Plan Review Details - Permit 22050729
Plan Review Stops For Permit 22050729
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-12 Cont ID  
Sent By cthroop Date 2022-07-12 Time 15:07 Rev Time 0.00
Received By cthroop Date 2022-07-12 Time 13:46 Sent To  
Notes
2022-07-12 15:48:25PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: CHANGED PERMIT TYPE TO BLD-RES. (ACCESSORY
 STRUCTURE-RESIDENTIAL)
 REMOVED THE WORD "TEMPORARY" FROM WORK DESCRIPTION.
 TEMPORARY STRUCTURES ARE ONLY ALLOWED FOR 6 MONTHS OR
 LESS.
  
 1. CITY OF WPB CHPT. 1- VALUE
 109.3 BUILDING PERMIT VALUATIONS.
 1A. THE STATED VALUE APPEARS LOW FOR THE PROPOSED SCOPE
 OF WORK.
 1B. THE PERMIT VALUATION AND PERMIT FEE MUST BE
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. THIS INCLUDES ALL LABOR,
 MATERIALS AND RENTALS OF EQUIPMENT TO PERFORM THE SCOPE
 OF WORK.
 1C. YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY
 THE OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT
 RENTAL TO VERIFY VALUE.
 FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE
 BUILDING OFFICIAL
  
 2. PROVIDE PROJECT DATA / DESIGN PARAMETERS:
 PROJECT DATA: ACCESSORY STRUCTURE-RESIDENTIAL
 SITE PLAN/SURVEY
 DRAINAGE PLAN:
 SCOPE OF WORK:
  
 3.PROVIDE GOVERNING CODES:
 2020 FLORIDA BUILDING CODE 7TH EDITION
 2020 FBC RESIDENTIAL BUILDING CODE
 MECHANICAL/ELECTRICAL/PLUMBING/FUEL GAS
 2017 NEC
  
 4.PROVIDE DESIGN PARAMETERS:
 SITE SPECIFIC DESIGN WIND LOADS PER FBC RES CHPT 3
 AND/OR ASCE 7-16
 (VULT 170MPH 3 SEC GUST / VASD 132MPH)
 EXPOSURE CLASSIFICATION ?__________
 RISK CATEGORY ? _______
 STRUCTURE - ENCLOSED / OPEN ?
 MRH ?
 BUILDING CLASSIFICATION ? VB
 OCCUPANCY CLASSIFICATION ? R3 SFR
  
 4.PROVIDE DESIGN PRESSURES FOR WINOWS/DOORS/ROOFS
 FBC 107.3.5.3 PROVIDE WIND DESIGN LOADS/DESIGN
 PRESSURES PURSUANT TO FBC-R301.2.
  
 R301.2.1 WIND DESIGN CRITERIA.
 BUILDINGS AND PORTIONS THEREOF SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH THE WIND PROVISIONS OF THIS CODE USING
 THE BASIC WIND SPEED IN TABLE R301.2(1) AS DETERMINED
 FROM FIGURE R301.2(4).
 WINDOWS AND DOORS ZONE 4 INT. / ZONE 5 CORNER
 (POSITVE/NEGATIVE)
 ROOF ZONE 1 (FIELD), ZONE 2 (EDGE), ZONE 3 (CORNERS)
  
 5.PROVIDE BATHROOM EXHAUST
 R303.3BATHROOMS.
 BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR
 ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN
 WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2),
 ONE-HALF OF WHICH MUST BE OPENABLE.
 EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE
 ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE
 PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE
 DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST
 AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE
 OUTDOORS.
  
 6.PROVIDE A COPY OF THE CURRENT FLORIDA PRODUCT
 APPROVAL, APPROVED UNDER THE 2020 FBC, FOR THE PROPOSED
 EXTERIOR DOOR.
 ( IF A WINDOW IS USED FOR BATHROOM VENTILATION, PROVIDE
 A PRODUCT APPROVAL FOR THAT WINDOW).
 FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS,
 EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 R301.2.1.2 PROTECTION OF OPENINGS.
 NOTE: STRUCTURES THAT ARE NOT DESIGNED FOR HUMAN
 HABITATION AND THAT HAVE A FLOOR AREA OF 720 SQUARE
 FEET (67 M2) OR LESS ARE NOT REQUIRED TO COMPLY WITH
 THE MANDATORY WIND-BORNE DEBRIS IMPACT STANDARD OF THIS
 CODE.
  
 7. PROVIDE THE FOLLOWING BUILDING PLANS
  
 7A) PROVIDE A FOUNDATION PLAN FOOTINGS/SLAB ON
 GRADE/REINFORCING/TIE DOWNS.
 7B) PROVIDE REQUIRED DIMENSIONS.
 7C) PROVIDE A FLOOR PLAN WITH FLOOR TO FOUNDATION
 CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 7D) PROVIDE A WALL PLAN (SECTION VIEW) WITH WALL TO
 FLOOR CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 7E) PROVIDE A ROOF FRAMING PLAN WITH ROOF TO WALL
 CONNECTION DETAIL, INCLUDE CONNECTOR TYPE AND
 FASTENERS.
 7F) PROVIDE A WINDOW AND/OR DOOR SCHEDULE WITH ROUGH
 OPENINGS AND DESIGN WIND LOADS. (COORDINATE SCHEDULE
 WITH OPENINGS ON FLOOR PLAN).
 7G) PROVIDE PRODUCT APPROVALS FOR ALL ROOFING, WINDOWS,
 DOORS, AND TIE DOWNS. >720 SQ. FT. SEE R301.2.1.2
 7H) ELECTRICAL PROVIDE AN ELECTRICAL PLAN. ELECTRIC
 SUB-PERMIT REQUIRED.
 7I) MECHANICAL PROVIDE A MECHANICAL PLAN. MECHANICAL
 SUB-PERMIT REQUIRED.
 7J) PLUMBING PROVIDE A PLUMBING PLAN. PLUMBING
 SUB-PERMIT REQUIRED.
 7K) ROOFING PROVIDE A ROOF PLAN. ROOFING SUB-PERMIT
 REQUIRED.
  
