Plan Review Details - Permit 22050867
Plan Review Stops For Permit 22050867
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 09:26 Rev Time 0.00
Received By shill Date 2022-08-29 Time 09:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 14:47 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 14:47 Sent To  
Notes
2022-08-03 14:51:32GENERATOR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
  
 1. FBC R 301, SEE THE GENERATOR PAD ENGINEERING. IT
 STATES:
  
 UNIT WT = 518 LBS - PAD WT = 225 LBS
  
 THE GENERATORS SPECS LIST A GENERATOR WEIGHT OF 455
 LBS. IT DOES NOT APPEAR THAT THE GENERATOR MEETS THE
 WEIGHT REQUIREMENT FOR THIS PREFAB PAD.
  
 EITHER REVISE ENGINEERING TO CLARIFY OR SUBMIT NEW A
 NEW GENERATOR PAD DETAIL.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 09:42 Rev Time 0.00
Received By shill Date 2022-07-18 Time 09:35 Sent To  
Notes
2022-07-18 09:40:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, SEE THE GENERATOR PAD ENGINEERING. IT
 STATES:
  
 UNIT WT = 850 LBS PAD WT = 225 LBS
  
 THE GENERATORS SPECS LIST A GENERATOR WEIGHT OF 455
 LBS. IT DOES NOT APPEAR THAT THE GENERATOR MEETS THE
 WEIGHT REQUIREMENT FOR THIS PREFAB PAD.
  
 EITHER REVISE ENGINEERING TO CLARIFY OR SUBMIT NEW A
 NEW GENERATOR PAD DETAIL.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By fgiaquin Date 2022-06-07 Time 23:04 Rev Time 0.00
Received By fgiaquin Date 2022-06-07 Time 23:01 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 11:34 Rev Time 0.00
Received By ccole Date 2022-08-02 Time 13:00 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-07-07 Cont ID  
Sent By ccole Date 2022-07-07 Time 09:10 Rev Time 0.00
Received By ccole Date 2022-07-07 Time 08:05 Sent To  
Notes
2022-07-07 09:10:461ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT- 22050866
 7/7/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE GAS RISER IS INCOMPLETE BECAUSE IT DOES NOT
 INCLUDE THE EXISTING GAS PIPING AND APPLIANCES ALREADY
 CONNECTED TO THE METER AND APPROVED UNDER PERMITS-
 02101227 & 15110062. PLEASE REFER TO SECS. G2412.2 &
 G2412.3 FBC RES AND PROVIDE A COMPLETE GAS RISER THAT
 SHOWS ALL NEW AND EXISTING GAS PIPING AND APPLIANCES AT
 THE RESIDENCE. THE RISER SHALL SHOW:
 A) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS.
 B) TYPES AND SIZES OF PIPING.
 C) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER
 TO THE MOST REMOTE APPLIANCE OUTLET.
 D) BRANCH AND CUT PIPE LENGTH MEASUREMENTS.
 E) LOCATIONS OF REGULATORS, SHUTOFF VALVES, DRIP LEGS,
 AND PIPE UNIONS.
 F) OUTLET PRESSURES AT REGULATORS.
 G) LOCATIONS AND TYPES OF PIPE SLEEVES.
 H) PIPE SIZING TABLES.
  
 2) PLEASE CORRECT THE SURVEY DRAWING TO SHOW THE
 GENERATOR SHALL BE LOCATED A MINIMUM OF 10 FT. FROM THE
 AIR INTAKE OPENINGS INTO THE BUILDING INCLUDING
 OPERABLE WINDOWS AND DOORS- SEC. R303.5.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-09-08 Cont ID  
Sent By lmarchan Date 2022-09-08 Time 11:06 Rev Time 0.00
Received By lmarchan Date 2022-09-08 Time 08:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-02 Cont ID  
Sent By aoliver Date 2022-09-02 Time 08:24 Rev Time 0.00
Received By aoliver Date 2022-08-31 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-30 Cont ID  
Sent By aoliver Date 2022-08-30 Time 09:45 Rev Time 0.00
Received By aoliver Date 2022-08-17 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-08 Cont ID  
Sent By asangele Date 2022-08-08 Time 12:29 Rev Time 0.00
Received By asangele Date 2022-08-08 Time 12:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 09:43 Rev Time 0.00
Received By shill Date 2022-05-18 Time 06:09 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-08-03 Cont ID  
Sent By ccole Date 2022-08-03 Time 10:47 Rev Time 0.00
Received By ccole Date 2022-08-02 Time 13:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-07-07 Cont ID  
Sent By ccole Date 2022-07-07 Time 08:13 Rev Time 0.00
Received By ccole Date 2022-07-07 Time 08:05 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date 2022-09-08 Cont ID  
Sent By rgathrig Date 2022-09-08 Time 10:48 Rev Time 0.00
Received By rgathrig Date 2022-09-08 Time 10:48 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2022-09-01 Cont ID  
Sent By jbaker Date 2022-09-01 Time 11:31 Rev Time 0.00
Received By jbaker Date 2022-09-01 Time 11:31 Sent To  
Notes
2022-09-01 11:39:38PRIVATE PROVIDER REVIEW FOR INSPECTIONS ONLY FAILED
  
 THE CERTIFICATE OF INSURANCE PROVIDED DOES NOT HAVE THE
 STATUTORY LANGUAGE FOUND IN 553.791(4)(B) THAT
 DEMONSTRATES THAT PROFESSIONAL LIABILITY INSURANCE
 COVERAGE IS IN PLACE FOR THE PRIVATE PROVIDER?S FIRM,
 THE PRIVATE PROVIDER, AND ANY DULY AUTHORIZED
 REPRESENTATIVE IN THE AMOUNTS REQUIRED.
  
