Plan Review Details - Permit 22050595
Plan Review Stops For Permit 22050595
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 09:30 Rev Time 0.00
Received By shill Date 2022-08-06 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 16:21 Rev Time 0.00
Received By shill Date 2022-07-23 Time 16:21 Sent To  
Notes
2022-07-23 16:23:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B 1609, PROVIDE A STRUCTURAL DETAIL FOR
 GENERATOR.
  
 2. FBC 107, PROVIDE A SITE PLAN SHOWING PROPOSED
 LOCATION.
  
 3. FBC 107, FUEL TANK REQUIRES A SEPARATE PERMIT. THIS
 PERMIT WILL BE ISSUED WITH PROVISO.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 13:39 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 11:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-11 Cont ID  
Sent By   Date 2022-08-11 Time   Rev Time 0.00
Received By   Date 2022-08-11 Time   Sent To  
Notes
2022-08-11 13:56:52THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE
 DEPARTMENT, WITH THE FOLLOWING COMMENTS:
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 FUEL TANK INSTALLATION MUST BE ON SEPERATE PERMIT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-06-13 Cont ID  
Sent By cwalker Date 2022-06-13 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-05-20 Cont ID  
Sent By   Date 2022-05-20 Time   Rev Time 0.00
Received By bdolan Date 2022-05-20 Time 10:56 Sent To  
Notes
2022-05-20 11:07:10PLAN IS FOR INSTALLATION OF TWO ADDITIONAL DIESEL
 GENERATORS FOR THE SITE. NOT INDICATED IS THE FUEL
 STOPRAGE SYSTEM FOR THE NEW UNITS.
  
 PLEASE INDICATE LOACTION OF FUEL STORAGE FOR NEW
 GENERATORS ON SITE IF EXISTING, OR LOCATION OF NEW FUEL
 STORAGE. IF NEW FUEL STORAGE IS BEING ADDED, PLEASE
 ENSURE FUEL TANKS MEET NFPA STANDARDS AS NOTED:
  
 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE
 LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-08-12 Cont ID  
Sent By lmarchan Date 2022-08-12 Time 16:43 Rev Time 0.00
Received By lmarchan Date 2022-08-03 Time 14:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-23 Cont ID  
Sent By shill Date 2022-07-23 Time 16:23 Rev Time 0.00
Received By shill Date 2022-06-25 Time 07:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 08:51 Rev Time 0.00
Received By mpeterso Date 2022-06-08 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 13:39 Rev Time 0.00
Received By mpeterso Date 2022-05-16 Time 07:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-06 Cont ID  
Sent By shill Date 2022-08-06 Time 09:30 Rev Time 0.00
Received By shill Date 2022-08-06 Time 09:30 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-21 Cont ID  
Sent By mpeterso Date 2022-06-21 Time 08:51 Rev Time 0.00
Received By mpeterso Date 2022-06-21 Time 08:51 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-07 Cont ID  
Sent By mpeterso Date 2022-06-07 Time 13:39 Rev Time 0.00
Received By mpeterso Date 2022-06-07 Time 13:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 2022-08-10 Cont ID  
Sent By vbroglia Date 2022-08-10 Time 14:57 Rev Time 0.00
Received By vbroglia Date 2022-08-10 Time 14:57 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2022-07-14 Cont ID  
Sent By vbroglia Date 2022-07-14 Time 12:22 Rev Time 0.00
Received By vbroglia Date 2022-07-14 Time 12:22 Sent To  
Notes
2022-07-14 12:30:287/14/2022
  
 NEED TO SHOW SETBACKS OF GENERATORS PROPOSED LOCATION
  
 REVIEW 1ST COMMENT TO REVIEW ZONING CODE
  
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 2022-06-16 Time   Rev Time 0.00
Received By vbroglia Date 2022-06-16 Time 14:38 Sent To  
Notes
2022-06-16 14:38:416/16/2022 FAILED
  
 PLEASE SEE PREVIOUS COMMENTS

Review Stop Z ZONING
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By vbroglia Date 2022-05-26 Time 16:44 Rev Time 0.00
Received By vbroglia Date 2022-05-26 Time 16:44 Sent To  
Notes
2022-05-26 16:54:445/26/2022 FAILED
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS
 MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED
 SIDE SETBACK
  
  
 PLEASE PROVIDE A SITE PLAN THAT DEMONSTRATES THE
 PROPERTY LINES, LOCATION OF PROJECT AND DISTANCES FORM
 BOUNDARY LINES
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  