| 2022-06-17 11:31:59 | FAILED |
| | |
| | 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT |
| | PERMIT - CITY RIGHTS-OF-WAY (21120271) MUST BE APPROVED |
| | PRIOR TO THIS PERMIT BEING APPROVED. THE PLANS ON THIS |
| | ELECTRIC PERMIT AND THE ONES ULTIMATELY RESUBMITTED |
| | WITH THE WCF ROW PERMIT NEED TO MATCH. |
| | |
| | 2) THE CITY CODE REQUIRES THAT WIRELESS FACILITIES IN |
| | THE RIGHT-OF-WAY MAY WITHIN RESIDENTIAL DISTRICTS MAY |
| | NOT BE PLACED DIRECTLY IN FRONT OF A RESIDENTIAL |
| | STRUCTURE. PLEASE SHIFT THE POLE TO THE NORTH SO THAT |
| | IT IS IN LINE WITH OR SLIGHTLY PAST THE FRONT FACADE OF |
| | THE HOUSES ON EITHER SIDE OF EITHER SIDE OF MANNING |
| | AVENUE. A MARK UP HAS BEEN SENT TO CHRISTINA WARR TO |
| | SHOW CLARIFY STAFF COMMENT. |
| | |
| | 3) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE |
| | THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE |
| | IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A |
| | SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY. |
| | |
| | 4) THE PLANS SHOW THE BORE PITS BEING DUG ADJACENT TO |
| | AN UNDERGROUND ELECTRIC LINE. IN ORDER TO VERIFY THAT |
| | THE INSTALLATION WILL NOT INTERFERE WITH THE EXISTING |
| | FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO |
| | OBJECTION FROM FPL REGARDING THE INSTALLATION. |
| | |
| | 5) THE EDGE OF THE BORE PIT EXCAVATION ON THE EAST SIDE |
| | OF MANNING AVENUE, WEST OF THE HANDHOLE BY THE POWER |
| | POLE MUST BE RELOCATED AT LEAST FIVE FEET FROM THE |
| | TRUNK OF THE EXISTING PALM TREE. THE CURRENT LOCATION |
| | WILL DAMAGE THE ROOT SYSTEM OF THE EXISTING PALM TREE |
| | AND IS NOT PERMITTED. |
| | |
| | 6) WHY IS THERE A LARGE X ACROSS THE BORING PROFILE |
| | DRAWINGS? THE UNDERGROUND ELECTRIC BORE ON THE BORING |
| | PROFILE MUST BE CLEARLY SHOWN AVOIDING THE UNDERGROUND |
| | INFRASTRUCTURE IN THE RIGHT-OF-WAY (EX: WATER AND |
| | SANITARY LINES). PROVIDED THE SEPARATION IS MET IN |
| | COMMENT #5, THE 36-INCH DEPTH WILL AVOID THE PALM TREE |
| | ROOT SYSTEMS THAT IT CROSSES. |
| | |
| | 7) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS. |
| | THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP |
| | 7042 TRAFFIC GREY A. THE SCOPE OF WORK ON SHEET T-1 |
| | NEEDS TO REFLECT THAT THIS IS A STEALTH POLE. |
| | |
| | CONTACT ERIC SCHNEIDER @ (561) 822-1446 |
| | [email protected] |
| | |
| | |
| | |