 TYPICALLY, THE INFORMATION IS FOUND IN THE DESCRIPTION
 OF OPERATIONS / LOCATIONS/VEHICLES BOX NEAR THE BOTTOM
 OF THE PAGE ON THE CERTIFICATE OF LIABILITY INSURANCE
 FORM THAT YOU SUBMIT. EACH SUBMITTAL HAS NOT HAD ANY
 INFORMATION IN THIS BOX.
  
  
 PLEASE PROVIDE
 JIM BAKER
 ASSISTANT BUILDING OFFICIAL
 561-805 6710
  
 IN THE DESCRIPTION OF OPERATIONS BOX ON THE CERTIFICATE
 OF LIABILITY INSURANCE FORM
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status F Date 2022-08-29 Cont ID  
Sent By jbaker Date 2022-08-29 Time 10:55 Rev Time 0.00
Received By jbaker Date 2022-08-29 Time 10:55 Sent To  
Notes
2022-08-29 11:17:53PRIVATE PROVIDER REVIEW FOR INSPECTIONS ONLY FAILED
  
 THE CERTIFICATE OF INSURANCE PROVIDED DOES NOT HAVE THE
 STATUTORY LANGUAGE FOUND IN 553.791(4)(B) THAT
 DEMONSTRATES THAT PROFESSIONAL LIABILITY INSURANCE
 COVERAGE IS IN PLACE FOR THE PRIVATE PROVIDER?S FIRM,
 THE PRIVATE PROVIDER, AND ANY DULY AUTHORIZED
 REPRESENTATIVE IN THE AMOUNTS REQUIRED. TYPICALLY, THIS
 LANGUAGE IS FOUND IN THE, DESCRIPTION OF OPERATIONS
 BOX.
  
 PLEASE PROVIDE
  
 JIM BAKER
 ASSISTANT BUILDING OFFICIAL
 561-805 6710
  
  
2022-08-29 11:13:53 
 JIM BAKER
 ASSISTANT BUILDING OFFICIAL
 561 805 6710
 [email protected]
  
  
  
  
 1. SAME COMMENT AS IN REVIEWS 1 AND 2 PROVIDE A
 CERTIFICATE OF INSURANCE DEMONSTRATING THAT
 PROFESSIONAL LIABILITY INSURANCE COVERAGE IS IN PLACE
 FOR THE PRIVATE PROVIDER?S FIRM, THE PRIVATE PROVIDER,
 AND ANY DULY AUTHORIZED REPRESENTATIVE IN THE AMOUNTS
 REQUIRED BY THIS SECTION

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-08-03 Cont ID  
Sent By dbattles Date 2022-08-03 Time 10:19 Rev Time 0.00
Received By dbattles Date 2022-08-03 Time 10:19 Sent To  
Notes
2022-08-03 10:20:27SEE PREVIOUS REVIEW ASKING FOR UPDATED COI.
 PLEASE PROVIDE UPDATED COI AS PREVIOUSLY REQUESTED.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-05-20 Cont ID  
Sent By rgathrig Date 2022-05-20 Time 13:45 Rev Time 0.00
Received By rgathrig Date   Time   Sent To  
Notes
2022-05-20 13:45:03PRIVATE PROVIDER INSPECTIONS ONLY REVIEW FAILED
  
 THE CERTIFICATE OF INSURANCE PROVIDED DOES NOT HAVE THE
 STATUTORY LANGUAGE FOUND IN 553.791(4)(B) THAT
 DEMONSTRATES THAT PROFESSIONAL LIABILITY INSURANCE
 COVERAGE IS IN PLACE FOR THE PRIVATE PROVIDER?S FIRM,
 THE PRIVATE PROVIDER, AND ANY DULY AUTHORIZED
 REPRESENTATIVE IN THE AMOUNTS REQUIRED. TYPICALLY, THIS
 LANGUAGE IS FOUND IN THE, DESCRIPTION OF OPERATIONS
 BOX.
  
 PLEASE PROVIDE
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561 805 6679
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-29 Cont ID  
Sent By shill Date 2022-08-29 Time 09:26 Rev Time 0.00
Received By shill Date 2022-08-29 Time 09:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-08-03 Cont ID  
Sent By rmcphers Date 2022-08-03 Time 14:52 Rev Time 0.00
Received By rmcphers Date 2022-08-03 Time 14:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-18 Cont ID  
Sent By shill Date 2022-07-18 Time 09:42 Rev Time 0.00
Received By shill Date 2022-07-18 Time 09:42 Sent To  
Notes
2022-07-18 09:42:54SEE BUILDING COMMENTS. DIGITAL SIGNATURE IS OK BUT WILL
 NEED TO BE VERIFIED NEXT REVIEW CYCLE IF A NEW DETAIL
 IS SUBMITTED.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-08 Cont ID  
Sent By asangele Date 2022-08-08 Time 12:29 Rev Time 0.00
Received By asangele Date 2022-08-08 Time 12:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-23 Cont ID  
Sent By asangele Date 2022-05-23 Time 09:37 Rev Time 0.00
Received By asangele Date 2022-05-23 Time 09:37 Sent To  
Notes
***NONE***