Plan Review Details - Permit 22050880
Plan Review Stops For Permit 22050880
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-05-28 Cont ID  
Sent By cpuell Date 2022-05-28 Time 11:16 Rev Time 0.00
Received By cpuell Date 2022-05-28 Time 11:16 Sent To  
Notes
2022-05-28 11:16:17ADDRESS APPROPRIATE FOR PROJECT.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2023-01-31 Cont ID  
Sent By fgiaquin Date 2023-01-31 Time 07:18 Rev Time 0.00
Received By fgiaquin Date 2023-01-30 Time 22:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-09 Cont ID  
Sent By fgiaquin Date 2022-06-09 Time 22:27 Rev Time 0.00
Received By fgiaquin Date 2022-06-09 Time 20:00 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2022-06-17 Cont ID  
Sent By eschneid Date 2022-06-17 Time 11:32 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2022-06-17 11:33:23ENGINEERING REVIEW PROVIDED UNDER WCF ROW PERMIT
 21120271

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-04-14 Cont ID  
Sent By aoliver Date 2023-04-14 Time 14:11 Rev Time 0.00
Received By aoliver Date 2023-01-18 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-22 Cont ID  
Sent By shill Date 2022-06-22 Time 09:19 Rev Time 0.00
Received By shill Date 2022-05-23 Time 06:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2023-04-14 Cont ID  
Sent By aoliver Date 2023-04-14 Time 14:11 Rev Time 0.00
Received By aoliver Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-22 Cont ID  
Sent By shill Date 2022-06-22 Time 09:14 Rev Time 0.00
Received By shill Date 2022-06-22 Time 09:14 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2023-04-14 Cont ID  
Sent By eschneid Date 2023-04-14 Time 14:06 Rev Time 0.25
Received By eschneid Date 2023-04-13 Time 13:42 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-17 Cont ID  
Sent By eschneid Date 2022-06-17 Time 11:31 Rev Time 0.25
Received By eschneid Date 2022-06-17 Time 10:25 Sent To  
Notes
2022-06-17 11:31:59FAILED
  
 1) THE SUBMITTED COMMUNICATION FACILITY PLACEMENT
 PERMIT - CITY RIGHTS-OF-WAY (21120271) MUST BE APPROVED
 PRIOR TO THIS PERMIT BEING APPROVED. THE PLANS ON THIS
 ELECTRIC PERMIT AND THE ONES ULTIMATELY RESUBMITTED
 WITH THE WCF ROW PERMIT NEED TO MATCH.
  
 2) THE CITY CODE REQUIRES THAT WIRELESS FACILITIES IN
 THE RIGHT-OF-WAY MAY WITHIN RESIDENTIAL DISTRICTS MAY
 NOT BE PLACED DIRECTLY IN FRONT OF A RESIDENTIAL
 STRUCTURE. PLEASE SHIFT THE POLE TO THE NORTH SO THAT
 IT IS IN LINE WITH OR SLIGHTLY PAST THE FRONT FACADE OF
 THE HOUSES ON EITHER SIDE OF EITHER SIDE OF MANNING
 AVENUE. A MARK UP HAS BEEN SENT TO CHRISTINA WARR TO
 SHOW CLARIFY STAFF COMMENT.
  
 3) THE HANDHOLE AND BORE PIT NOTES ON SHEET P-1 STATE
 THAT THE SIDEWALK WILL BE RESTORED; HOWEVER, THESE ARE
 IN LANDSCAPED AREAS AND NOT OVERLAPPING WITH A
 SIDEWALK. PLEASE UPDATE THE NOTATIONS ACCORDINGLY.
  
 4) THE PLANS SHOW THE BORE PITS BEING DUG ADJACENT TO
 AN UNDERGROUND ELECTRIC LINE. IN ORDER TO VERIFY THAT
 THE INSTALLATION WILL NOT INTERFERE WITH THE EXISTING
 FACILITIES, PROVIDE A PUBLIC UTILITY LETTER OF NO
 OBJECTION FROM FPL REGARDING THE INSTALLATION.
  
 5) THE EDGE OF THE BORE PIT EXCAVATION ON THE EAST SIDE
 OF MANNING AVENUE, WEST OF THE HANDHOLE BY THE POWER
 POLE MUST BE RELOCATED AT LEAST FIVE FEET FROM THE
 TRUNK OF THE EXISTING PALM TREE. THE CURRENT LOCATION
 WILL DAMAGE THE ROOT SYSTEM OF THE EXISTING PALM TREE
 AND IS NOT PERMITTED.
  
 6) WHY IS THERE A LARGE X ACROSS THE BORING PROFILE
 DRAWINGS? THE UNDERGROUND ELECTRIC BORE ON THE BORING
 PROFILE MUST BE CLEARLY SHOWN AVOIDING THE UNDERGROUND
 INFRASTRUCTURE IN THE RIGHT-OF-WAY (EX: WATER AND
 SANITARY LINES). PROVIDED THE SEPARATION IS MET IN
 COMMENT #5, THE 36-INCH DEPTH WILL AVOID THE PALM TREE
 ROOT SYSTEMS THAT IT CROSSES.
  
 7) THE POLE STYLE AND HEIGHT MEET CITY REQUIREMENTS.
 THE POLE COLOR AT THIS LOCATION SHALL BE RAL/RAYCAP
 7042 TRAFFIC GREY A. THE SCOPE OF WORK ON SHEET T-1
 NEEDS TO REFLECT THAT THIS IS A STEALTH POLE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
  
  