Plan Review Details - Permit 22050669
Plan Review Stops For Permit 22050669
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-07-27 Cont ID  
Sent By jwitmer Date 2022-07-27 Time 13:27 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-07-26 Cont ID  
Sent By jwitmer Date 2022-07-26 Time 11:17 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-07-26 11:17:49WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22050669
 ADD: 616 CLEARWATER PARK RD # 1106
 CONT: GENESIS DEVELOPMENT GROUP
 TEL: 786-282-4554
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. JULY 26TH/2022
 ACTION: DENIED
  
 1)3RD REVIEW. THE PERMIT APPLICATION STATES THIS
 FLOORING PERMIT IS A AFTER THE FACT OR FLOORING AND
 SOUND PROOFING WERE COMPLETED BEFORE A PERMIT WAS
 APPLIED FOR. IT DOES NOT HELP TO SUBMIT A PRODUCT THAT
 WAS NOT INSTALLED, THAT DOES NOT MAKE CODE COMPLIANCE.
 THIS REVIEW THE PERMIT APPLICATION STATES AFTER THE
 FACT LAMINATE FLOORING (COMPOSITE WOOD, ENGINEERED WOOD
 FLOORING) OVER SOUNDPROOFING. THIS REVIEW PROFLEX SUPER
 SIM 90 TEST REPORTS WERE SUBMITTED FOR THE IIC & STC
 RATINGS FOR USE WITH TILE FLOORS NOTLAMINATE FLOORING.
  
 2ND REVIEW CYCLE. THERE ARE 2 OPTIONS, ONE GET ON SITE
 TESTING FOR THE IIC AND STC RATINGS, THE REQUIRED
 RATINGS FOR ONSITE TESTING ARE ONLY 45 IIC & STC BUT
 VERY EXPENSIVE, ALSO A RECOGNIZED TESTING FACILITY. THE
 OTHER OPTION IS TO REMOVE THE FLOORING AND UNDERLAYMENT
 AND APPLY WITH PRODUCT FOR A FLOOR TYPE (LUXURY VINYL
 TILE FLOORING) LVT/ LVP TO BE INSTALLED AND SOUND
 PROOFING THAT WAS TESTED FOR THAT FLOOR FINISH.
  
 1ST ROUND COMMENTS. SOUND PROOFING SPECS SUBMITTED IS
 FOR PROFLEX 90 MSC FLOOR UNDERLAYMENT. PLEASE BE
 ADVISED TO DATE WE HAVE NOT SEEN TEST REPORTS FOR
 PROFLEX 90 MSC FLOOR UNDERLAYMENT FOR USE ON 6 INCH
 CONCRETE SLAB NO DROPPED CEILINGS FOR USE WITH LAMINATE
 (WOOD) FLOORING.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) 3RD REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) 3RD REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 3RD REQUEST. FBC-B 804.4.4.1 SOFT FLOOR FINISHES
 (LVT/ LPT, OR LAMINATED OR ENGINEERED WOOD FLOORING)
 WITHIN TENANT SPACE. INTERIOR FLOOR COVERING MATERIALS
 SHALL COMPLY WITH THE REQUIREMENTS OF THE COC FF-1
 ?PILL TEST? (CPSC 16 CFR PART 1630) OR WITH ASTM D2859.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED. BEST WAY OF COMMUNICATION IS
 BY E-MAIL, YOU HAVE A WRITTEN RECORD..
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 09:40 Rev Time 0.00
Received By jwitmer Date 2022-06-28 Time 09:37 Sent To  
Notes
2022-06-28 09:40:25WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22050669
 ADD: 616 CLEARWATER PARK RD # 1106
 CONT: GENESIS DEVELOPMENT GROUP
 TEL: 786-282-4554
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 28TH/2022
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION STATES THIS FLOORING PERMIT
 IS A AFTER THE FACT OR FLOORING AND SOUND PROOFING WERE
 COMPLETED BEFORE A PERMIT WAS APPLIED FOR. IT DOES NOT
 HELP TO SUBMIT A PRODUCT THAT WAS NOT INSTALLED, THAT
 DOES NOT MAKE CODE COMPLIANCE. THERE ARE 2 OPTIONS, ONE
 GET ON SITE TESTING FOR THE IIC AND STC RATINGS, THE
 REQUIRED RATINGS FOR ONSITE TESTING ARE ONLY 45 IIC &
 STC BUT VERY EXPENSIVE, ALSO A RECOGNIZED TESTING
 FACILITY. THE OTHER OPTION IS TO REMOVE THE FLOORING
 AND UNDERLAYMENT AND APPLY WITH PRODUCT FOR A FLOOR
 TYPE (LUXURY VINYL TILE FLOORING) LVT/ LVP TO BE
 INSTALLED AND SOUND PROOFING THAT WAS TESTED FOR THAT
 FLOOR FINISH.
 1ST ROUND COMMENTS. SOUND PROOFING SPECS SUBMITTED IS
 FOR PROFLEX 90 MSC FLOOR UNDERLAYMENT. PLEASE BE
 ADVISED TO DATE WE HAVE NOT SEEN TEST REPORTS FOR
 PROFLEX 90 MSC FLOOR UNDERLAYMENT FOR USE ON 6 INCH
 CONCRETE SLAB NO DROPPED CEILINGS FOR USE WITH LAMINATE
 (WOOD) FLOORING.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT, OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED. BEST WAY OF COMMUNICATION IS
 BY E-MAIL, YOU HAVE A WRITTEN RECORD..
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-01 Cont ID  
Sent By jwitmer Date 2022-06-01 Time 11:19 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2022-06-01 11:19:19WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22050669
 ADD: 616 CLEARWATER PARK RD # 1106
 CONT: GENESIS DEVELOPMENT GROUP
 TEL: 786-282-4554
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. JUNE 01/2022
 ACTION: DENIED
  
 1) SOUND PROOFING SPECS SUBMITTED IS FOR PROFLEX 90 MSC
 FLOOR UNDERLAYMENT. PLEASE BE ADVISED TO DATE WE HAVE
 NOT SEEN TEST REPORTS FOR PROFLEX 90 MSC FLOOR
 UNDERLAYMENT FOR USE ON 6 INCH CONCRETE SLAB NO DROPPED
 CEILINGS FOR USE WITH LAMINATE (WOOD) FLOORING.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT, OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ?PILL TEST? (CPSC
 16 CFR PART 1630) OR WITH ASTM D2859.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-27 Cont ID  
Sent By cwalker Date 2022-07-27 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-31 Cont ID  
Sent By cwalker Date 2022-05-31 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-07-27 Cont ID  
Sent By jwitmer Date 2022-07-27 Time 13:27 Rev Time 0.00
Received By jwitmer Date 2022-07-26 Time 16:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-07-26 Time   Rev Time 0.00
Received By lmarchan Date 2022-07-18 Time 07:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-28 Cont ID  
Sent By jwitmer Date 2022-06-28 Time 09:40 Rev Time 0.00
Received By jwitmer Date 2022-06-02 Time 06:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-01 Cont ID  
Sent By jwitmer Date 2022-06-01 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2022-05-27 Time 08:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-01 Cont ID  
Sent By jwitmer Date 2022-06-01 Time 11:19 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***