| | 1ST REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22050559 |
| | 5/16/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE $3000.00 VALUE ON THE APPLICATION IS LOW FOR A |
| | NEW GAS SERVICE, PIPING AND APPLIANCE INSTALLATIONS. |
| | PLEASE NOTE THAT PERMIT VALUE IS BASED ON LABOR, |
| | MATERIALS, EQUIPMENT, APPLIANCES, FIXTURES, SITE WORK |
| | AND DESIGN FEES- SEC. 109.3 WPB. PLEASE PROVIDE AN |
| | ITEMIZED COST BREAKDOWN TO VERIFY TOTAL COSTS. |
| | |
| | 2) PROVIDE A BASIC SITE OR FLOOR PLAN SHOWING THE |
| | PHYSICAL LOCATIONS OF THE APPLIANCES AND THE PIPING |
| | RUNS- SEC. 107.2.1 WPB, SEC. G2406.1 FBC RES. |
| | |
| | 3) THE GAS RISER SHALL BEAR THE ADDRESS OF THE |
| | PROPERTY, AND THE PRINTED NAME, LICENSE NUMBER AND |
| | SIGNATURE OF THE PERSON WHO PREPARED THE DRAWING- SEC. |
| | 107.2.1 WPB. |
| | |
| | 4) GAS RISER- FBC RES CHAPTER 24 |
| | A) PROVIDE THE DELIVERY PRESSURE AT THE METER AND THE |
| | PIPE SIZING TABLE ON THE DRAWING- SEC. G2413.4. |
| | B) THE LETTERS A & M ARE PRINTED BY SHUTOFF VALVES. |
| | ONLY MANUAL SHUTOFFS ARE REQUIRED FOR THE SYSTEM AT THE |
| | METER. THERE IS NO REQUIREMENT FOR AN AUTO VALVE IF |
| | THAT IS WHAT THE A STANDS FOR- SEC. G2420.2 & TABLE |
| | G2420.1.1. IF AN AUTO VALVE IS TO BE INSTALLED PLEAE |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS IN ACCORDANCE WITH |
| | SEC. G2408.1. |
| | C) PROVIDE THE SIZE AND LENGTH OF THE PIPES FROM THE |
| | METER TO THE WATER HEATER, AND THE LENGTH OF THE PIPE |
| | RISER TO THE WATER HEATER- SEC. G2413.4.1 FBC RES. |
| | BASED ON THE SUBMITTED TABLE 402.4(3) FBC FG A MINIMUM |
| | 1-INCH MAIN SUPPLY PIPE IS REQUIRED FOR A 320,000 BTU |
| | SYSTEM WITH A TOTAL DEVELOPED LENGTH OF 78 FT. |
| | D) SHOW ELECTRICAL BONDING METHOD FOR THE SCHEDULE 40 |
| | PIPING- SEC. G2411. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW GAS |
| | WATER HEATER THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE |
| | OF THE APPLIANCE- SEC. G2448.1 FBC RES. PROVIDE ON THE |
| | PLAN THE REQUIRED INSTALLATION CLEARANCES- SECS. |
| | G2427.1 & G2448.1 FBC RES. |
| | |
| | 6) PROVIDE TANKLESS WATER HEATER CONDENSATE DISPOSAL |
| | PLANS INCLUDING INSTALLATION OF THE MANUFACTURER'S |
| | RECOMMENDED NEUTRALIZING DEVICE PER SEC. G2408.1 FBC |
| | RES. INCLUDE THE SPECS FOR THE DEVICES IN THE EQUIPMENT |
| | SCHEDULE AND MODIFY THE DRAWINGS TO SHOW TYPE AND SIZE |
| | OF PIPING, PIPING RUN AND DISCHARGE LOCATIONS- SECS. |
| | 307.2-307.3 FBC FG. |
| | |
| | 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | RANGE THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE, AND |
| | LISTING OF THE APPLIANCE- SEC. G2447.1 FBC RES. A) |
| | PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RANGE- SEC. |
| | G2407.1 FBC RES. |
| | |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | RANGE THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE, AND |
| | LISTING OF THE APPLIANCE- SEC. G2447.1 FBC RES. A) |
| | PROVIDE COMBUSTION AIR CALCULATIONS AND VENTING PLANS |
| | FOR THE RANGE- SEC. G2407.1 FBC RES & SEC. 107.2.1 WPB. |
| | |
| | 9) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW |
| | DRYER THAT SHOW THE BTU GAS LOAD, INPUT PRESSURE, AND |
| | LISTING OF THE APPLIANCE- SEC. G2439.1 FBC RES. A) |
| | PROVIDE COMBUSTION AIR CALCULATIONS AND VENTING PLANS- |
| | SEC. G2407.1 FBC RES & SEC. 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |