| 2022-05-17 11:58:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE IS AN INDICATION OF THE INSTALLATION OF ACCESS |
| | CONTROL HOWEVER THERE IS NO PLAN SHEET, FLOOR PLAN NOR |
| | DOOR LOCATION. |
| | |
| | PER NFPA 1 |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | THE ALTERATION OF THE MEANS OF EGRESS OR FIRE |
| | PROTECTION SYSTEMS OF ANY EXISTING BUILDING. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN, |
| | LOCATION OF DEVICES AND DOOR LOCATIONS. |
| | |
| | |
| | 1A) ACCESS CONTROL WITHI A MEANS OF EGRESS SHALL COMPLY |
| | WITH THE APPLICABLE REQUIREMENTS OF NFPA 101, CH 7, |
| | MEANS OF EGRESS. |
| | |
| | PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF |
| | ACKNOWLDGMENT. |
| | |
| | |
| | |
| | 1B) THERE ARE NO INDICATIONS OF AN ELECTRICAL POWER |
| | SUPPLY AND WIRE SIZES. |
| | |
| | 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER |
| | CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE |
| | COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS. |
| | |
| | PLEASE PROVIDE THE ELECTRICAL POWER PLAN AND APPLICABLE |
| | EQUIPMENT AND DIAGRAMS IN COMPLIANCE WITH NPFA CODES |
| | AND MANUFACTURES SPECIFIACATIONS. |
| | |
| | |
| | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |