Plan Review Details - Permit 22050687
Plan Review Stops For Permit 22050687
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-06 Cont ID  
Sent By mpeterso Date 2022-06-06 Time 13:18 Rev Time 0.00
Received By mpeterso Date 2022-06-06 Time 13:18 Sent To  
Notes
2022-06-06 13:20:51ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE A FLOOR PLAN INICATING ALL WIRING AND
 DEVICES, RISER DIAGRAM IF APPLICABLE, AND WIRING
 DIAGRAMS. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-05-17 Cont ID  
Sent By pleduc Date 2022-05-17 Time   Rev Time 0.00
Received By pleduc Date 2022-05-17 Time 11:53 Sent To  
Notes
2022-05-17 11:58:34THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF THE INSTALLATION OF ACCESS
 CONTROL HOWEVER THERE IS NO PLAN SHEET, FLOOR PLAN NOR
 DOOR LOCATION.
  
 PER NFPA 1
 1.7.12 PLANS AND SPECIFICATIONS.
  
 1.7.12.6 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO
 THE ALTERATION OF THE MEANS OF EGRESS OR FIRE
 PROTECTION SYSTEMS OF ANY EXISTING BUILDING.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN,
 LOCATION OF DEVICES AND DOOR LOCATIONS.
  
  
 1A) ACCESS CONTROL WITHI A MEANS OF EGRESS SHALL COMPLY
 WITH THE APPLICABLE REQUIREMENTS OF NFPA 101, CH 7,
 MEANS OF EGRESS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLDGMENT.
  
  
  
 1B) THERE ARE NO INDICATIONS OF AN ELECTRICAL POWER
 SUPPLY AND WIRE SIZES.
  
 1.7.12.7 PLANS SHALL BE SUBMITTED TO THE AHJ FOR OTHER
 CONDITIONS AS DEEMED NECESSARY BY THE AHJ TO DETERMINE
 COMPLIANCE WITH THE APPLICABLE CODES AND STANDARDS.
  
 PLEASE PROVIDE THE ELECTRICAL POWER PLAN AND APPLICABLE
 EQUIPMENT AND DIAGRAMS IN COMPLIANCE WITH NPFA CODES
 AND MANUFACTURES SPECIFIACATIONS.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-06 Cont ID  
Sent By mpeterso Date 2022-06-06 Time 13:23 Rev Time 0.00
Received By mpeterso Date 2022-05-16 Time 06:52 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-06 Cont ID  
Sent By mpeterso Date 2022-06-06 Time 13:22 Rev Time 0.00
Received By mpeterso Date 2022-06-06 Time 13:22 Sent To  
Notes
2022-06-06 13:22:54NO DRAWINGS PROVIDED AS REQUIRED