOR-DRIVEN FIRE
 PUMPS. ELECTRIC MOTOR-DRIVEN FIRE PUMPS SHALL HAVE A
 RELI ABLE SOURCE OF POWER.
 (A) INDIVIDUAL SOURCES. WHERE RELIABLE, AND WHERE CA
 PABLE OF CARRYING INDEFINITELY THE SUM OF THE
 LOCKED-ROTOR
 RRENT OF THE FIRE PUMP MOTOR(S) AND THE PRESSURE MAINTE
 NANCE PUMP MOTOR(S) AND THE FULL-LOAD CURRENT OF THE
 ASSO CIATED FIRE PUMP ACCESSORY EQUIPMENT WHEN
 CONNECTED TO
 THIS POWER SUPPLY, THE POWER SOURCE FOR AN ELECTRIC
 MOTOR
 DRIVEN FIRE PUMP SHALL BE ONE OR MORE OF THE FOLLOWING.
  
 1) ELECTRIC UTILITY SERVICE CONNECTION.
 A FIRE PUMP SHALL BE PERMITTED TO BE SUPPLIED BY A
 SEPARATE SERVICE, OR FROM A
 CONNECTION LOCATED AHEAD OF AND NOT WITHIN THE SAME
 CABI NET, ENCLOSURE, VERTICAL SWITCHGEAR SECTION, OR
 VERTICAL
 SWITCHBOARD SECTION AS THE SERVICE DISCONNECTING MEANS.
 THE CONNECTION SHALL BE LOCATED AND ARRANGED SO AS TO
 MINI MIZE THE POSSIBILITY OF DAMAGE BY FIRE FROM WITHIN
 THE
 PREMISES AND FROM EXPOSING HAZARDS. A TAP AHEAD OF THE
 SER VICE DISCONNECTING MEANS SHALL COMPLY WITH
 230.82(5). THE
 SERVICE EQUIPMENT SHALL COMPLY WITH THE LABELING
 REQUIRE MENTS IN 230.2 AND THE LOCATION REQUIREMENTS IN
 230.72(B).
 [20:9.2.2(1)]
  
 2) ON-SITE POWER PRODUCTION FACILITY. A FIRE PUMP SHALL
 BE PERMITTED TO BE SUPPLIED BY AN ON-SITE POWER
 PRODUCTION
 FACILITY. THE SOURCE FACILITY SHALL BE LOCATED AND
 PROTECTED TO
 MINIMIZE THE POSSIBILITY OF DAMAGE BY FIRE.
 [20:9.2.2(3)]
 (3) DEDICATED FEEDER. A DEDICATED FEEDER SHALL BE
 PERMIT TED WHERE IT IS DERIVED FROM A SERVICE
 CONNECTION AS DE SCRIBED IN 695.3(A)(1). [20:9.2.2(3)]
 (B) MULTIPLE SOURCES. IF RELIABLE POWER CANNOT BE OB
 TAINED FROM A SOURCE DESCRIBED IN 695.3(A), POWER SHALL
 BE
 SUPPLIED BY ONE OF THE FOLLOWING: [20:9.3.2]
 (1) INDIVIDUAL SOURCES. AN APPROVED COMBINATION OF TWO
 OR MORE OF THE SOURCES FROM 695.3(A).
 (2) INDIVIDUAL SOURCE AND ON-SITE STANDBY GENERATOR.
 AN APPROVED COMBINATION OF ONE OR MORE OF THE SOURCES
 IN
 695.3(A) AND AN ON-SITE STANDBY GENERATOR COMPLYING
 WITH
 695.3(D). [20:9.3.4]
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS IN
 COMPLIANCE AND/OR CONFIRM THAT THE FIRE PUMP WILL BE
 BACKED-UP BY THE DIESEL GENERATOR AND THAT THE
 GENERATOR COMPLIES WITH NFPA 110 & 37.
  
  
  
 4) SHEET FA 201 - THERE IS A TWO-WAY COMMUNCATION RISER
 DIAGRAM.
  
 ANY TWO-WAY COMMUNCATION SYSTEM SHALL BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 HOWEVER, ANY SYSTEM SHALL BE SUBMITTED TO THE FIRE
 MARSHAL AND MARK FILLA PALM BEACH COUNTY RADIO MANAGER.
  
 DAQ TESTS AND RSSI/DBM LEVELS WILL NEED TO BE COMPLETED
 AT SUBSTANTIAL CONSTRUCTION (WALLS AND WINDOWS) PRIOR
 TO ANY PERMIT SUBMITTALS.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGMENT ON
 THIS SHEET.
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
2022-07-28 10:56:59 
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2022-12-27 Cont ID  
Sent By rwbrown Date 2022-12-27 Time 06:33 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-12-06 Cont ID  
Sent By ccole Date 2022-12-06 Time 12:18 Rev Time 0.00
Received By ccole Date 2022-12-02 Time 07:38 Sent To  
Notes
2022-12-06 12:23:182ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 22050891
 12/6/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 1) SHEETS FG001, FG101B, FG200, FG201: THERE ARE TWO
 FUTURE RETAIL SPACES HOWEVER ONLY ONE SPECIFICATION
 TABLE WAS PROVIDED ON SHEET FG001 FOR RETAIL 137. THE
 TABLE INDICATES A 4-INCH PIPE FROM THE MP REGULATOR TO
 THE APPLIANCES. BASED ON TABLE 402.4(2) FBC FG, THE
 PIPE IS UNDERSIZED AND MUST BE INCREASED TO 5-INCH.
 A) PLEASE PROVIDE THE SPECIFICATION TABLE FOR FUTURE
 RETAIL 143.
  
 2) FG201: THE 2-INCH SCH 40 GALV. STEEL @14 IN.WC IS
 UNDERSIZED TO SUPPLY BOTH BOILERS PER TABLE 402.4(2)
 AND MUST BE INCREASED TO 2-1/2 INCHES.
  
 3) FG1001, FG201: THE PIPE SIZING TABLE 402.4(2) DOES
 NOT PROVIDE THE GAS PIPE DATA FROM THE MP REG TO THE
 POOL HEATERS. BASED ON THE RISER THE RUN APPEARS TO BE
 APPROXIMATELY 50 FT. TO THE 1ST OF THE 4 POOL HEATERS
 WHICH WOULD REQUIRE A MINIMUM 2-1/2 INCH PIPE, HOWEVER
 THE RISER INDICATES 2-INCH.
  
 4) FG200: AS PREVIOUSLY REQUESTED PLEASE PROVIDE THE
 ESTIMATED OR MAXIMUM GAS LOAD AT THE FUTURE KITCHEN-
 SEC. 402.3 FBC FG.
  
 5) FG201: AS PREVIOUSLY REQUESTED PLEASE PROVIDE THE
 PIPES SIZES FROM THE 2-INCH GAS HEADER TO EACH POOL
 HEATER- SEC. 402.3 FBC FG.
  
 6) FG201, FG301: THE GWH SCHEDULE SPECIFIES 6-INCH FLUE
 AND AIR INTAKE DUCTS BUT THE PLAN SHOWS 4-INCH- SEC.
 624.1 FBC FG.
  
 7) FG202, FG303: THE AIR INTAKE EXHAUST SPECS FOR THE
 WATER HEATERS SPECIFY THE MATERIAL TO BE PVC/CPVC FOR
 EITHER VERTICAL CAT IV VENTING, OR VERTICAL DIRECT
 VENTING. THE PLAN SHOWS POLYPROPLYENE DUCTS WHICH DO
 NOT APPEAR TO MEET THE MANUFACTURER'S SPECIFICATIONS.
 THE SPECS ALSO REFERENCE TABLE V FOR MAXIMUM AND
 MINIMUM VENT LENGTHS. PLEASE PROVIDE THE TABLE AND ALSO
 INDICATE CAT IV OR DIRECT VENT SYSTEM.
  
 8) FG202, FG303: THE SUBMITTED AIR INTAKE AND EXHAUST
 SPECS FOR THE BOILERS SPECIFY A DIRECT VENT SYSTEM BUT
 DO NOT SPECIFY THE TYPE OF DUCT MATERIAL. THE SPECS
 ALSO REFERENCE LENGTH TABLES L AND N WHICH ARE NOT
 INCLUDED IN THE SUBMITTAL. PLEASE PROVIDE A COMPLETE
 SUBMTTAL FOR REVIEW.
  
 9) FG202, FG303: THE AIR INTAKE AND EXAHUST DUCT SPECS
 INDICATE A CONDENSATE DRAIN SHALL BE INSTALLED IN THE
 VENT PIPING FOR BOTH THE WATER HEATERS AND THE BOILERS.
 REFER TO THE MANUFACTURER'S GUIDELINES AND PROVIDE A
 CONDENSATE DISPOSAL PLAN INCLUDING TYPE AND SIZE OF
 PIPING, PIPING RUNS AND DISPOSAL LOACTIONS- SECS. 307.2
 & 307.3 FBC FG.
  
 10) FG103A, FG304, FG305: BASED ON THE SUBMITTED SPECS
 FOR THE POOL HEATER VENTING SYSTEM PLEASE PROVIDE ON
 THE PLAN OR IN A DIAGRAM, THE AIR INTAKE AND EXHAUST
 DUCT TYPES AND SIZES, AND RUN LENGTHS- SEC. 617.1 FBC
 FG.
  
 11) FG001: PLEASE SEE COMMENT #16 FROM THE 1ST REVIEW
 COPIED BELOW HERE AND PROVIDE A NOTE ON THE PLAN TO
 VERIFY COMPLIANCE WILL BE MET.
  
 REFER TO SEC. C408.2 FBC ENERGY- PRIOR TO FINAL
 PLUMBING AND GAS APPROVAL, THE LICENSED DESIGN
 PROFESSIONAL, MECHANICAL ENGINEER, OR APPROVED AGENCY
 SHALL PROVIDE EVIDENCE OF MECHANICAL AND SERVICE WATER
 HEATING COMMISSIONING WITH THE APPLICABLE PROVISIONS OF
 SEC. C408. PLEASE SUBMIT A COMMISSIONING PLAN- SEC.
 C408.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-10-21 Cont ID  
Sent By ccole Date 2022-10-21 Time 08:05 Rev Time 0.00
Received By ccole Date 2022-10-17 Time 15:01 Sent To  
Notes
2022-10-21 08:08:14 
 1ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22050891
 10/20/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. PLEASE NOTE THE GAS PLAN
 SUBMITTAL IS INCOMPLETE. PLEASE REVIEW THE COMMENTS AND
 DETERMINE IF THE GAS SYSTEMS, AND EQUIPMENT AND
 APPLIANCE INSTALLATIONS WILL REMAIN UNDER THE MASTER
 PERMIT, OR WILL BE INSTALLED UNDER SEPARATE PERMITS.
 THE CONTRACTOR HAS THE OPTION OF INCLUDING A PORTION OF
 THE SYSTEM (WATER HEATERS AND BOILER) UNDER THE MASTER
 WITH NOTES TO INDICATE THE KITCHEN, FIREPLACE, AND GAS
 GRILLS WILL BE INSTALLED UNDER SEPARATE PERMITS.
 CONCERNING THE POOL HEATERS PLEASE SEE COMMENT #12
 BELOW.
  
 1) SHEET FG001: PLEASE UPDATE THE CODE REFERENCES TO
 INDICATE THE 2020 FLORIDA FUEL GAS CODE 7TH EDITION-
 SEC. 107.2.1 WPB.
  
 2) FG001 DETAIL 1: PROVIDE PIPE UNIONS WITHIN 1 FT. OF
 EITHER SIDE OF THE REGULATOR- SEC. 410. 2(7) FBC FG.
  
 3) FG200 & FG201: TO HELP EXPEDITE THE REVIEW PLEASE
 PROVIDE THE BRANCH PIPE LENGTH MEASUREMENTS ON THE
 DRAWINGS AND THE TOTAL DEVELOPED LENGTH OF THE SYSTEM-
 SEC. 402.4.1 FBC FG.
  
 4) FG104A & FG200: PLEASE SHOW GAS TIGHT CAPS AT THE
 SUPPLY PIPES TO THE FUTURE KITCHEN APPLIANCES- SEC.
 404.15 FBC FG.
  
 5) FG001 & P503: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE GAS WATER HEATERS (GWH 1-3)- SEC. 624.1 FBC FG.
 PLEASE NOTE INSTALLATION OF THE UNITS SHALL BE IN
 ACCORDANCE WITH THE MANUFACTURER'S GUIDELINES WHICH
 SHALL BE ONSITE FOR INSPECTION.
  
 6) FG001 & P503: PROVIDE EQUIPMENT SCHEDULES FOR THE
 MECHANICAL BOILERS AND SUBMIT MANUFACTURER'S
 SPECIFICATIONS- SEC. 631.1 FBC FG. PLEASE NOTE
 INSTALLATION OF THE UNITS SHALL BE IN ACCORDANCE WITH
 THE MANUFACTURER'S GUIDELINES WHICH SHALL BE ONSITE FOR
 INSPECTION.
  
 7) FG105A: PLEASE SUBMIT AN UPPER ROOF PLAN SHOWING THE
 TERMINATION LOCATIONS OF THE AIR INTAKE AND EXHAUST
 OUTLETS FOR THE DOMESTIC AND MECHANICAL BOILERS- SEC.
 503.6.5 FBC FG. PLEASE NOTE INSTALLATION OF THE UNITS
 SHALL BE IN ACCORDANCE WITH THE MANUFACTURER'S
 GUIDELINES WHICH SHALL BE ONSITE FOR INSPECTION.
  
 8) FG105A: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 UL 1738 AIR INTAKE AND EXHAUST DUCTS- SECS. 502.1,
 5032.3, & 503.8 FBC FG. PLEASE NOTE INSTALLATION OF THE
 DUCT SHALL BE IN ACCORDANCE WITH THE MANUFACTURER???S
 GUIDELINES WHICH SHALL BE ONSITE FOR INSPECTION.
  
 9) FG200: SHOW THE TOTAL BTU LOAD OF THE WATER HEATERS
 AND BOILERS AT THE 3-INCH PIPE ENTRANCE INTO THE ROOM-
 SEC. 402.2 FBC FG.
  
 10) FG201: SHOW SUPPLY PIPE SIZES FROM THE SHUTOFF
 VALVES TO THE GAS WATER HEATERS- SEC. 402.3 FBC FG.
  
 11) FG201: IT APPEARS NO REGULATORS ARE TO BE INSTALLED
 AT THE BOILERS TO REDUCE THE 2 PSI INPUT PRESSURE.
 PLEASE INDICATE THE INPUT PRESSURE RATINGS OF THE
 UNITS- SEC. 410.1 & 631.1 FBC FG. A) SHOW SUPPLY PIPE
 SIZES FROM THE SHUTOFF VALVES TO THE UNITS- SEC. 402.3
 FBC FG.
  
 12) FG001 & P503: SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE POOL HEATERS- SEC. 617.1 FBC FG. PLEASE NOTE
 THAT INSTALLATION OF THE POOL HEATERS INCLUDING FINAL
 CONNECTIONS OF GAS AND PLUMBING PIPING SHALL BE UNDER
 SEPARATE PERMIT- SEC. 105.1 & 107.2.1 WPB. THE
 INSTALLATION OF THE UNITS SHALL BE IN ACCORDANCE WITH
 THE MANUFACTURER'S GUIDELINES WHICH SHALL BE ONSITE FOR
 INSPECTION. CONCERNING THE AIR INTAKE AND EXHAUST DUCTS
 PLEASE SEE COMMENT #8 ABOVE.
  
 13) FG201: SHOW SUPPLY PIPE SIZES FROM THE SHUTOFF
 VALVES TO THE POOL HEATERS- SEC. 402.3 FBC FG.
  
 14) FG200: SHOW THE APPROXIMATE GAS LOAD AT THE FUTURE
 KITCHEN- SEC. 402.3 FBC FG. AS NOTED, GAS TIGHT CAPS AT
 THE SUPPLY PIPES ARE REQUIRED FOR FUTURE.
  
 15) FG001, FG104A, FG200: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE FIREPLACE AND FIREPLACE VENT
 SYSTEM AND PROVIDE AN EQUIPMENT SCHEDULE ON THE PLAN-
 SECS. 604.1 & 605.1 FBC FG.
  
 A) REVISE THE RISER DRAWING TO INCLUDE THE CSST PIPING
 CALLED OUT IN NOTE FG04 (SHEET FG104A).
  
 B) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR IS TO BE PROVIDED- SEC. 304.1 FBC FG.
  
 C) PROVIDE A VENTING DIAGRAM INDICATING THE TYPE AND
 SIZE OF VENT FLUE, TOTAL VENT FLUE RUN AND TERMINATION
 LOCATION. SUBMIT SPECS FOR ALL COMPONENTS OF THE
 SYSTEM- SECS. 502.1 & 503.1 FBC FG.
  
 15) FG001, FG104A, FG200: SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR THE GAS GRILLS AND PROVIDE AN
 EQUIPMENT SCHEDULE ON THE PLAN- SECS. 623.1 FBC FG.
  
 A) PROVIDE INSTALLATION DETAILS ON THE PLAN SHOWING HOW
 THE UNITS WILL BE ANCHORED TO THE OUTDOOR COUNTER
 ASSEMBLIES AND HOW COMBUSTION AIR WILL BE PROVIDED-
 SEC. 107.2.1 WPB & SEC. 304.1 FBC FG.
  
 16) REFER TO SEC. C408.2 FBC ENERGY- PRIOR TO FINAL
 PLUMBING AND GAS APPROVAL, THE LICENSED DESIGN
 PROFESSIONAL, MECHANICAL ENGINEER, OR APPROVED AGENCY
 SHALL PROVIDE EVIDENCE OF MECHANICAL AND SERVICE WATER
 HEATING COMMISSIONING WITH THE APPLICABLE PROVISIONS OF
 SEC. C408. PLEASE SUBMIT A COMMISSIONING PLAN- SEC.
 C408.2.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2023-02-03 Cont ID  
Sent By lmarchan Date 2023-02-03 Time 16:08 Rev Time 0.00
Received By lmarchan Date 2023-02-02 Time 12:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2023-01-18 Cont ID  
Sent By lmarchan Date 2023-01-18 Time 14:27 Rev Time 0.00
Received By lmarchan Date 2022-12-22 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-12 Cont ID  
Sent By cpuell Date 2022-12-12 Time 10:17 Rev Time 0.00
Received By cpuell Date 2022-11-29 Time 10:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-10-24 Cont ID  
Sent By rmcphers Date 2022-10-24 Time 14:26 Rev Time 0.00
Received By rmcphers Date 2022-09-23 Time 10:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-09-21 Cont ID  
Sent By shill Date 2022-09-21 Time 17:49 Rev Time 0.00
Received By shill Date 2022-09-20 Time 06:47 Sent To  
Notes
2022-09-21 17:50:04REMOVED FROM REVIEW PER APPLICANT'S REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-09-01 Cont ID  
Sent By shill Date 2022-09-01 Time 10:11 Rev Time 0.00
Received By shill Date 2022-07-26 Time 06:20 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2022-05-24 Cont ID  
Sent By shill Date 2022-05-24 Time 11:52 Rev Time 0.00
Received By shill Date 2022-05-24 Time 11:52 Sent To  
Notes
2022-05-24 11:53:04MU-2021-034663-0000, RECEIPT NO 2022-0511-140,
 $1,944,464.88
  
 IMPACT FEES PAID UNDER INVOICE FROM 20120019
 HISTORY - FOUNDATION PERMIT 20120019 INCLUDED A FULL
 SET OF PLANS FOR REFERENCE. THIS WAS SENT TO PALM BEACH
 COUNTY IMPACT FEES FOR REVIEW. THE APPLICANT WAS GIVEN
 AN INVOICE. THEY LATER REQUESTED THAT IMPACT FEES BE
 DEFERRED, WHICH WAS GRANTED AT THAT TIME. FOUNDATION
 PREMIT 20120019 WAS ISSUED.
  
 ON 5/11/22 THE OWNER PAID THE INVOICE. THE BUILDING
 PLANS EXAMINER COMPARED BOTH SUBMITTALS (FOUNDATION
 20120019 AND BUILDING/STRUCTURE 21071620) AND CONFIRMED
 THAT THE TWO PLANS ARE THE SAME.
  
 5/24/22 THE APPLICANT INDICATED THAT THE ORIGINAL
 DESIGN PREVIOUSLY PERMITTED HAS CHANGED. THESE CHANGES
 DO NOT AFFECT THE ISSUED FOUNDATION AND STRUCTURE
 PERMITS.
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-12-29 Cont ID  
Sent By medwards Date 2022-12-29 Time 14:12 Rev Time 0.00
Received By medwards Date 2022-12-29 Time 14:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-12-01 Cont ID  
Sent By medwards Date 2022-12-01 Time 11:38 Rev Time 0.00
Received By medwards Date 2022-12-01 Time 11:38 Sent To  
Notes
2022-12-01 11:38:342ND REVIEW FMC
 PERMIT: 22050891
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M201A1: NEW AHU-1-1B FOR THE CART STORAGE IS
 NEW, PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. ALSO SHOW THIS NEW AHU ON THE SCHEDULE
 SHEET M502
  
 2) SHEET M201A1: REVISE THE DRAWING TO SHOW THE OUTDOOR
 AIR DUCT FOR THIS SYSTEM.
  
 3) SHEET M201A1: EF-A IS MISSING FROM THE BOH AREA ON
 THIS REVISED DRAWING, EXPLAIN WHY IT WAS REMOVED.
  
 4) SHEET M201A1: SHOW THE OUTDOOR AIR DUCT WORK FOR
 AHU-1-9 IN THE BIKE STORAGE RESIDENTIAL ROOM AND SHOW
 THE OUTDOOR AIR CALCULATIONS ON SHEET M502 FMC TABLE
 403.3.1.1
  
 5) SHEET M201B1: REVISE THIS DRAWING TO SHOW THE
 OUTDOOR AIR FOR AHU-1-17 FOR THIS CONDITIONED SPACE.
 FMC TABLE 403.3.1.1
  
 6) SHEET M501: DUCT CONSTRUCTION SCHEDULE DOES NOT LIST
 THE DRYER DUCT THAT WAS ASKED FOR IN THE 1ST REVIEW
 COMMENTS. THE DRYER DUCT SHALL MEET FMC 504.8.1
 504.8.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A
 SMOOTH INTERIOR FINISH AND SHALL BE CONSTRUCTED OF
 METAL A MINIMUM 0.016 INCH (0.4 MM) THICK. THE EXHAUST
 DUCT SIZE SHALL BE 4 INCHES (102 MM) NOMINAL IN
 DIAMETER.
  
 7) THE DRYER DUCT LENGTH MUST MEET THE REQUIREMENTS OF
 FMC 504.8.4.1 FOR LENGTH OR USE THE MANUFACTURERS
 INSTRUCTIONS ACCORDING TO FMC 504.8.4.2
  
 8) DRYER SPECS WERE NOT SUBMITTED IN THIS CYCLE FOR
 REVIEW. PLEASE PROVIDE THE DRYER SPECS. FBC 107.3.5
  
 9) PROVIDE THE MANUFACTURERS DUCTING REQUIREMENTS ON
 THE MECHANICAL DRAWINGS FOR THE RESIDENTIAL DRYERS. FMC
 504504.8.4.2
  
 10) COMMENT 25 FROM 1ST REVIEW WAS NOT ANSWERED. SHEETS
 M301- M313 WERE NOT REVISED TO SHOW THE TRANSFER DUCTS.
 UNIT TYPE A AND INIT TYPE B STILL DOES NOT SHOW THE
 TRANSFER AIR GRILLE FOR THE DRYER. PLEASE CORRECT THE
 DRAWING. FBC 107.3.5
  
 11) COMMENT 26 FROM 1ST CYCLE REVIEW WAS NOT ANSWERED.
 26) SHEET M305: PLEASE REVISE THE UNIT TYPE J TO
 INCLUDE THE MISSING DUCTWORK. FBC 107.3.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-10-17 Cont ID  
Sent By medwards Date 2022-10-17 Time 13:24 Rev Time 0.00
Received By medwards Date 2022-10-17 Time 13:24 Sent To  
Notes
2022-10-17 13:24:521ST REVIEW FMC
 PERMIT: 22050891
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADD A NOTE ON THE MECHANICAL DRAWING STATING THAT
 THE GENERATOR WILL REQUIRE A SEPARATE APPLICATION WITH
 DOCUMENTS AND SEPARATE PLAN REVIEW AS THE GENERATOR
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 2) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT
 THE KITCHEN HOODS AND ALL GREASE DUCT WILL REQUIRE A
 SEPARATE PERMIT APPLICATION AND A SEPARATE REVIEW AS IT
 WILL NOT BE REVIEWED UNDER THIS PERMIT.
  
 3) ADD A NOTE TO THE MECHANICAL DRAWINGS STATING THAT
 REFRIGERATION EQUIPMENT WILL REQUIRE A SEPARATE PERMIT
 APPLICATION AND A SEPARATE REVIEW AS IT WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 4) SHEET M201A1: THE BATHROOM IN THE BOH AREA IS
 MISSING AN EXHAUST FAN AND EXHAUST DUCT. PLEASE REVISE
 THE DRAWING TO INCLUDE THE EXHAUST FAN, DUCT AND DUCT
 TERMINATION LOCATION. FMC 501.3
  
 5) SHEET M201A1: THERE IS A SYMBOL IN THE BATHROOM IN
 THE BOH AREA THAT APPEARS TO BE A DAMPER. PLEASE
 IDENTIFY AND STATE THE PURPOSE OF THIS ITEM. FBC
 107.3.5
  
 6) SHEET M201A1: THE MAIL ROOM SHOWS ONLY RETURN AIR
 DUCTWORK, PLEASE INDICATE THE SUPPLY AIR FOR THIS AREA?
 FBC 107.3.5
  
 7) SHEET M201A1: THE LOUNGE, GALLERY AND CONCIERGE
 AREAS DO NOT SHOW ANY RETURN DUCTWORK, PLEASE SHOW THE
 RETURN AIR PATH FROM THESE AREAS TO THE AHU-1-1. FMC
 601.6
  
 8) SHEET M201A1: THE DUCT SMOKE DETECTOR IS SHOWN IN
 THE RETURN SIDE OF AHU-1-1. REVISE THE DRAWING TO SHOW
 A DUCT SMOKE DETECTOR IN THE SUPPLY DUCT OF AHU1-1. FMC
 606.2.1
  
 9) SHEET M201A1: THE EF-A IN THE BOH AREA IS NOT LISTED
 IN THE FAN SCHEDULE ON SHEET M502. PLEASE IDENTIFY THIS
 EF AND EXPLAIN WHAT IT IS EXHAUSTING. FBC 107.3.5
  
 10) SHEET M201B1: THE STAIR WAY 2 CORRIDOR IS AN EXIT
 PASSAGEWAY. REVISE THE MECHANICAL DRAWING TO REMOVE ALL
 DUCTWORK FROM THIS EXIT PASSAGEWAY. FMC 601.3
  
 11) SHEET M201B1: EF-1-4 EXHAUST TERMINATION LOCATION
 MUST MEET THE EXCEPTION OF FMC 501.3.1
  
 12) SHEET M201B1: EF-1-3 APPEARS TO BE EXHAUSTING INTO
 THE LOADING DOCK ACCORDING TO LS101. PLEASE REVISE THE
 DRAWING TO SHOW THAT EF-1-3 IS EXHAUSTING TO THE
 EXTERIOR OF THE BUILDING AND MEETING THE TERMINATION
 REQUIREMENTS OF FMC 501.3.1
  
 13) SHEET M201B1: PLEASE EXPLAIN AHU-1-17 BEING IN THE
 RETAIL/OFFICE TRASH COMPACTOR AREA. FBC 107.3.5
  
 14) SHEET M201A1, SHEET M301: IT APPEARS THAT THE
 EXHAUST DUCTS FOR STUDIO UNITS C AND D PASS THROUGH
 RATED WALLS INTO STUDIO B UNIT. PLEASE REVISE THE
 DRAWING TO INDICATE HOW THESE PENETRATIONS WILL BE
 PROTECTED. FMC 607.5
  
 15) SHEET M202A1: PLEASE EXPLAIN THE 18 X 10 INCH OA
 DUCTWORK PASSING THROUGH THE RATED WALL OF THE CORRIDOR
 AND STUDIO A. WHAT IS IT???S PURPOSE? FBC 107.3.5
  
 16) SHEET M202A1: ALL OF THE EXHAUST IN THE LIVING
 UNITS MUST MEET THE 3 FEET CLEARANCE FROM OPENINGS FOR
 EXHAUST TERMINATION LOCATION. FMC 501.3.1-3
  
 17) ALL SHEETS SHOWING THE BATHROOMS HAVING RETURN AIR
 DUCTS, REVISE THESE DRAWINGS TO REMOVE THE RETURN AIR
 DUCTS FROM THE BATHROOMS. FMC 601.5;7
  
 18) SHEET M202B1: NOTES 60 61 ARE FOR THE EXHAUST FAN
 OUT SIDE OF THE TRASH CHUTE. PLEASE SHOW THE RATED
 SHAFT THAT THIS SUBDUCT WILL ENTER. FBC 107.3.5
  
 19) SHEET M203A1: REVISE THE DRAWING TO INDICATE THE
 BATHROOM EXHAUST CFM???S. FMC TABLE 403.3.1.1
  
 20) * SHOW THAT THE OUTDOOR AIR DUCTS FOR EACH UNIT
 SHALL NOT TERMINATE AT A WALL REGISTER IN THE
 FIRE-RESISTANCE-RATED WALL. FMC 607.5.3 EXCEPTION 3.5
  
 21) SHEET M203B1: NOTES 60 61 ARE FOR THE EXHAUST FAN
 OUT SIDE OF THE TRASH CHUTE. PLEASE SHOW THE RATED
 SHAFT THAT THIS SUBDUCT WILL ENTER. FBC 107.3.5
  
 22) SHEET M203B2: REVISE THE DRAWING TO EXPLAIN THE 16
 X 30 AND 18 X 36 OA DUCTS IN THE OFFICE AREA OF THIS
 FLOOR. ALSO NOTE WHERE THEY ORIGINATE. FBC 107.3.5
  
 23) PROVIDE THE DRYER DUCT MATERIAL, SIZE AND LENGTH
 FOR EACH UNIT INCLUDE ALL 45 AND 90 DEGREE BENDS, OR
 PROVIDE THE SPECIFIC DRYERS TO BE USED AND THE DRYER
 MAX. LENGTH CHART FROM THE MANUFACTURER. FMC 504.8.4
 AND 504.8.4.2
  
 24) PROVIDE DUCT SIZES AND MOTOR CFM???S FOR THE
 KITCHEN HOODS OF EACH UNIT. FMC 505.1 AND 505.2
  
 25) SOME OF THE UNITS HAVE THE TRANSFER GRILLES FOR THE
 MAKE UP AIR FOR THE DRYER EXHAUST AND SOME DO NOT.
 PLEASE SHOW THE DRYER EXHAUST CFM???S OR PROVIDE THE
 MAKE UP AIR TRANSFER GRILLE FOR THE DRYERS IN EACH
 UNIT. FMC 504.6
  
 26) SHEET M305: PLEASE REVISE THE UNIT TYPE J TO
 INCLUDE THE MISSING DUCTWORK. FBC 107.3.5
  
 27) SHEET M502: THE BEAUTY AND NAIL SALONS LISTED
 TOGETHER IN THE VENTILATION CALCULATIONS SHOULD BE
 SEPARATED AND LIST EACH SEPARATELY AS THEY ARE LISTED
 SEPARATELY IN FMC TABLE 403.3.1.1. ALSO ADDA NOTE FOR
 THE REQUIREMENTS IN FMC TABLE 403.3.1.1 FOOTNOTE H.
  
 28) PROVIDE A TRASH CHUTE AND VENT RISER DIAGRAM. FMC
 601.1 AND NFPA 82-2014
  
 29) PROVIDE A PARKING GARAGE MECHANICAL VENTILATION
 DESIGN ACCORDING TO FMC 404.1
  
 30) SHEET M203A2: PLEASE SPECIFY WHICH OA UNIT IS
 SUPPLYING THE 38 X 14 INCH OA SD-28. FBC 107.3.5
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-27 Cont ID  
Sent By rwbrown Date 2022-12-27 Time 06:33 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-12-06 Cont ID  
Sent By ccole Date 2022-12-06 Time 17:33 Rev Time 0.00
Received By ccole Date 2022-12-02 Time 07:38 Sent To  
Notes
2022-12-06 17:37:232ND REVIEW FBC-2017 PLUMBING
 PERMIT- 22050891
 12/2/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 6TH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE 6TH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 6TH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. THE REQUESTED PERMIT APPLICATIONS FOR THE
 POTABLE WATER BACKFLOW PREVENTER AND THE SAND
 INTERCEPTOR WERE NOT PROVIDED.
  
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL PERMIT APPLICATIONS FOR THE BACKFLOW
 AND INTERCEPTOR HAVE BEEN SUBMITTED. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected]. YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT GENERATED, NOTIFY ME VIA EMAIL AND
 I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 2) FAILED. NO CORRECTIONS WERE MADE TO SHOW POOL
 WASTEWATER IN THE POOL EQUIPMENT ROOM VIA THE FLOOR
 DRAINS WILL BE DECHLORINATED AND DISCHARGED INTO THE
 CITY STORMWARTER SYSTEM- SEC. 90-205(1) WPB CODE OF
 ORDINANCES.
  
  
 3) FAILED. PLUMBING FIXTURE CALCULATIONS- SHEETS LS100,
 LS101, LS2102, LS103, LS104, P SHEETS. CONCERNING THE
 REQUIRED NUMBER OF PLUMBING FIXTURES FOR LEVELS 3 & 4
 WHICH ARE NOW GROUPED TOGETHER IN THE CALCULATION
 TABLES, THE ARCHITECT'S NARRATIVE RESPONSE CITES SEC.
 403.3.3 OF THE FBC- P. "THE REQUIRED PUBLIC AND
 EMPLOYEE TOILET FACILITIES SHALL BE LOCATED NOT MORE
 THAN ONE STORY ABOVE OR BELOW THE SPACE REQUIRED TO BE
 PROVIDED WITH TOILET FACILITIES". THIS SECTION DOES NOT
 APPEAR TO APPLY TO THE POOL DECK AND AMENITY AREAS
 WHICH THE ARCHITECT STATES IN THE NARRATIVE ARE
 "NONCOMMERCIAL PRIVATE SPACES". CONCERNING THE LEVEL 4
 POOL AND AMENITY BATHROOMS, THE ARCHITECT STATES "PER
 EXCEPTION B ADDITIONAL FIXTURES ARE LOCATED INSIDE THE
 BUILDING". IT APPEARS THE EXCEPTION BEING CITED IS THE
 EXCEPTION UNDER SEC. 454.1.6.1.1 FBC B WHICH IS COPIED
 HERE FOR CLARITY.
  
 EXCEPTION: WHEN A PUBLIC SWIMMING POOL MEETS ALL OF THE
 FOLLOWING CONDITIONS THE FOLLOWING SHALL APPLY:
 1. THE POOL SERVES ONLY A DESIGNATED GROUP OF DWELLING
 UNITS,
 2. THE POOL IS NOT FOR THE USE OF THE GENERAL PUBLIC,
 AND
 3. A BUILDING PROVIDES SANITARY FACILITIES;
 THE FIXTURE REQUIREMENT FOR THE BUILDING SHALL BE
 DETERMINED AND IF IT EXCEEDS THE REQUIREMENT IN TABLE
 454.1.6.1 THEN THE BUILDING REQUIREMENT SHALL REGULATE
 THE FIXTURE COUNT, OTHERWISE THE FIXTURE COUNT SHALL BE
 BASED ON THE REQUIREMENT FOR THE POOL. UNDER NO
 CIRCUMSTANCES SHALL THE FIXTURE COUNTS BE CUMULATIVE.
 AN ADDITIONAL SET OF FIXTURES SHALL BE PROVIDED IN THE
 MEN'S RESTROOM FOR EVERY 7,500 SQUARE FEET OR MAJOR
 FRACTION THEREOF FOR POOLS GREATER THAN 10,000 SQUARE
 FEET.
 WOMEN'S RESTROOMS SHALL HAVE A RATIO OF THREE TO TWO
 WATER CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS PROVIDED FOR MEN.
 LAVATORY COUNTS SHALL BE EQUAL.
  
 BASED ON THIS EXCEPTION IT APPEARS THE ARCHITECT IS
 CHOOSING THE BUILDING REQUIREMENT TO REGULATE THE
 FIXTURE COUNT WHICH IS ACCEPTABLE HOWEVER THE EXCEPTION
 ALSO REQUIRES THE THREE TO TWO WATER CLOSET RATIO FOR
 WOMEN IN THE RESTROOMS. PLEASE REVISE THE PLANS
 ACCORDINGLY.
 A SECOND OPTION WOULD BE TO LABEL THE BATHROOMS BY THE
 POOL AS POOL BATHROOMS FOR MALE AND FEMALE AND SHOW
 SEPARATE CALCULATIONS FOR THE POOL (NOTE: THE CALCS
 ASSUME A DECK AREA THREE TIMES THE SQUARE FOOTAGE OF
 THE POOL). CALCULATIONS WOULD THEN HAVE TO SHOW THE TWO
 REMAINING UNISEX RESTROOMS WOULD ACCOMMODATE THE
 REMAINING ASSEMBLY OCCUPANT LOAD ON THE FLOOR.
  
 CONCERNING THE POOL BATHROOMS PLEASE NOTE THE FOLLOWING
 REQUIREMENTS.
  
 A) SEC. 403.6.1 FBC P: POOL BATHROOMS FOR FEMALE USE
 SHALL HAVE A RATIO OF THREE TO TWO WATER CLOSETS
 PROVIDED AS THE COMBINED TOTAL OF WATER CLOSETS AND
 URINALS PROVIDED FOR MALE USE.
  
 B) SEC. 454.1.6.1.1 FBC B REQUIRES EACH BATHROOM TO
 CONTAIN A DIAPER CHANGING STATION- SEC. 454.1.6.1.1.
  
 C) SEC. 454.1.6.1.3 FBC B REQUIRES EACH BATHROOM TO
 CONTAIN A FLOOR DRAIN- SEC. 454.1.6.1.3.
  
 D) SEC. 454.1.6.1.4 REQUIRES A HOSE BIB WITH A VACUUM
 BREAKER TO BE INSTALLED WITHIN 25 FT. OF EACH BATHROOM.
  
 4) A408 DETAIL 2- FBC ACC COMPLIANCES
 A) PROVIDE THE SHOWER DIMENSIONS AND OPENING WIDTHS-
 SEC. 608.2.3
 B) SHOW THE 30X60-INCH CLEAR FLOOR APPROACH SPACES AT
 THE SHOWERS- SEC. 608.2.2.1.
 C) SHOW THE SHOWER GRAB BAR LENGTHS AND MOUNTING
 HEIGHTS- SECS. 608.3.3 & 609.4. PLEASE NOTE THE DETAILS
 ON SHEET A810 ARE NOT COMPLIANT FOR THE ALTERNATE-TYPE
 SHOWERS SHOWN ON THE PLAN.
 D) SHOW THE SHOWER CONTROL LOCATIONS- SEC. 608.5.3.
 PLEASE NOTE THE DETAILS ON SHEET A810 ARE NOT COMPLIANT
 FOR THE ALTERNATE-TYPE SHOWERS SHOWN ON THE PLAN.
  
 5) A408 DETAIL 2: PROVIDE THE DIMENSIONS OF THE
 STANDARD WATER CLOSET COMPARTMENTS- WIDTHS AND DEPTHS-
 SEC. 405.3.1 FBC P.
  
 6) A408 DETAIL 4: THE DOORS ARE SWINGING INTO THE CLEAR
 FLOOR SPACES FOR THE LAVATORIES AND THE 30X48 CLEAR
 FLOOR SPACE WHICH SHOULD BE LOCATED BEYOND THE ARC OF
 THE DOOR- SEC. 603.2.3 EXCEPTION 2 FBC ACC.
  
 7) A408 DETAIL 4: SHOW THE CLEAR FLOOR SPACE DIAGRAMS
 AND DIMENSIONS POSITIONED FOR A FORWARD APPROACH TO THE
 LAVATORIES- SEC. 606.2 FBC ACC. PARALLEL APPROACHES TO
 ACCESSIBLE LAVATORIES ARE NOT ALLOWED.
  
 8) SHEETS A600- A-611, & A640- A645, A660- A665,
 A670-A681 & A810: IN RESPONSE TO THE PREVIOUS COMMENT
 REQUESTING THE DESIGN INTENTION FOR THE DWELLING UNITS
 THE ARCHITECT STATES IN THE NARRATIVE- "DRAWINGS
 ILLUSTRATE FHA REQUIREMENTS". HOWEVER NO DESIGN
 STANDARD IS INDICATED ON THE PLAN. PLEASE NOTE THERE
 ARE SEVEN DIFFERENT COMPLIANCE PATHS THAT WILL PROVIDE
 SAFE HARBOR FOR THE RESIDENTIAL DWELLING UNITS
 INDICATED IN THE FAIR HOUSING DESIGN ACT MANUAL. SINCE
 MOST OF THE UNITS FLOOR PLANS SHOWN ARE LABELED AS TYPE
 B IT APPEARS THAT THE DESIGN STANDARD USED IS THE
 ICC/ANSI A117.1. TYPE B UNITS ARE SPECIFIED IN SEC.
 1001.1 OF THE ANSI STANDARD. SEC. 1001.1 REFERS TO SEC.
 1002.11.2 WHICH STATES A MINIMUM OF ONE BATHROOM SHALL
 HAVE FIXTURES INSTALLATIONS IN COMPLIANCE WITH SECS.
 603- 610. LOOKING AT THE CLEAR FLOOR SPACE OUTLINES FOR
 THE FIXTURES SHOWN ON THE PLANS IT APPEARS MANY OF THE
 BATHROOMS WILL NOT COMPLY AS TYPE B, BUT RATHER AS TYPE
 A BECAUSE THE FIXTURE CLEARANCES SHOWN DO NOT PROVIDE
 THE GREATER ACCESS PROVIDED UNDER TYPE B. AS STATED IN
 THE FIRST REVIEW A COMPLETE FHA REVIEW CANNOT BE
 COMPLETED WITHOUT THE DIMENSIONS OF THE CLEAR FLOOR
 SPACES WHICH STILL HAVE NOT BEEN PROVIDED.
  
  
 9) IN RESPONSE TO COMMENT #13, NEW SHEETS P360, P361,
 362 HAVE BEEN SUBMITTED PER THE ENGINEER'S NARRATIVE
 AND ALSO DETAIL 13.
 A) P360: CORRECT THE NOTE AT THE TOP OF THE RISER TO
 INDICATE P361 FOR CONTINUATION- SEC. 107.2.1 WPB.
 B) P360, P361, P362: MANY OF THE VENT SIZES ARE NOT
 SHOWN INCLUDING THE STACK VENTS ON P362, AND FOR
 CLARITY PLEASE EXTEND THE SOME OF BLUE LINES
 REPRESENTING VENTS ON P360 A LITTLE HIGHER SO THEY CAN
 BE LOCATED EASIER- SEC. 107.2.1 WPB.
 C) P360, P361, P362: VENT STACKS ARE REQUIRED FOR THE
 DRAINAGE STACKS THAT HAVE FIVE BRANCH INTERVALS OR
 MORE. PLEASE SHOW THESE VENTS IN BLUE LINES
 CONTINUOUSLY FROM THE POINTS OF CONNECTIONS AT OR BELOW
 THE LOWEST HORIZONTAL BRANCH, AND WHERE THEY ARE
 CONNECTING TO THE BUILDING DRAIN, SHOW THE CONNECTIONS
 DOWNSTREAM OF THE DRAINAGE STACK WITHIN A DISTANCE OF
 10 TIMES THE DIAMETER OF THE STACK- SEC. 904.4 FBC P.
 IF NOT ABLE TO SHOW THE RUNS PLEASE LABEL THEM AS VENT
 STACKS.
 D) P362: THIS SHEET IS TITLED PH1 TO ROOF, BUT IT SHOWS
 CONTINUATIONS FROM P361 WHICH WOULD INDICATE LEVEL 7 TO
 ROOF. PLEASE CORRECT.
 E) P360, P361, & P362: PLEASE LABEL THE WASTE STACKS
 FOR WASHING MACHINES AND SINKS TO VERIFY THERE ARE NOT
 OFFSETS BETWEEN THE LOWEST FIXTURE DRAIN AND CONNECTION
 AND HIGHEST DRAIN CONNECTION- SEC.913.2 FBC P.
 F) P361 & P362: PLEASE LABEL THE RELIEF VENT LOCATIONS
 AND WHICH FLOOR INTERVALS THEY ARE LOCATED AT. SHOW THE
 VENT SIZES, AND FOR CLARITY, SHOW THE VENT RUNS
 CONTINUOUSLY FROM THE LOWER AND UPPER POINTS OF
 CONNECTIONS- SEC. 908.2 FBC P.
 G) I WAS NOT ABLE TO LOCATED DETAIL 13.
  
 10) IN RESPONSE TO COMMENT #18, NEW SHEETS P220, P221,
 & P222 HAVE BEEN SUBMITTED. PLEASE SHOW THE DW RISER
 NUMBERS ON SHEET P222 AS THEY ARE SHOWN ON P220 & P221.
  
 11) IN RESPONSE TO COMMENT #21 THE ENGINEER REFERENCES
 NOTES 41 & 43 ON SHEET P001, HOWEVER THE LAVATORY
 DETAIL 10 ON P501 DOES NOT SHOW THE TEMPERED WATER
 MIXING VALVE. PLEASE REVISE THE DETAIL TO SHOW THE
 LOCATION OF THE VALVE AND PIPING CONNECTIONS. PLEASE
 NOTE A DEDICATED FULL OPEN SHUTOFF VALVE IS REQUIRED
 FOR THE COLD WATER LINE TO THE POINT OF USE WATER
 HEATER- SEC. 503.1 FBC P.
  
 12) IN RESPONSE TO COMMENT #25 A DOUBLE CHECK VALVE
 BACKFLOW ASSEMBLY IS SPECIFIED FOR THE MAKEUP WATER
 LINE TO THE COOLING TOWERS, HOWEVER AN RPZ IS REQUIRED
 PER SEC. E TABLE 1.1 WPB UTILITIES CROSS-CONNECTION
 MANUAL. PLEASE CORRECT THE NOTE AND ADD THE MAKE AND
 MODEL OF THE ASSEMBLY TO THE BACKFLOW SCHEDULE ON P504.
  
 13) IN RESPONSE TO COMMENT #26, WATER HAMMER ARRESTORS
 ARE PROVIDED FOR THE WASHING MACHINE SUPPLY LINES
 HOWEVER NOT PROVIDED FOR THE ICE MAKER AND DISHWASHER
 LINES- SEC. 604.9 FBC P.
  
 14) IN RESPONSE TO COMMENT #29 THE ENGINEER REFERENCES
 SHEET P329 FOR THE SANITARY PLAN AND RISER WHICH ARE
 NOT SHOWN ON THE PLAN- SECS. 107.2.1 & 107.3.5.1.3 WPB.
  
 15) IN RESPONSE TO COMMENT #29 THE SANITARY RISERS AND
 LAYOUT PLANS WERE NOT PROVIDED FOR THE DWELLING UNIT
 PLANS ON P333- P340- SEC. 107.2.1 & 107.3.5.1.3 WPB.
  
 16) IN RESPONSE TO COMMENTS 30-32 STORM DRAINAGE AREA
 PLANS HAVE BEEN SUBMITTED.
  
 A) SHEET P402: IT APPEARS SECONDARY OR OVERFLOW DRAINS
 HAVE NOT BEEN PROVIDED IN AREAS L1- L8 WHERE THERE THE
 SIZING TABLE SHOWS VERTICAL WALL CALCULATIONS- SEC.
 1108.1 FBC P.
  
 B) SHEET P404: IT APPEARS SECONDARY OR OVERFLOW DRAINS
 HAVE NOT BEEN PROVIDED IN AREAS T8, T9, T29, T30, T43,
 T44, T45, & T46 WHERE THE SIZING TABLE SHOWS VERTICAL
 WALL CALCULATIONS- SEC. 1108.1 FBC P. SECONDARY DRAINS
 ARE SHOWN ON THE PLANS IN OTHER AREAS NOT HAVING
 VERTICAL WALL CALCULATIONS SUCH AS T3, T4, T5 ETC.
 PLEASE CLARIFY.
  
 17) IN RESPONSE TO COMMENT #32 A GREASE WASTE LINE HAS
 BEEN ADDED ON SHEET P104C. PLEASE SHOW THE NEW LINE
 CONNECTION ON SHEET P101C- SEC. 107.2.1 WPB. PLEASE
 REVISE THE GREASE WASTE CALCULATIONS ON SHEET P505-
 SEC. 1003.3.4 FBC P.
  
 18) IN RESPONSE TO COMMENT #33 DRAINS HAVE BEEN
 PROVIDED IN THE STEAM ROOMS, HOWEVER THE PLAN DOES NOT
 SHOW DRAINS IN THE SHOWERS- SEC. 417.3 FBC P. PLEASE
 PROVIDE A SHOWER PAN DETAIL- SEC. 417.5.2.
  
 19) IN REPONSE TO COMMENT #33 STEAM GENERATOR SPEC
 SHEETS HAVE BEEN SUBMITTED INDICATING THE UNITS ARE
 EQUIPPED WITH 3/4-INCH SAFETY VALVES REQUIRING INDIRECT
 WASTE PIPES AND WASTE RECEPTORS. PLEASE PROVIDE
 DETAILS- SEC. 107.2.1 WPB.
  
 20) NO RESPONSE WAS MADE TO COMMENT #36 COPIED HERE.
 P101B: AN OIL INTERCEPTOR MAY BE REQUIRED TO RECEIVE
 THE DRAINAGE FROM THE TRASH COMPACTOR FOR SEPARATION
 AND DISPOSAL. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR REVIEW- SEC. 1003.4 FBC P.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-10-20 Cont ID  
Sent By ccole Date 2022-10-20 Time 15:15 Rev Time 0.00
Received By ccole Date 2022-10-17 Time 15:01 Sent To  
Notes
2022-10-20 15:21:241ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22050891
 10/18/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE FOLLOWING ITEMS SHOWN ON THE PLANS:
 * POTABLE WATER SERVICE BACKFLOW PREVENTER.
 * GREASE AND SOLIDS INTERCEPTORS.
 * SAND INTERCEPTOR.
 THE SUBMITTED PLUMBING PLANS FOR THE BUILDING WILL NOT
 BE APPROVED UNTIL PERMIT APPLICATIONS FOR THOSE ITEMS
 HAVE BEEN SUBMITTED. YOU CAN SUBMIT AN APPLICATION TBD
 (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR
 SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected]. YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT GENERATED, NOTIFY ME VIA EMAIL AND I WILL CHANGE
 THE REVIEW STATUS TO PASS.
  
 2) SEPARATE PERMITS AND PLANS ARE ALSO REQUIRED FOR THE
 POOL, IRRIGATION SYSTEM, AND THE IRRIGATION SYSTEM
 BACKFLOW PREVENTER- SEC. 107.2.1 WPB. COMPLETE REVIEWS
 OF THOSE ITEMS ARE NOT BEING CONDUCTED AT THIS TIME.
 CONCERNING THE POOL- SHEET P103A SHOWS A FLOOR DRAIN IN
 THE POOL EQUIPMENT ROOM AND FLOOR DRAINS THAT APPEAR TO
 BE BELOW THE POOL SHELL POSSIBLY FOR POOL LEAKAGE OR
 DRAINAGE. THESE DRAINS ARE DISCHARGING INTO THE
 SANITARY SYSTEM. PLEASE BE ADVISED THAT POOL WASTEWATER
 SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM IN
 ACCORDANCE WITH SEC. 90-126(5) WPB CODE OF ORDINANCES.
 REVIEW THE INFORMATION BELOW:
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED
 TO FILTER THROUGH GRASS AREA ON THE POOL OWNER'S
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 3) PLUMBING FIXTURE CALCULATIONS- SHEETS LS100, LS101,
 LS2102, LS103, LS104, P SHEETS:
  
 A) LEVEL-1: PROVIDE 2 WATER CLOSETS FOR MALE USE AND 2
 WATER CLOSETS FOR FEMALE USE- TABLE 403.1 FBC P. THE
 FLOOR PLAN SHOWS ONE SINGLE USER TOILET ROOM WITH ONE
 WATER CLOSET IN THE BOH WHICH WILL NOT MEET COMPLIANCE.
 FIXTURES ARE REQUIRED FOR PUBLIC AND EMPLOYEE USE, AND
 SEPARATE FACILITIES FOR MALE AND FEMALE USE ARE
 REQUIRED- SEC. 403.2 & 403.3. LAVATORIES FOR EACH
 SEPARATE TOILET ROOM ARE ALSO REQUIRED PER SEC. 403.7.
 B) LEVEL-1: PROVIDE A MINIMUM OF TWO DRINKING FOUNTAINS
 FOR PUBLIC AND EMPLOYEE USE- TABLE 403.1 AND SEC.
 410.3. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 C) LEVEL-1: PLEASE REVISE THE CALCULATION TABLE TO SHOW
 THE TOTAL PROVIDED NUMBER OF FIXTURES.
 D) LEVEL-2: OCCUPANT LOAD, RESTROOM LOCATIONS AND
 PLUMBING PIPING DETAILS HAVE BEEN PROVIDED FOR THE
 FUTURE OFFICE/STORAGE TENANT. PLEASE PROVIDE THE
 FIXTURE CALCULATIONS PER TABLE 403.1. PLEASE NOTE A
 MINIMUM OF TWO DRINKING FOUNTAINS FOR PUBLIC AND
 EMPLOYEE USE ARE REQUIRED- TABLE 403.1 AND SEC. 410.3.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 E) LEVEL-3: PLEASE LABEL THE RESTROOMS IN THE OFFICE
 AND BREAKROOM AS MALE, FEMALE, OR UNISEX- SEC. 403.4
 FBC P.
 F) LEVEL-3: BASED ON THE CALCULATIONS A 3RD FEMALE
 WATER CLOSET IS REQUIRED FOR THE A-3 AREA. THERE ARE
 ONLY 2 AVAILABLE IN THE SPA BATHROOMS- TABLE 403.1 FBC
 P.
 G) LEVEL-3: PROVIDE A MINIMUM OF TWO DRINKING FOUNTAINS
 FOR PUBLIC AND EMPLOYEE USE- TABLE 403.1 AND SEC.
 410.3. ONE DRINKING FOUNTAIN SHALL COMPLY WITH THE
 REQUIREMENTS FOR PEOPLE WHO USE A WHEELCHAIR AND ONE
 DRINKING FOUNTAIN SHALL COMPLY WITH THE REQUIREMENTS
 FOR STANDING PERSONS.
 H) LEVEL-3: SHOW THE LOCATION OF THE REQUIRED SERVICE
 SINK FOR THE OCCUPANCIES- TABLE 403.1.
 I) LEVEL-4: THE CALCULATION TABLE DOES NOT ACCOUNT FOR
 THE BAR AND DINING AREAS WHICH HAVE RATIOS OF 1 PER 40
 AND 1 PER 75 FOR WATER CLOSETS AND LAVATORIES- TABLE
 403.1. PLEASE PROVIDE A BREAKDOWN CALCULATION THAT
 INCLUDES THE SQ. FOOTAGE AND ASSOCIATED OCCUPANT LOADS
 OF ALL AMENITY AREAS AND REVISE THE TABLE ACCORDINGLY.
 J) LEVEL-4: SEC. 454.1.6.1.1 EXCEPTION FBC B ALLOWS FOR
 THE BUILDING TO PROVIDE THE REQUIRED NUMBER OF POOL
 BATHROOM FIXTURES HOWEVER INDIVIDUAL CALCULATION TABLES
 HAVE BEEN PROVIDED FOR THE ASSEMBLY OCCUPANCY AND THE
 POOL. PLEASE CLARIFY IF THE BATHROOMS BY THE DECK AND
 BAR ARE DESIGNATED FOR THE POOL AND LABEL THEM
 ACCORDINGLY. PLEASE NOTE SEC. 403.6.1 FBC P REQUIRES
 WOMEN'S POOL RESTROOMS TO HAVE A RATIO OF THREE TO TWO
 WATER CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL
 OF WATER CLOSETS AND URINALS PROVIDED FOR MEN. IT
 APPEARS ONE ADDITIONAL FEMALE WATER CLOSET IS REQUIRED.
 LAVATORY COUNTS SHALL BE EQUAL.
 K) LEVEL-4: PROVIDE AN AREA CALCULATION FOR THE POOL
 DECK TO SHOW COMPLIANCE WITH TABLE AND SEC. 403.6.1.
 THE FIXTURE COUNT OF TABLE 403.6 IS DEEMED TO BE
 ADEQUATE FOR THE POOL AND POOL DECK AREA THAT IS UP TO
 THREE TIMES THE AREA OF THE POOL SURFACE PROVIDED.
 L) LEVEL-4: CORRECT THE ASSEMBLY CALCULATION FOR MALE
 WATER CLOSETS TO INDICATE 1.39 REQUIRED. THE PLANS
 APPEAR TO INDICATE A SHORTAGE OF ONE MALE WATER CLOSET,
 ONE MALE LAVATORY, TWO FEMALE WATER CLOSETS, AND ONE
 FEMALE LAVATORY FOR THE ASSEMBLY OCCUPANCY.
 M) LEVEL-4: SHOW THE LOCATION OF THE REQUIRED SERVICE
 SINK FOR THE OCCUPANCIES- TABLE 403.1.
  
 4) LS100: PLEASE UPDATE THE APPLICABLE CODE REFERENCES
 TO INDICATE THE 2020 FLORIDA BUILDING CODE 7TH EDITION
 WHICH IS THE CURRENT CODE IN EFFECT- SEC. 107.2.1 WPB.
 A) PLEASE ADD THE 2020 FBC ACCESSIBILITY 7TH EDITION TO
 THE APPLICABLE CODES LIST. COMPLIANCE WITH THE FBC ACC
 REQUIRES THAT A PERCENTAGE OF THE NEW DWELLING UNITS
 SHALL BE DESIGNED AND CONSTRUCTED MOBILITY FEATURES
 COMPLYING WITH SECS. 809.2- 809.4 AND COMMUNICATION
 FEATURES COMPLYING WITH SEC. 809.5. FACILITIES
 REGULATED BY THE DEPARTMENT OF HOUSING AND URBAN
 DEVELOPMENT (HUD)- SEC. 233.2 SHALL HAVE THE NUMBER OF
 UNITS IN COMPLIANCE DETERMINED BY HUD. FACILITIES NOT
 SUBJECT TO HUD SHALL HAVE AT LEAST 5% OF THE UNITS
 DESIGNED AND CONSTRUCTED WITH MOBILITY FEATURES AND 2%
 WITH COMMUNICATION FEATURES. TO HELP EXPEDITE THE
 REVIEW PLEASE PROVIDE A LIST OF APARTMENTS THAT ARE
 MEETING COMPLIANCE. PLEASE NOTE THE UNITS SHALL BE
 DISPERSED AMONG THE VARIOUS TYPES OF UNITS IN THE
 FACILITY- SEC. 233.3.5. CONCERNING THE TOILET AND
 BATHING FACILITIES PLEASE REFER TO SEC. 809.4 WHICH
 REFERENCES SECS. 603-610 FOR FIXTURE COMPLIANCE.
 CONCERNING PLUMBING FIXTURES AND APPLIANCES IN THE
 KITCHENS PLEASE REFER TO SECS. 809.3 & 804.
 B) COMPLIANCE WITH OTHER FEDERAL LAWS SUCH AS THE FAIR
 HOUSING ACT AND SECTION 504 OF THE REHABILITATION ACT
 OF 1973, AS AMENDED IS REQUIRED. PLEASE REFER TO THE
 FAIR HOUSING DESIGN ACT MANUAL FOR FURTHER INFORMATION-
 SEE PAGE 1 OF THE INTRODUCTION. CLARIFY HOW COMPLIANCE
 WITH THE ACT AND SAFE HARBOR FOR THE FACILITY IS BEING
 PROVIDED.
  
 5) SHEET A408 DETAILS 1-6: PLEASE PROVIDE THE FOLLOWING
 FBC ACC COMPLIANCE INFORMATION:
 A) DIMENSIONS OF THE CLEAR FLOOR SPACE DIAGRAMS FOR THE
 WATER CLOSETS, LAVATORIES, AND URINAL- SECS. 604.3,
 605.3 & 606.2.
 B) DIAMETERS OF THE TURNING CIRCLES- SEC. 304.3 FBC
 ACC.
 C) ACCESSIBLE SHOWER DIMENSIONS- SECS. 213.3.6, 608.2.1
 AND/OR 608.2.2 FBC ACC.
 D) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 ACCESSIBLE SHOWERS- SECS. 608.2.1 AND/OR 608.2.2.
 E) SHOW THE SAUNA AND STEAM ROOM BENCH LOCATIONS AND
 CLEAR FLOOR SPACE DIAGRAMS WITH DIMENSIONS- SEC. 612.2
 PLEASE PROVIDE ENLARGED BENCH DETAILS- SECS. 903.3-
 903.7.
 F) SHOW THE REQUIRED TURNING SPACES WITH DIMENSIONS
 INSIDE THE SAUNAS AND STEAM ROOMS- SECS. 612.3 & 304.1.
  
 6) A408: PROVIDE THE STANDARD TOILET COMPARTMENT
 DIMENSIONS- SEC. 405.3.1 FBC P.
  
 7) A810: PROVIDE ACCESSIBLE SHOWER DETAILS PER FBC ACC.
 A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECS. 608.3.1 AND/OR 608.3.2.
 B) LOCATION OF CONTROLS, FAUCETS, AND SHOWER SPRAYS-
 SECS. 608.5.1 AND/OR 608.5.2.
 C) LOCATION OF ACCESSIBLE SEATS AND MOUNTING DETAILS
 (IF APPLICABLE)- SECS. 610.3, 610.3.1, & 610.3.2.
  
 8) SHEETS A600- A-611, & A640- A645, A660- A665,
 A670-A681: A THOROUGH REVIEW OF THE RESIDENTIAL BATH
 AND KITCHEN PLUMBING FIXTURE INSTALLATIONS CANNOT BE
 CONDUCTED WITHOUT THE NECESSARY CODE REFERENCE DATA
 INFORMATION PROVIDED AS REQUESTED IN COMMENTS 4A & 4B
 ABOVE. TO HELP EXPEDITE THE RE- REVIEW PLEASE LABEL ALL
 UNITS THAT ARE ACCESSIBLE OR FHDA COMPLIANT AND PROVIDE
 COMPLETE KITCHEN AND BATH COMPLIANCE DETAILS.
  
 9) SHEET P100: THE DRAINAGE FROM THE SAND INTERCEPTOR
 SHALL DISCHARGE INTO THE SANITARY SEWER AND NOT INTO
 THE STORM DRAIN PER SEC. 90- 203(A) WPB CODE OF
 ORDINANCES. SEC. 90-203. - PROHIBITED GENERAL
 PROHIBITION. EXCEPT AS PROVIDED IN SECTION 90-205, AND
 EXCEPT PURSUANT TO A VALID NPDES PERMIT, IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO DIRECTLY OR INDIRECTLY
 DEPOSIT, DISCHARGE, SPILL, OR DUMP INTO ANY OF THE
 PUBLIC WATERS OR MUNICIPAL SEPARATE STORM SEWER SYSTEM
 WITHIN THE CITY, ANY SUBSTANCE OTHER THAN THAT COMPOSED
 ENTIRELY OF STORMWATER.
 IF YOU HAVE FURTHER QUESTIONS PLEASE CONTACT-
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS ST., 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-494-1120
 FAX: 561-494-1116
 CELL 561-351-0510
 [email protected]
  
 10) SHEETS P100 & P501 DETAIL 6: AS NOTED IN COMMENT #1
 THE SAND INTERCEPTOR SHALL BE INSTALLED UNDER A
 SEPARATE PERMIT, HOWEVER PLEASE CLARIFY IF THE UNIT IS
 ALSO AN OIL INTERCEPTOR PER SEC. 1003.4- 1003.4.2.1 FBC
 P.
 PLEASE NOTE THAT OIL/SAND INTERCEPTORS SHALL BE LISTED
 OR COMPLY WITH SEC. 1003.4.2.1 GENERAL DESIGN
 REQUIREMENTS- OIL SEPARATORS SHALL HAVE A DEPTH OF NOT
 LESS THAN 2 FEET BELOW THE INVERT OF THE DISCHARGE
 DRAIN. THE OUTLET OPENING OF THE SEPARATOR SHALL HAVE
 NOT LESS THAN AN 18-INCH WATER SEAL. THE DETAIL SHOWS
 THE DEPTH IS TOO SHALLOW. PLEASE PROVIDE MORE
 INFORMATION ABOUT THE UNIT INCLUDING HOW IT WILL BE
 PROTECTED FROM VEHICULAR DAMAGE ABOVE. CLARIFY IF THE
 PIT ACCESS LID SHOWN IN THE DETAIL IS HEAVY DUTY
 TRAFFIC RATED AND IS EQUIPPED WITH AN ACCESS
 RESTRICTOR- SEC. 107.2.1 WPB.
 A) PROVIDE DIMENSIONED CONCRETE VAULT CONSTRUCTION AND
 BURIAL DETAILS- SEC. 107.2.1 WPB.
  
 11) P100, P101C & P503: AS NOTED IN COMMENT #1 THE
 GREASE AND SOLIDS INTERCEPTORS SHALL BE INSTALLED UNDER
 A SEPARATE PERMIT. A COMPLETE PLAN SUBMITTAL WILL BE
 REQUIRED AT THAT TIME WHICH SHALL INCLUDE THE FOLLOWING
 ITEMS:
 A) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF
 RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P.
 B) EQUIPMENT SCHEDULE INDICATING THE MAKES, MODELS AND
 CAPACITIES OF THE UNITS.
 C) SIZING CALCULATIONS IN ACCORDANCE WITH ASME
 A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3,
 OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7
 FOR GRAVITY TYPES.
 D) DIMENSIONED TANK BURIAL, ANCHORING, AND BACKFILLING
 DETAILS.
 E) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND
 SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL
 VENTS, AND SAMPLING PORTS.
 F) ACCESS LID DETAILS INDICATING THE LIDS WILL BE HEAVY
 DUTY TRAFFIC RATED AND WILL BE EQUIPPED WITH ACCESS
 RESTRICTORS. HEAVY DUTY LIDS ARE ALSO REQUIRED FOR
 CLEANOUTS, AND SAMPLING PORTS (IF INSTALLED).
  
 12) P100: PLEASE INDICATE THE SIZE OF THE MAIN STORM
 DRAIN PIPE EXISTING ON THE NORTH SIDE OF THE BUILDING-
 SEC. 107.2.1 WPB.
  
 13) P101A: THE MAIN SOIL, WASTE AND VENT STACK
 CONNECTIONS TO THE BUILDING DRAIN ARE SHOWN HOWEVER
 THERE ARE NO CONTINUOUS ISOMETRIC DRAWINGS SUBMITTED
 THAT CLEARLY SHOW STACK RUNS FROM THE FOUNDATION TO THE
 ROOF- SEC. 904.2, 904.3, & 904.4. TO HELP EXPEDITE THE
 REVIEW PLEASE PROVIDE THE ISOMETRICS WHICH SHALL ALSO
 SHOW THE LOCATIONS OF RELIEF VENTS WHERE REQUIRED PER
 SEC. 908.1 AND SEC. 107.3.5.3.1 WPB.
 A) PLEASE NOTE SEC. 913.2 PROHIBITS EITHER VERTICAL OR
 HORIZONTAL OFFSETS IN THE WASTE STACK SERVING THE
 WASHING MACHINES IN THE DWELLING UNITS BETWEEN THE
 LOWEST AND HIGHEST FIXTURE DRAIN CONNECTIONS. PLEASE
 PROVIDE THE ISO FOR THE STACK.
 B) PLEASE NOTE SEC. 913.3 REQUIRES A STACK VENT FOR THE
 WASTE STACK WHICH SHALL NOT BE LESS THAN THE SIZE OF
 THE WASTE STACK.
  
 14) P101A: PROVIDE A 3-INCH VENT AT (S20). THE PLAN
 SHOWS A 2-INCH- SEC. 904.4 FBC P.
  
 15) P101A: (S16) NOTE INDICATES A 4-INCH SANITARY BUT
 IT APPEARS TO BE AN 8-INCH. PLEASE SEE THE RISER ON
 SHEET P101C.
  
 16) P101B: PLEASE SHOW THE LOCATION OF THE 8-INCH RISER
 CALLED OUT IN NOTE (S21)- SEC. 107.2.1 WPB.
  
 17) P102A, P104A, P105, P106: THE 4-INCH VENT STACK
 CONTINUATION FROM THE 1ST FLOOR IS NOT SHOWN- SEC.
 904.4 FBC P. IT RE-APPEARS ON P107.
  
 18) P201B, P201C: TO HELP EXPEDITE THE REVIEW PLEASE
 PROVIDE COMPLETE WATER RISER DRAWINGS THAT SHOW THE
 UPFEEDING LINES FROM THE GROUND FLOOR AND THE
 DOWNFEEDING LINES FROM THE TOP FLOORS INCLUDING THE HW
 RECIRCULATION SYSTEM LOOP FROM THE HOT WATER HEATERS ON
 THE ROOF DOWN THROUGH THE BUILDING- SEC. 607.2 FBC P.
 AND SEC. 107.3.5.1.3 WPB. PLEASE NOTE THAT THE
 DEVELOPED LENGTH OF HOT WATER OR TEMPERED WATER PIPING
 FROM THE SOURCE OF HOT WATER TO FIXTURES REQUIRING HOT
 OR TEMPERED WATER SHALL NOT EXCEED 50 FT.
  
 19) P202B, P202C: THE HWR LINE DOES NOT APPEAR TO BE
 MAKING A CONNECTION BACK INTO THE HW LINE. PLEASE REFER
 TO SEC. C404.5.1 FBC ENERGY- THE HWR LINE IS THE HOT
 WATER SOURCE AND THE 1/2-INCH HW FIXTURE SUPPLY PIPES
 TO THE LAVATORIES ARE EXCEEDING THEIR MAXIMUM 2 FT.
 ALLOWABLE LENGTHS FROM THE HW SOURCE.
  
 20) P203A, P203B, P203C: THE HWR LINES DO NOT APPEAR TO
 BE MAKING COMPLETE LOOPS DOWN TO ALL THE LAVATORIES.
 PLEASE REFER TO SEC. C404.5.1 FBC ENERGY- THE HWR LINE
 IS THE HOT WATER SOURCE AND THE 1/2-INCH HW FIXTURE
 SUPPLY PIPES TO THE LAVATORIES ARE EXCEEDING THEIR
 MAXIMUM 2 FT. ALLOWABLE LENGTHS FROM THE HW SOURCE.
  
 21) P202B, P202C, P203A, P203B, P203C: INDICATE HOW
 TEMPERED WATER WILL BE PROVIDED TO THE PUBLIC
 LAVATORIES- SEC. 419.5 FBC P.
  
 22) P203B NOTE D15: PLEASE INDICATE THE MAKE AND MODEL
 OF THE ASSE 1013 RPZ TO PROTECT THE POTABLE WATER LINE
 TO THE IRRIGATION SYSTEM- SECS. 608.3 & 608.17.5 FBC P.
 TO HELP EXPEDITE THE REVIEW PLEASE ADD A BACKFLOW
 ASSEMBLY SCHEDULE FOR ALL DEVICES TO SHEET P503- SEC.
 107.2.1 WPB.
  
 23) P204A: PROVIDE A WATER RISER DRAWING FOR THE
 RESTROOMS- SEC. 107.3.5.1.3 WPB. PLEASE NOTE COMMENTS
 18 & 19 ABOVE PERTAINING TO THE HW SOURCE AND TEMPERED
 WATER REQUIREMENT.
  
 24) P204B: PLEASE MODIFY NOTE D23 TO INDICATE ASSE 1022
 APPROVED BACKFLOW PREVENTERS FOR CARBONATED BEVERAGE
 DISPENSERS, AND ASSE 1024 APPROVED BACKFLOW PREVENTERS
 FOR NON- CARBONATED BEVERAGES- SECS. 608.17.1.1 &
 608.17.1.2 FBC P.
  
 25) P210: PLEASE SHOW THE COOLING TOWER MAKEUP WATER
 LINE CONTINUATION TO THE TOWERS- SEC. 107.2.1 WPB.
  
 26) P202A- P209 DWELLING UNIT WATER SYSTEMS: PLEASE ADD
 NOTES TO INDICATE WATER HAMMER ON LINES SUPPLYING THE
 DISHWASHERS, WASHING MACHINES AND REFRIGERATOR ICE
 MAKERS- SEC. 604.9 FBC P.
  
 27) P202A- P209 DWELLING UNIT WATER SYSTEMS: PLEASE ADD
 NOTES INDICATING BACKFLOW PREVENTERS WILL BE INSTALLED
 ON LINES SUPPLYING THE REFRIGERATOR ICE MAKERS- SEC.
 608.3 FBC P. PLEASE SPECIFY THE MAKE AND MODEL OF THE
 DEVICES AND INCLUDE IN THE SCHEDULE ON P503.
 A) PLEASE INDICATE THE TYPE, SIZE AND R-VALUE OF HW AND
 HWR PIPE INSULATION PER TABLE C403.2.10 FBC EC. NOTES
 OR DETAILS SHALL BE PLACED ON THE DWELLING UNIT PLANS
 AND THE NON-RESIDENTIAL PLANS AND RISERS.
  
 28) P329: PLEASE INDICATE WHICH SHEET HAS THE SANITARY
 PIPING LAYOUT AND ISOMETRIC DRAWINGS FOR THESE UNITS C1
 & D1- SEC. 107.2.1 WPB.
  
 29) P330- P340: THESE TYPICAL UNIT PLANS DO NOT HAVE
 SANITARY PIPING LAYOUT AND ISOMETRIC DRAWINGS- SEC.
 107.2.1 WPB.
  
 30) P421: PLEASE PROVIDE THE AREA PLANS AND DRAINAGE
 CALCULATIONS THAT MATCH WITH THESE STORM WATER
 ISOMETRIC DRAWINGS- SEC. 107.2.1 WPB AND SEC. 1106.1
 FBC P.
  
 31) P402C: PLEASE PROVIDE A BRIDGE ROOF DRAINAGE PLAN
 AND DRAINAGE CALCULATIONS- SEC. 1106.1 FBC P.
  
 32) P421, P422, P423: TO HELP EXPEDITE THE REVIEW,
 PLEASE INDICATE THE ROOF DRAINAGE GPM'S AT THE ROOF
 DRAINS AND THE ACCUMULATIVE FLOW THROUGH THE BUILDING
 TO THE GROUND LEVEL MAIN STORM DRAINS- SEC. 1106.1,
 TABLES 1106.2 & 1106.3 FBC P.
  
 31) P501 DETAIL 10: PLEASE SHOW A DEDICATED SHUTOFF
 VALVE FOR THE COLD WATER FEED TO THE WATER HEATER- SEC.
 503.1 FBC P.
  
 32) LS104, P104C, P104D: SHEET LS104 SHOWS TWO BARS ON
 THE DECK, PRIVATE AND OUTDOOR DINING, GRILLS, AND A
 MAIN KITCHEN AND SHOW KITCHEN. THE PLUMBING PLANS DO
 NOT SHOW ANY PIPING AT THE LOCATION OF THE BAR ON THE
 NW SIDE OF THE DECK, AND DO NOT SHOW ANY MEANS OF
 SEPARATING AND DISPOSING OF GREASE FROM THE FIXTURE
 DRAINAGE FLOWS INTO THE SANITARY SYSTEM- SEC. 1003.3.1
 FBC P, AND SEC. 107.2.1 WPB. PLEASE REFER TO COMMENT
 #11 FOR GREASE INTERCEPTOR SUBMITTAL REQUIREMENTS AS
 APPLICABLE.
  
 33) P203A P503: THE LOCATIONS OF THE STEAM GENERATORS
 IN THE STEAM ROOMS, THE WATER SUPPLY TO THE UNITS, AND
 DRAINAGE DISPOSAL DETAILS ARE NOT SHOWN ON THE PLANS-
 SEC. 107.2.1 WPB.
  
 34) P502, P503: PLEASE LABEL THE TWO UNIDENTIFIED
 PIECES OF EQUIPMENT IN THE CORNER OF THE BOILER ROOM
 AND PROVIDE EQUIPMENT SCHEDULES- SEC. 107.2.1 WPB.
  
 35) P502: PLEASE INDICATE THE SIZE OF THE WATER SUPPLY
 PIPE LEAVING THE BOILER ROOM TO SUPPLY THE BUILDING,
 AND INCLUDE THE TEMPERATURE OF THE WATER- SEC. 607.1
 FBC P.
  
 36) P101B: AN OIL INTERCEPTOR MAY BE REQUIRED TO
 RECEIVE THE DRAINAGE FROM THE TRASH COMPACTOR FOR
 SEPARTION AND DISPOSAL. PLEASE SUBMIT MANUFACTURER'S
 SPECIFICATIONS FOR REVIEW- SEC. 1003.4 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
  

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2022-10-20 Cont ID  
Sent By ccole Date 2022-10-20 Time 15:23 Rev Time 0.00
Received By ccole Date 2022-10-20 Time 15:23 Sent To  
Notes
2022-10-20 15:24:35SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE GREASE
 INTERCEPTOR AND THE SAND INTERCEPTOR .

Review Stop P-IRRIGATE IRRIGATION REVIEW
Rev No 1 Status N Date 2022-10-20 Cont ID  
Sent By ccole Date 2022-10-20 Time 15:24 Rev Time 0.00
Received By ccole Date 2022-10-20 Time 15:24 Sent To  
Notes
2022-10-20 15:26:24A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR
 INSTALLATION OF THE IRRIGATION SYSTEM.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-10-13 Cont ID  
Sent By shill Date 2022-10-13 Time 09:09 Rev Time 0.00
Received By shill Date 2022-10-13 Time 09:09 Sent To  
Notes
2022-10-13 09:09:42REVIEWED UNDER FOUNDATION PERMIT
 INSPECTIONS ONLY
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-10-24 Cont ID  
Sent By rmcphers Date 2022-10-24 Time 13:50 Rev Time 0.00
Received By rmcphers Date 2022-10-24 Time 13:50 Sent To  
Notes
2022-10-24 13:50:58ROOFING SYSTEM TO BE DEFERRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 6 Status P Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 08:00 Rev Time 0.00
Received By rwbrown Date 2023-02-06 Time 08:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2023-02-06 Cont ID  
Sent By rwbrown Date 2023-02-06 Time 05:26 Rev Time 0.00
Received By rwbrown Date 2023-02-06 Time 05:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2023-02-03 Cont ID  
Sent By rmcphers Date 2023-02-03 Time 11:36 Rev Time 0.00
Received By rmcphers Date 2023-02-03 Time 11:36 Sent To  
Notes
2023-02-03 11:38:14PLEASE PROVIDE CORRECTIONS PER THE LAST REVIEW-- BY
 RYAN BROWN
  
  
 SIGNATURE REVIEW FAILED - THE "LC" PAGES SUBMITTED ARE
 NOT ELECTRONICALLY SEALED. PLEASE RESUBMIT THE LC PAGES
 WITH THE PROPER ELECTRONIC SEAL ON THE FILE. ALL OTHERS
 APPEAR TO BE OKAY.
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-12-27 Cont ID  
Sent By rwbrown Date 2022-12-27 Time 06:57 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
2022-12-27 06:59:21SIGNATURE REVIEW FAILED - THE "LC" PAGES SUBMITTED ARE
 NOT ELECTRONICALLY SEALED. PLEASE RESUBMIT THE LC PAGES
 WITH THE PROPER ELECTRONIC SEAL ON THE FILE. ALL OTHERS
 APPEAR TO BE OKAY.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-12-09 11:21:53PLUMBING (P) AND FUEL GAS (FG) PLANS PASSED.
2022-12-06 16:02:28DRAWINGS A106 AND LS103 NEED TO BE DIGITALLY SIGNED -
 RMCP
2022-12-01 11:39:14MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2022-10-24 14:26:25ELECTRICAL "LC" DRAWINGS ARE NOT SIGNED
2022-10-24 14:21:55ARCHITECTURAL AND STRUCTURAL DRAWINGS SIGNATURES OK
2022-10-21 08:39:26PLUMBING AND FUEL GAS DIGITAL SEALS AND SIGNATURES
 PASSED.
2022-10-17 13:35:10MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status P Date 2022-05-25 Cont ID  
Sent By shill Date 2022-05-25 Time 12:08 Rev Time 0.00
Received By shill Date 2022-05-25 Time 12:08 Sent To  
Notes
2022-05-25 12:08:28PASSED UNDER FOUNDATION PERMIT 20120019
  

Review Stop Z ZONING
Rev No 5 Status P Date 2023-02-03 Cont ID  
Sent By eschneid Date 2023-02-03 Time 15:48 Rev Time 0.75
Received By eschneid Date 2023-02-03 Time 12:07 Sent To  
Notes
2023-02-03 15:49:28PASSED W/PROVISOS
  
 1) ADDITIONAL PERMITS, WITH PLANS ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. EXTERIOR BICYCLE RACKS
 D. HARDSCAPE
 E. SITE/LANDSCAPE LIGHTING - THE PERMIT NEEDS TO
 INCLUDE A PHOTOMETRIC PLAN, AS WELL AS THE SPEC SHEETS
 FOR ALL OF THE LIGHTING TYPES.
 F. AWNINGS NOT INCLUDED WITH THIS PERMIT
 G. MODIFICATIONS TO THE GARAGE, INCLUDING THE EV
 CHARGERS.
 H. REQUIRED ROOFTOP SOLAR.
  
 2) PRIOR TO 1ST C.O.:
  
 A. PROVIDE VERIFICATION THAT NO LESS THAN 15% OF ALL
 CONSTRUCTION SERVICES
 ARE FROM SMALL BUSINESS ENTERPRISE (SBE) FIRMS LOCATED
 IN PALM BEACH COUNTY.
 B. VERIFICATION OF COMPLIANCE WITH THE WORKFORCE
 HOUSING REQUIREMENTS OF THE ROSEMARY SQUARE CENTER
 SUBAREA BY THE CITY'S HOUSING AND COMMUNITY DEVELOPMENT
 DEPARTMENT.
 C. VERIFICATION THAT THE BUILDING HAS BEEN CONSTRUCTED
 TO A LEED SILVER STANDARD OR EQUIVALENT RATING SYSTEM.
 D. VERIFICATION THAT THE CHARGING STATIONS AND THE RIDE
 SHARE SPACE HAVE BEEN INSTALLED WITHIN THE D GARAGE.
 E. WAYFINDING SIGNS MUST BE INSTALLED TO DIRECT
 PEDESTRIANS FROM THE D GARAGE TO THE RESIDENTIAL AND
 RETAIL ENTRANCES.
 F. PROVIDE VERIFICATION OF THE BICYCLE SHARE DISCOUNT
 MEMBERSHIP PROGRAM.
 G. A MINOR SUBDIVISION (REPLAT) APPLICATION MUST BE
 FILED WITH THE CITY'S PLANNING DIVISION AND BE APPROVED
 BY THE CITY COMMISSION.
  
 3) PRIOR TO THE APPROVAL OF THE FINAL INSPECTION (104)
 FOR THE GROUND FLOOR SPACE THAT FRONTS THE ACCESS
 EASEMENT AT THE NORTH END TO THE SITE, A PUBLIC ACCESS
 EASEMENT, IN A FORM ACCEPTABLE TO THE CITY ATTORNEY'S
 OFFICE, FOR THE PUBLIC SPACE TERMINATING THE PUBLIC
 OPEN SPACE - PASSAGE, MUST BE RECORDED.
  

Review Stop Z ZONING
Rev No 4 Status F Date 2023-01-18 Cont ID  
Sent By eschneid Date 2023-01-18 Time 09:57 Rev Time 4.00
Received By eschneid Date 2023-01-12 Time 13:55 Sent To  
Notes
2023-01-18 09:58:31FAILED
  
 1) PROVIDE THE ZONING CODE COMPLIANCE INFORMATION FOR
 THE PROJECT, INCLUDING THE SITE AND PROJECT DATA, THE
 FACADE ARTICULATION INFORMATION, THE OPEN SPACE
 DIAGRAMS AND CALCULATIONS, THE ACTIVE USE DIAGRAMS, THE
 FAR SPACE DIAGRAMS, THE GROSS BUILDING USE CALCULATIONS
 APPROVED AS PART OF THE MINOR PLANNED DEVELOPMENT
 AMENDMENT. NOTE: THE MINOR PLANNED DEVELOPMENT IS NOT
 YET APPROVED SINCE SOME OF THESE SHEETS HAVE
 CORRECTIONS THAT NEED TO BE MADE. DO NOT UPLOAD THESE
 SHEETS UNTIL THE MINOR PLANNED DEVELOPMENT AMENDMENT IS
 APPROVED. THESE SHEETS SHALL BE UPLOADED TO THE
 SUPPORTING DOCUMENTS FOLDER, NOT TO THE DRAWINGS
 FOLDER.
  
 2) ENLARGED EXTERIOR SKIN DETAIL 1 ON SHEET A507 MUST
 SHOW THE PODIUM SETBACK LINE SO THAT STAFF CAN VERIFY
 THAT THERE IS NO BUILDING ENCROACHMENT.
  
 3) ADDITIONAL PERMITS, WITH PLANS ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE
 B. IRRIGATION
 C. EXTERIOR BICYCLE RACKS
 D. HARDSCAPE
 E. SITE/LANDSCAPE LIGHTING - THE PERMIT NEEDS TO
 INCLUDE A PHOTOMETRIC PLAN, AS WELL AS THE SPEC SHEETS
 FOR ALL OF THE LIGHTING TYPES.
 F. AWNINGS NOT INCLUDED WITH THIS PERMIT
 G. MODIFICATIONS TO THE GARAGE, INCLUDING THE EV
 CHARGERS.
 H. REQUIRED ROOFTOP SOLAR.
 PARKING GARAGE IMPROVEMENTS. NOTE: THIS IS A SEPARATE
 PARCEL.
  
 4) PRIOR TO 1ST C.O.:
  
 A. PROVIDE VERIFICATION THAT NO LESS THAN 15% OF ALL
 CONSTRUCTION SERVICES
 ARE FROM SMALL BUSINESS ENTERPRISE (SBE) FIRMS LOCATED
 IN PALM BEACH COUNTY.
 B. VERIFICATION OF COMPLIANCE WITH THE WORKFORCE
 HOUSING REQUIREMENTS OF THE ROSEMARY SQUARE CENTER
 SUBAREA BY THE CITY'S HOUSING AND COMMUNITY DEVELOPMENT
 DEPARTMENT.
 C. VERIFICATION THAT THE BUILDING HAS BEEN CONSTRUCTED
 TO A LEED SILVER STANDARD OR EQUIVALENT RATING SYSTEM.
 D. VERIFICATION THAT THE CHARGING STATIONS AND THE RIDE
 SHARE SPACE HAVE BEEN INSTALLED WITHIN THE D GARAGE.
 E. WAYFINDING SIGNS MUST BE INSTALLED TO DIRECT
 PEDESTRIANS FROM THE D GARAGE TO THE RESIDENTIAL AND
 RETAIL ENTRANCES.
 F. PROVIDE VERIFICATION OF THE BICYCLE SHARE DISCOUNT
 MEMBERSHIP PROGRAM.
 G. A MINOR SUBDIVISION (REPLAT) APPLICATION MUST BE
 FILED WITH THE CITY'S PLANNING DIVISION AND BE APPROVED
 BY THE CITY COMMISSION.
  
 5) PRIOR TO THE APPROVAL OF THE FINAL INSPECTION (104)
 FOR THE GROUND FLOOR SPACE THAT FRONTS THE ACCESS
 EASEMENT AT THE NORTH END TO THE SITE, A PUBLIC ACCESS
 EASEMENT, IN A FORM ACCEPTABLE TO THE CITY ATTORNEY'S
 OFFICE, FOR THE PUBLIC SPACE TERMINATING THE PUBLIC
 OPEN SPACE - PASSAGE, MUST BE RECORDED.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446.
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-12-09 Cont ID  
Sent By eschneid Date 2022-12-09 Time 16:59 Rev Time 0.25
Received By eschneid Date 2022-12-07 Time 09:14 Sent To  
Notes
2022-12-07 14:59:03THE MINOR AMENDMENT FOR THIS REVISION DID NOT PASS.
 ZONING WILL NOT REVIEW THE PERMIT UNTIL THE MINOR
 AMENDMENT PASSES. FAIL RESULT ENTERED TO CLOSE THE
 REVIEW - THIS DOES NOT COUNT AS A ZONING REVIEW.
  
 NOTE: IF ANY PLANS CHANGE BASED ON ADDRESSING THE MINOR
 AMENDMENT COMMENTS, THE UPDATED PLANS SHOULD BE
 UPLOADED TO SAVE A REVIEW CYCLE.
  
 CONTACT ERIC SCHNEIDER @ 561-822-1446
 [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2022-10-18 Cont ID  
Sent By eschneid Date 2022-10-18 Time 17:48 Rev Time 0.25
Received By eschneid Date 2022-10-18 Time 17:45 Sent To  
Notes
2022-10-18 17:49:17FAILED
  
 THE PLANS HAVE CHANGED FROM THE PREVIOUS SUBMITTAL.
 ZONING WILL NOT REVIEW THE PERMIT UNTIL THE SUBMITTED
 MINOR PLANNED DEVELOPMENT AMENDMENT FOR THE CHANGES HAS
 BEEN REVIEWED AND APPROVED. YOU CAN TRACK THE MINOR
 AMENDMENT STATUS UNDER Z22080060.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-30 Cont ID  
Sent By escheide Date 2022-08-30 Time 16:00 Rev Time 0.25
Received By eschneid Date 2022-08-23 Time 14:10 Sent To  
Notes
2022-08-30 16:00:45FAILED
  
 THE PLANS HAVE CHANGED FROM THE PREVIOUS SUBMITTAL.
 ZONING WILL NOT REVIEW THE PERMIT UNTIL THE SUBMITTED
 MINOR PLANNED DEVELOPMENT AMENDMENT FOR THE CHANGES HAS
 BEEN REVIEWED AND APPROVED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]