Plan Review Details - Permit 22050529
Plan Review Stops For Permit 22050529
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-07-21 Cont ID  
Sent By rmcphers Date 2022-07-21 Time 16:50 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 16:40 Sent To  
Notes
2022-07-21 16:51:12NEW BUILDING BUILDOUT

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-09-16 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 15:33 Rev Time 0.00
Received By rmcphers Date 2022-09-16 Time 15:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-08-22 Cont ID  
Sent By rmcphers Date 2022-08-22 Time 08:45 Rev Time 0.00
Received By rmcphers Date 2022-08-22 Time 08:45 Sent To  
Notes
2022-08-22 08:45:40BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By rmcphers Date 2022-07-22 Time 08:28 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 16:40 Sent To  
Notes
2022-07-21 16:57:27BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE RESTROOM WALL FINISH TO COMPLY WITH
 FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 2) ACCESSIBLE RESTROOM - THE TOILET PAPER HOLDER
 DIMENSION FROM THE FACE OF THE TOILET SHOULD BE SHOWN
 TO THE CENTER OF THE DISPENSER FBC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER
  
 3) SIGNED AND SEALED DRAWINGS DO NOT SHOW AS DIGITALLY
 SIGNED IN ADOBE READER - SIGNED AND SEALED DRAWINGS IN
 PROJECTDOX NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED
 TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-09-21 Cont ID  
Sent By jleahy Date 2022-09-21 Time 14:07 Rev Time 0.00
Received By jleahy Date 2022-09-21 Time 13:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-08-29 Cont ID  
Sent By mpeterso Date 2022-08-29 Time 12:59 Rev Time 0.00
Received By mpeterso Date 2022-08-29 Time 12:59 Sent To  
Notes
2022-08-29 13:00:28PREVIOUS COMMENTS NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-28 Cont ID  
Sent By mpeterso Date 2022-06-28 Time 11:50 Rev Time 0.00
Received By mpeterso Date 2022-06-28 Time 11:50 Sent To  
Notes
2022-06-28 11:54:06SEE SIGNATURE REVIEW

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-09-21 Cont ID  
Sent By jleahy Date 2022-09-21 Time 14:07 Rev Time 0.00
Received By jleahy Date 2022-09-21 Time 14:07 Sent To  
Notes
2022-09-21 14:08:20VOICE AND DATA AS PER PLAN JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-08-30 Cont ID  
Sent By pleduc Date 2022-08-30 Time   Rev Time 0.00
Received By pleduc Date 2022-08-30 Time 11:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-08-05 Cont ID  
Sent By pleduc Date 2022-08-05 Time   Rev Time 0.00
Received By pleduc Date 2022-08-05 Time 15:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By pleduc Date 2022-05-25 Time   Rev Time 0.00
Received By pleduc Date 2022-05-25 Time 13:25 Sent To  
Notes
2022-05-25 13:38:03THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET A 0.0 - THERE IS AN INDICATION OF AN EXIT PATH
 TO A SINGLE FRONT EXIT DOOR; HOWEVER, THERE ARE OTHER
 ROOMS TO EXIT FROM WITH NO INDICATIONS OF EXIT MARKINGS
 TO THAT SAME EXIT OR TO A REAS EXTERIOR DOOR.
  
 PER NFPA 101 CH 38, NEW BUSINESS OCCUPANCIES AND CH 7
 MEANS OF EGRESS,
  
 38.2.5 ARRANGEMENT OF MEANS OF EGRESS.
 38.2.5.1 MEANS OF EGRESS SHALL BE ARRANGED IN
 ACCORDANCE WITH
 SECTION 7.5.
  
 38.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO THAT
 EXITS ARE READILY ACCESSIBLE AT ALL TIMES.
 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE
 FROM AN OPEN
 FLOOR AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR
 CORRIDORS LEADING DIRECTLY
 TO EVERY EXIT SHALL BE MAINTAINED AND SHALL BE ARRANGED
 TO PROVIDE ACCESS
 FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY
 SEPARATE WAYS OF TRAVEL,
 UNLESS OTHERWISE PROVIDED IN 7.5.1.1.3 AND 7.5.1.1.4
  
 PLEASE REVIEW AND CORRECT THE EXIT ACCESS/MARKINGS FROM
 THE 2 ROOMS(STORAGE & BREAK)'
  
  
  
 2) SHEET GN.0 - THERE IS AN INDICATION THAT THE
 BUILDING IS SPRINKLED HOWEVER, THIS IS NO INDICATION OF
 FIRE SPRINKLER MODIFICATIONS.
  
 THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER, INCLUDING DEMO, SHALL
 BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDEGMENT
  
  
 2A) THERE IS NO INDICATIONS THAT THIS BUILDING HAS A
 FIRE ALARM WHICH IS EXISTING.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT
 DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE ALARM, INCLUDING DEMO, SHALL BE
 DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLDEGMENT
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-09-21 Cont ID  
Sent By shill Date 2022-09-21 Time 17:38 Rev Time 0.00
Received By shill Date 2022-08-29 Time 17:05 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-29 Cont ID  
Sent By mpeterso Date 2022-08-29 Time 13:00 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 06:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-07-22 Cont ID  
Sent By rmcphers Date 2022-07-22 Time 08:29 Rev Time 0.00
Received By rmcphers Date 2022-05-23 Time 07:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-07-21 Cont ID  
Sent By rmcphers Date 2022-07-21 Time 16:51 Rev Time 0.00
Received By rmcphers Date 2022-07-21 Time 16:51 Sent To  
Notes
2022-07-21 16:51:40NEW BUILDING BUILDOUT

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-09-15 Cont ID  
Sent By medwards Date 2022-09-15 Time 07:45 Rev Time 0.00
Received By medwards Date 2022-09-15 Time 07:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-08-19 Cont ID  
Sent By medwards Date 2022-08-19 Time 09:38 Rev Time 0.00
Received By medwards Date 2022-08-19 Time 09:38 Sent To  
Notes
2022-08-19 09:39:53SEE 1ST CYCLE REVIEW COMMENTS BELOW:
  
 REVISE THE MECHANICAL DRAWINGS TO INCLUDE THE DRYER
 EXHAUST DUCT AND THE TERMINATION LOCATION. FMC 504
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-06-17 Cont ID  
Sent By medwards Date 2022-06-17 Time 09:38 Rev Time 0.00
Received By medwards Date 2022-06-17 Time 09:38 Sent To  
Notes
2022-06-17 09:39:59REVISED THE MECHANICAL DRAWING TO INCLUDE THE DRYER
 EXHAUST DUCT AND THE TERMINATION LOCATION. FMC 504
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-08-30 Cont ID  
Sent By jesmith Date 2022-08-30 Time 14:57 Rev Time 0.00
Received By jesmith Date 2022-08-30 Time 14:13 Sent To  
Notes
2022-08-30 14:57:02PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 PROVISO #1: DEFERRED SUBMITTALS SHALL BE SUBMITTED,
 APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED
 AT YOUR OWN RISK. WPB FBC 107.3.4.1
  
 PROVISO #2: FIRE RATED ASSEMBLIES FOR ANY APPLICABLE
 PENETRATIONS SHALL BE SUBMITTED, APPROVED AND ON SITE
 PRIOR TO INSPECTION PER WPB FBC 107.3.4.1. PROCEED AT
 YOUR OWN RISK.
  
 PROVISO #3: WASHER/DRYER COMBO IS ON THE LIST OF
 DEFERRED SUBMITTALS. UNIT SHALL COMPLY WITH FBC ACC
 611.4
  
 PROVISO #4: HAIR WASH SINK IS ON THE LIST OF DEFERRED
 SUBMITTALS. UNIT SHALL INCLUDE A BACKFLOW PREVENTER
 COMPLYING WITH FBC PL SECTION 608
  
 PROVISO #5: PLAN SHEET P1.1/NOTE 2; REFRIGERATOR IS ON
 THE LIST OF DEFERRED SUBMITTALS.IF A DRAIN IS REQUIRED
 FOR THE REFRIGERATOR THEN A REVISED PLAN SHOWING THE
 DRAIN IS REQUIRED PER FBC 107.2.1, SHOWING THE REVISED
 PIPING. PLAN SHALL BE SUBMITTED, APPRVED AND ON SITE
 PRIOR TO INSPECTION.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-08-11 Cont ID  
Sent By jesmith Date 2022-08-11 Time 11:46 Rev Time 0.00
Received By jesmith Date 2022-08-09 Time 16:33 Sent To  
Notes
2022-08-11 11:39:06CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 22050529 3161 S DIXIE HWY
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 I(3). SECOND REQUEST: MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL FOR THE FOLLOWING
 SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) BACKFLOW PREVENTER DEVICES
 ***C) THERMOSTATIC MIXING VALVES
 ***D) PRESSURE REDUCING VALVES
 ***E) SHAMPOO/HAIR WASH SINKS
 ***F) HAIR TRAP
 ***G) CLOTHES WASHER DISCHARGE INTERCEPTOR
 ***H) OWNER PROVIDED WATER DISPENSER
 PER WPB FBC 107.2.1, SUBMITTALS MAY BE DEFERRED.
 DEFERRED SUBMITTALS SHALL BE LISTED ON THE PLANS.
 DOCUMENTS SHALL BE SUBMITTED, APPROVED AND ON SITE
 PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK.
  
 II(10). P0.0/WATER HEATER DETAIL:
 NEW COMMENT: PROVIDE A CHECK VALVE IN THE COLD WATER
 LINE BETWEEN THE EXPANSION TANK CONNECTION AND THE
 SHUT-OFF VALVE TO PREVENT RECIRCULATION PUMP FROM
 FORCING HOT WATER INTO THE COLD WATER SYSTEM. PLEASE
 NOTE, CHECK VALVE WAS IN THE ORIGINAL DETAIL.
  
 III(20). P1.1/PLUMBING PLAN NOTE 5: PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING; PARTIALLY COMPLIED
 ***B) ROUTING OF HORIZONTAL 3 INCH MAIN VENT TO CHASE.
 TO BE CLEAR, PLEASE SHOW THE LOCATION OF THE CHASE;
 CLARIFY ON THE PLANS THAT IT COMMUNICATES DIRECTLY FROM
 GROUND FLOOR TO THE ROOF AND PROVIDE APPLICABLE FIRE
 RATED DETAILS FOR THE PIPE PENETRATION(S).
  
 IV(23). WASHING MACHINE/DRYER COMBO: PER WPB FBC
 107.2.1, PROVIDE THE FOLLOWING:
 ***A) DETAIL SHOWING COMPLIANCE WITH FBC ACC 611.4;
 FRONT LOADING MACHINES SHALL HAVE THE BOTTOM OF THE
 OPENING TO THE LAUNDRY COMPARTMENT LOCATED 15 INCHES
 MINIMUM AND 36 INCHES MAXIMUM ABOVE THE FINISH FLOOR
 PER FBC ACC 611.4
 ***B) A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR PARALLEL APPROACH SHALL BE PROVIDED. THE
 CLEAR FLOOR OR GROUND SPACE SHALL BE CENTERED ON THE
 APPLIANCE PER FBC ACC 611.2.
 PARTIALLY COMPLIED: THE DETAIL AND NOTES PROVIDED ON
 P1.1/DETAIL 6 ARE APPLICABLE TO A WASHER, BUT WITH NO
 MENTION OF THE DRYER; THE SPEED QUEEN LTEE5ASP173TW01
 NOTED ON A2.2 IS A STACKED COMBO AND IS NOT COMPLIANT.
 PROVIDE A COMPLIANT WASHER/DRYER COMBO AND REVISE
 A14.1/DETAIL 14 TO SHOW COMPLIANCE.
  
 V-(26). PER WPB FBC 107.2.1, PROVIDE DETAIL OF WATER
 CONNECTIONS TO HAIR WASH SINK. INCLUDE SHUT-OFF VALVES,
 TMV AND BACKFLOW PREVENTER DEVICES
 PARTIALLY COMPLIED: PROVIDE BACKFLOW PREVENTER DEVICE
  
 VI. NEW COMMENT: P1.1/NOTE 2; IF A DRAIN IS REQUIRED
 FOR THE REFRIGERATOR, IT SHALL DISCHARGE TO THE
 SANITARY THROUGH AN INDIRECT WASTE TO A WASTE
 RECEPTACLE WITH AN AIR GAP PER FBC PL 802.1
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-31 Cont ID  
Sent By jesmith Date 2022-05-31 Time 14:08 Rev Time 0.00
Received By jesmith Date 2022-05-26 Time 14:33 Sent To  
Notes
2022-05-31 13:54:16CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 22050529 3161 S DIXIE HWY
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 1. PER WPB FBC 107.2.1, A SEPARATE PERMIT IS REQUIRED
 FOR THE BACKFLOW PREVENTER.
 DUE TO A CHANGE IN PROCESS, THE BACKFLOW PERMIT AND
 GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED
 PRIOR TO ISSUANCE OF THE PRIMARY PERMIT (AS
 APPLICABLE). YOU CAN SUBMIT AN APPLICATION "TBD" (TO BE
 DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED BY
 EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
  
 2. THE SPACE APPEARS TO BE ON THE GROUND FLOOR IN A
 MULTI-USE BUILDING WITH RESIDENTIAL APARTMENTS ON THE
 UPPER FLOORS. PER WPB FBC 107.2.1, PLEASE CONFIRM OR
 CLARIFY; NOTE THE FLOOR LEVEL ON PLAN SHEET GN.0.
  
 3. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR
 THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***A) WATER HEATER
 ***B) BACKFLOW PREVENTER DEVICES
 ***C) THERMOSTATIC MIXING VALVES
 ***D) PRESSURE REDUCING VALVES
 ***E) SHAMPOO/HAIR WASH SINKS
 ***F) HAIR TRAP
 ***G) CLOTHES WASHER DISCHARGE INTERCEPTOR
  
 4. PLAN SHEET GN.0/MINIMUM PLUMBING FIXTURE
 CALCULATION: COMPLY WITH FLORIDA PLUMBING CODE 2020 7TH
 EDITION, TABLE 403.1 AND SECTION 403.2, NOT 2902.2.4
  
 5. PLAN SHEET GN.0/ACCESSIBILITY CODE: PER WPB FBC
 107.2.1, PLEASE LIST FLORIDA ACCESSIBILITY CODE 2020
 7TH EDITION
  
 6. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL
 SPECIFICATION FOR EACH SYSTEM INCLUDING BUT NOT LIMITED
 TO SANITARY DRAINS AND VENTS, WATER DISTRIBUTION, AC
 CONDENSATE. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND
 11.
  
 7. ALL COMPONENTS IN THE DOMESTIC WATER SYSTEM SHALL BE
 LEAD FREE IN ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
 PER WPB FBC 107.2.1, PROVIDE NOTE ON PLANS STATING THE
 SAME.
  
 8. PER WPB FBC 107.2.1, PROVIDE INSULATION
 SPECIFICATION FOR HOT WATER INSULATION. COMPLY WITH FBC
 EC C404.4 (A) AND TABLE C403.2.10.
  
 9. HANGER DETAIL- PER WPB FBC 107.2.1, PROVIDE PIPE
 HANGER DETAIL WITH A NOTE STATING, "HORIZONTAL PIPE
 SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 10. P0.0/WATER HEATER DETAIL
 ***A) FBC PL 504.6 (2) (10): T&P DISCHARGE TO FLOOR
 DRAIN SHALL BE THROUGH AN AIR GAP LOCATED IN THE SAME
 ROOM AS THE WATER HEATER; TERMINATE NOT MORE THAN 6
 INCHES ABOVE AND NOT LESS THAN TWO TIMES THE DISCHARGE
 PIPE DIAMETER ABOVE THE FLOOR OR FLOOD LEVEL RIM OF THE
 WASTE RECEPTOR .
 ***B) PROVIDE WATER HEATER PAN AND DRAIN (INCLUDING
 TERMINATION) PER WPB FPC 107.2.1; COMPLY WITH FBC PL
 504.7, 504.7.1 AND 504.7.2.
 ***C) THE DETAIL INDICATES A THERMAL MIXING VALVE
 (TMV-1) WITH140 DEGREE WATER DISTRIBUTION AND 120
 DEGREE WATER DISTRIBUTION. P1.0 WATER PLAN SHOWS ONLY
 ONE HOT WATER TO DISTRIBUTION. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND NOTE TEMPERATURE TO DISTRIBUTION.
 PLEASE NOTE, LEGIONELLA BACTERIA GROW AND MULTIPLY
 BETWEEN 68 DEGREES F AND 122 DEGREES F; THEY REPRODUCE
 RAPIDLY AND THRIVE BETWEEN 95 DEGREES F AND 115 DEGREES
 F. BELOW 68 DEGREES F, THE BACTERIA SURVIVES, BUT IT
 DOES NOT MULTIPLY. FROM 115 DEGREES F TO ABOUT 122
 DEGREES F, THE BACTERIA GROW SLOWLY. FROM 123 DEGREES F
 TO 131 DEGREES F, THE BACTERIA SURVIVE BUT DO NOT
 MULTIPLY. AT 131 DEGREES F, IT TAKES ABOUT FIVE TO SIX
 HOURS FOR THE BACTERIA TO DIE. AT 140 DEGREES F, THE
 BACTERIA DIES IN 32 MINUTES. ONE OF THE MOST WIDELY
 ACCEPTED AND PREFERRED METHODS OF CONTROLLING
 LEGIONELLA BACTERIA IS TO MAINTAIN THE HOT WATER SYSTEM
 STORAGE TANK TEMPERATURE AT OR ABOVE 135 DEGREES F TO
 140 DEGREES F.
 ***D) PLEASE NOTE, DUE TO THE WEIGHT (23LBS. EMPTY PLUS
 10.2 GALLON OF WATER AT 8.33 LBS. PER GALLON) THE
 AMTROL ST-25V EXPANSION TANK IS A FREE STANDING TANK
 DESIGNED TO SIT ON THE FLOOR. PER WPB FBC 107.2.1,
 PLEASE SHOW THIS ON THE DETAIL. ADDITIONALLY, SHOW
 LOCATION ON THE FLOOR PLAN AND ASSOCIATED PIPING.
  
 11. P0.0/PLUMBING FIXTURE SCHEDULE/WH-1: PER WPB FBC
 107.2.1, PROVIDE ENERGY EFFICIENCY FOR WATER HEATER;
 COMPLY WITH FBC EC TABLE C404.2
  
  
 12. P0.0/PLUMBING FIXTURE SCHEDULE/EWC-1/ WATER
 COOLER/EZSTL8LC IS A BI-LEVEL ADA COMPLIANT DRINKING
 FOUNTAIN; DESCRIPTION IS OF A WALL HYDRANT. SANITARY
 AND WATER PLANS DO NOT SHOW CONNECTIONS FOR THE
 FIXTURE. THE WATER PLAN DOES SHOW HOT AND COLD WATER TO
 A WATER DISPENSER. PER WPB FBC 107.2.1, PLEASE CLARIFY.
 SPECIFY AND PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL FOR THE WATER
 DISPENSER.
  
 13. P0.0/PLUMBING FIXTURE SCHEDULE/RPBP/REDUCED
 PRESSURE BACKFLOW PREVENTER: PER FBC PL 605.2 AND
 605.2.1. SPECIFY LEAD FREE BACKFLOW PREVENTER.
  
 14. PER PL 604.9, PROVIDE WATER HAMMER ARRESTORS
 COMPLYING WITH ASSE 1010 FOR THE WATER CONNECTIONS TO
 THE WASHING MACHINE AND TO THE REFRIGERATOR ICE LINE.
  
 15. PER FBC 1210.2.2 AND FBC PL 310.3, THE WALL
 COVERING NOTED (WC-3) IN THE RESTROOM DOES NOT COMPLY.
 WALL FINISH (WC-1) FOR MOP SINK IS COMPLIANT. WPB FBC
 107.2.1, PROVIDE COMPLIANT FINISH WALL SCHEDULE FOR
 RESTROOM SHOWING COMPLIANCE WITH FBC 1210.2.2 AND FBC
 PL 310.3. WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE PER FBC-BUILDING SEC.
 1210.2.2. SECTION 1210.2.2 STIPULATES THAT THE MATERIAL
 BE "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 16. THE PLANS ARE UNCLEAR. WILL THERE BE A NEW SLAB ON
 GRADE OR IS THERE AN EXISTING SLAB THAT WILL NEED TO BE
 CUT FOR TRENCHING. PER WPB FBC 107.2.1, PLEASE CLARIFY,
 AND IF APPLICABLE, PROVIDE A SLAB REPAIR DETAIL ON THE
 PLANS. SHOW THE WIDTH OF THE REPAIR, THE MINIMUM
 THICKNESS AND PSI OF THE CONCRETE TO BE REPLACED. SHOW
 SIZE, LENGTH, SPACING (ON CENTER), MINIMUM EMBEDMENT
 AND ANCHORING/ADHESIVE MATERIAL FOR DOWELS. THE REPAIR
 SHALL ALSO INCLUDE TERMITE TREATMENT OF THE SOIL AS
 WELL AS THE REQUIRED VAPOR BARRIER OVER WELL COMPACTED
 SOIL. A COPY OF THE TERMITE CERTIFICATE SHALL BE ONSITE
 FOR FINAL INSPECTION.
  
 17. PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC PL
 704.1, PROVIDE NOTE STATING "HORIZONTAL DRAINAGE PIPING
 LESS THAN 3 INCH DIAMETER SHALL HAVE A MINIMUM SLOPE OF
 1/4 INCH PER FOOT. 3 INCH TO 6 INCH DIAMETER SHALL HAVE
 A MINIMUM SLOPE OF 1/8 INCH PER FOOT".
  
 18. PLAN SHEET P1.1/NOTE 6: AC CONDENSATE- PER WPB CODE
 OF ORDINANCE CHAPTER 90, ARTICLE 3, SECTION 90-12B5,
 A/C CONDENSATE (INTERPRET THIS AS ANY CONDENSATION FROM
 EVAPORATOR COILS) SHALL NOT DISCHARGE TO THE CITY
 UTILITIES SANITARY SEWAGE INFRASTRUCTURE WITHOUT
 PERMISSION FROM THE UTILITIES DEPARTMENT. YOU MAY
 CONTACT 561-494-1128 FOR ADDITIONAL INFORMATION. MOVING
 FORWARD, DISCHARGE THE CONDENSATE TO AN EXTERIOR
 DRYWELL; PER WPB FBC 107.2.1, PROVIDE ROUTING AND
 DRYWELL DETAIL.
  
 19. P1.0/PRV-1: PER FBC PL 604.8, PROVIDE A STRAINER
 AHEAD OF PRV-1.
  
 20. P1.1/PLUMBING PLAN NOTE 5: PER WPB FBC 107.2.1,
 PROVIDE THE FOLLOWING;
 ***A) DETAIL FOR SUPPORT OF 3 INCH VERTICAL VENT IN
 CHASE
 ***B) ROUTING OF HORIZONTAL 3 INCH MAIN VENT TO CHASE.
  
 21. PER WPB FBC 107.2.1, PROVIDE DRAINAGE FIXTURE UNIT
 SCHEDULE. COMPLY WITH FBC PL TABLES 709.1, 709.2.
  
 22. A4.1/FINISH WALL KEY: PER WPB FBC 107.2.1, ADD TAG
 WC-1 WALL COVERING FOR MOP SINK.
  
 23. WASHING MACHINE/DRYER COMBO: PER WPB FBC 107.2.1,
 PROVIDE THE FOLLOWING:
 ***A) DETAIL SHOWING COMPLIANCE WITH FBC ACC 611.4;
 FRONT LOADING MACHINES SHALL HAVE THE BOTTOM OF THE
 OPENING TO THE LAUNDRY COMPARTMENT LOCATED 15 INCHES
 MINIMUM AND 36 INCHESMAXIMUM ABOVE THE FINISH FLOOR PER
 FBC ACC 611.4
 ***B) A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305
 POSITIONED FOR PARALLEL APPROACH SHALL BE PROVIDED. THE
 CLEAR FLOOR OR GROUND SPACE SHALL BE CENTERED ON THE
 APPLIANCE PER FBC ACC 611.2.
  
 24. PER FBC PL 1002.4, SPECIFY TRAP SEAL PROTECTION FOR
 THE FLOOR DRAIN(S) COMPLYING ONE OF THE METHODS IN
 SECTIONS 1002.4.1.1 THROUGH 1002.4.1.4.
 ***A) PER WPB FBC 107.2.1, PROVIDE TRAP
 PROTECTION/PRIMER DETAIL.
  
 25. PER FBC PL 1003.6, AN INTERCEPTOR IS REQUIRED FOR
 THE CLOTHES WASHER DRAIN.
 ***A) PER WPB FBC 107.2.1, PROVIDE MANUFACTURER'S
 SPECIFICATION AND A DETAIL FOR THE INSTALLATION.
  
 26. PER WPB FBC 107.2.1, PROVIDE DETAIL OF WATER
 CONNECTIONS TO HAIR WASH SINK. INCLUDE SHUT-OFF VALVES,
 TMV AND BACKFLOW PREVENTER DEVICES
  
 27. P1.1/PLUMBING NOTE 4: SPECIFIED HAIR TRAP COMES
 WITH 1-1/2 INCH SLIP JOINT TUBULAR CONNECTIONS
 REQUIRING CONNECTION TO TUBULAR FITTINGS, TAILPIECES,
 ETC. NOTE SAYS NO THIN WALL PVC WILL BE PERMITTED. PER
 WPB FBC 107.2.1, PLEASE CLARIFY. MODIFY NOTE AS NEEDED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-09-15 Cont ID  
Sent By medwards Date 2022-09-15 Time 07:45 Rev Time 0.00
Received By medwards Date 2022-09-15 Time 07:45 Sent To  
Notes
2022-08-30 14:56:28SIGNATURES FOR PLUMBING PLANS ARE VALID. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-08-22 Cont ID  
Sent By rmcphers Date 2022-08-22 Time 08:46 Rev Time 0.00
Received By rmcphers Date 2022-08-22 Time 08:46 Sent To  
Notes
2022-08-22 08:49:53SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) ALL SIGNED AND SEALED DRAWINGS DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
2022-08-11 11:46:16PLANS APPEAR TO BE SCANNED WET SEAL. PROVIDE DIGITAL
 SIGNATURES FOR PLUMBING. JS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-28 Cont ID  
Sent By mpeterso Date 2022-06-28 Time 11:54 Rev Time 0.00
Received By mpeterso Date 2022-06-28 Time 11:54 Sent To  
Notes
2022-06-28 11:55:31SIGNATURE REVIEW FAILED
 ALL PLANS DO NOT HAVE THE REQUIRED DIGITAL SIGNATURE
  
 SIGNATURE REVIEW FAILED
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
2022-06-17 09:42:09SIGNATURES APPEAR TO BE COPIES OF A WET SEAL. THERE
 MUST BE AN ORIGINAL DIGITAL SIGNATURE FOR MECHANICAL.
 ME
  
  
  
2022-05-26 15:31:36SIGNATURES FOR PLUMBING; NOT APPARENT IN PDFS.
 CORRECTIONS NEEDED. JS

Review Stop Z ZONING
Rev No 3 Status P Date 2022-09-21 Cont ID  
Sent By jroach Date 2022-09-21 Time 10:55 Rev Time 0.00
Received By jroach Date 2022-09-21 Time 10:47 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-19 Cont ID  
Sent By jroach Date 2022-08-19 Time 09:49 Rev Time 0.00
Received By jroach Date 2022-08-19 Time 09:49 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-06-17 Cont ID  
Sent By jroach Date 2022-06-17 Time 16:21 Rev Time 0.00