| Plan Review Stops For Permit 22050595 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-08-06 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-06 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-23 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-07-23 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2022-07-23 16:23:34 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC B 1609, PROVIDE A STRUCTURAL DETAIL FOR | | | GENERATOR. | | | | | | 2. FBC 107, PROVIDE A SITE PLAN SHOWING PROPOSED | | | LOCATION. | | | | | | 3. FBC 107, FUEL TANK REQUIRES A SEPARATE PERMIT. THIS | | | PERMIT WILL BE ISSUED WITH PROVISO. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-06-07 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-07 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-07 |
Time |
11:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2022-08-11 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-08-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2022-08-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-08-11 13:56:52 | THIS PLAN WAS REVIEWED AND APPROVED BY THE FIRE | | | DEPARTMENT, WITH THE FOLLOWING COMMENTS: | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | FUEL TANK INSTALLATION MUST BE ON SEPERATE PERMIT. | | | | | | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-06-13 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-06-13 |
Time |
|
Rev Time |
0.00 |
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-05-20 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-05-20 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2022-05-20 |
Time |
10:56 |
Sent To |
|
|
| Notes |
| 2022-05-20 11:07:10 | PLAN IS FOR INSTALLATION OF TWO ADDITIONAL DIESEL | | | GENERATORS FOR THE SITE. NOT INDICATED IS THE FUEL | | | STOPRAGE SYSTEM FOR THE NEW UNITS. | | | | | | PLEASE INDICATE LOACTION OF FUEL STORAGE FOR NEW | | | GENERATORS ON SITE IF EXISTING, OR LOCATION OF NEW FUEL | | | STORAGE. IF NEW FUEL STORAGE IS BEING ADDED, PLEASE | | | ENSURE FUEL TANKS MEET NFPA STANDARDS AS NOTED: | | | | | | 7.9.1.1 ALL FUEL TANKS AND SYSTEMS SHALL BE INSTALLED | | | AND MAINTAINED | | | IN ACCORDANCE WITH NFPA 30, FLAMMABLE AND COMBUSTIBLE | | | LIQUIDS CODE; NFPA 37, STANDARD FOR THE INSTALLATION | | | AND USE OF | | | STATIONARY COMBUSTION ENGINES AND GAS TURBINES | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-08-12 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-08-12 |
Time |
16:43 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-08-03 |
Time |
14:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-07-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-07-23 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-06-25 |
Time |
07:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-21 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-08 |
Time |
12:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-06-07 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-07 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-16 |
Time |
07:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-08-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-08-06 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-06 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-21 |
Time |
08:51 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-21 |
Time |
08:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-06-07 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-07 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-07 |
Time |
13:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2022-08-10 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-08-10 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-08-10 |
Time |
14:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2022-07-14 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-07-14 |
Time |
12:22 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-07-14 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2022-07-14 12:30:28 | 7/14/2022 | | | | | | NEED TO SHOW SETBACKS OF GENERATORS PROPOSED LOCATION | | | | | | REVIEW 1ST COMMENT TO REVIEW ZONING CODE | | | | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-06-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-06-16 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2022-06-16 14:38:41 | 6/16/2022 FAILED | | | | | | PLEASE SEE PREVIOUS COMMENTS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-05-26 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-05-26 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-05-26 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2022-05-26 16:54:44 | 5/26/2022 FAILED | | | | | | PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR: | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | | INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS | | | MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED | | | SIDE SETBACK | | | | | | | | | PLEASE PROVIDE A SITE PLAN THAT DEMONSTRATES THE | | | PROPERTY LINES, LOCATION OF PROJECT AND DISTANCES FORM | | | BOUNDARY LINES | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|