 NOTICE: A SEPERATE ROOFING PERMIT IS REQUIRED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2022-07-14 Cont ID  
Sent By jleahy Date 2022-07-14 Time 07:49 Rev Time 0.00
Received By jleahy Date 2022-07-14 Time 07:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-04 Cont ID  
Sent By ajones Date 2022-08-04 Time 16:43 Rev Time 0.00
Received By ajones Date 2022-07-11 Time 06:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-10 Cont ID  
Sent By aoliver Date 2022-06-10 Time 10:57 Rev Time 0.00
Received By aoliver Date 2022-05-25 Time 06:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-07-12 Cont ID  
Sent By ccole Date 2022-07-12 Time 17:19 Rev Time 0.00
Received By ccole Date 2022-07-12 Time 08:07 Sent To  
Notes
2022-07-12 17:19:562ND REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 22050729
 7/12/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS 01 & 02: THE BUILDING PLAN REVIEWER HAS
 DETERMINED THE TOILET ROOM STRUCTURE IS NOT A TEMPORARY
 INSTALLATION AND HAS CONVERTED THE PERMIT TYPE TO BLD
 RES. THE PLUMBING CANNOT BE APPROVED AT THIS TIME UNTIL
 NEW PLANS DESIGNED IN ACCORDANCE WITH THE FBC RES 2020
 CODE ARE SUBMITTED ADDRESSING ALL OF THE BUILDING PLAN
 REVIEW COMMENTS- SEC. 107.2.1 WPB.
  
 2) SHEET 02: PLEASE NOTE THE CURRENT PLANS DO NOT SHOW
 A FLOOR FOR THE STRUCTURE OR ANY TYPE OF MOUNTING
 SURFACE TO SECURELY ANCHOR THE TOILET DRAIN FLANGE AND
 THE TOILET- SEC. P2705.1 FBC RES. A) REFER TO SEC.
 P3005.1.4 AND NOTE WATER CLOSET CONNECTION BETWEEN
 FLANGE AND PIPE.
 ONE-QUARTER BENDS 3 INCHES IN DIAMETER SHALL BE
 ACCEPTABLE FOR WATER CLOSET OR SIMILAR CONNECTIONS,
 PROVIDED THAT A 4-INCH BY 3-INCH FLANGE IS INSTALLED TO
 RECEIVE THE CLOSET FIXTURE HORN. ALTERNATELY, A 4-INCH
 BY 3-INCH ELBOW SHALL BE ACCEPTABLE WITH A 4-INCH
 FLANGE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By rwbrown Date 2022-05-26 Time 14:13 Rev Time 0.00
Received By rwbrown Date 2022-05-26 Time 13:59 Sent To  
Notes
2022-05-26 14:12:551ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.3 - PLEASE DETAIL THE
 BACKFLOW PREVENTION AND REFERENCE THE PERMIT NUMBER FOR
 THE BACKFLOW.
  
 2. 2017 WPB AMENDS 107.3.5.3 - PLEASE DETAIL THE DRAIN
 CONNECTIONS AND SHOW HOW IT WILL BE VENTED. IF A
 TRAPPED FIXTURE IS CONNECTED TO A SEWER SYSTEM, IT WILL
 NEED TO BE VENTED ACCORDING TO CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status P Date 2022-06-10 Cont ID  
Sent By aoliver Date 2022-06-10 Time 10:57 Rev Time 0.00
Received By aoliver Date 2022-06-10 Time 10:57 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2022-07-12 Cont ID  
Sent By cthroop Date 2022-07-12 Time 15:52 Rev Time 0.00
Received By cthroop Date 2022-07-12 Time 15:52 Sent To  
Notes
2022-07-12 15:52:57A SEPERATE ROOFING PERMIT IS REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-06 Cont ID  
Sent By cthroop Date 2022-06-06 Time 14:59 Rev Time 0.00
Received By cthroop Date 2022-06-06 Time 12:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-08-04 Cont ID  
Sent By ajones Date 2022-08-04 Time 16:42 Rev Time 0.00
Received By ajones Date 2022-08-04 Time 16:42 Sent To  
Notes
2022-08-04 16:43:368/4/22- FAILED. ALL ACCESSORY STRUCTURES MUST BE A
 MINIMUM OF 5 FEET FROM THE REAR AND SIDE PROPERTY
 LINES.
  
 ANGELLA VANN, AICP
 [email protected]
 5618221441

Review Stop Z ZONING
Rev No 1 Status F Date 2022-06-02 Cont ID  
Sent By avann Date 2022-06-02 Time 16:48 Rev Time 0.00
Received By ajones Date 2022-06-02 Time 16:48 Sent To  
Notes
2022-06-02 16:50:086/2/22- FAILED. PLEASE PROVIDE SETBACK FOR PROPOSED
 STRUCTURE FROM SIDE PROPERTY LINE.
  
 ANGELLA VANN
 [email protected]
 561-822-1441