Plan Review Details - Permit 22050430
Plan Review Stops For Permit 22050430
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-21 Cont ID  
Sent By jbrooks Date 2022-07-21 Time 09:54 Rev Time 0.00
Received By jbrooks Date 2022-07-21 Time 07:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-29 Cont ID  
Sent By jbrooks Date 2022-06-29 Time 13:06 Rev Time 0.00
Received By jbrooks Date 2022-06-29 Time 12:42 Sent To  
Notes
2022-06-29 13:06:19JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 18-1105.05 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT
 SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-13 Cont ID  
Sent By jbrooks Date 2022-06-13 Time 08:59 Rev Time 0.00
Received By jbrooks Date 2022-06-13 Time 07:40 Sent To  
Notes
2022-06-13 08:59:45JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL10674-R16 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-10 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 1-10.
 2. FBC R 301 FAC9N-3 FLORIDA STATE PRODUCT APPROVAL
 FL10758-R8 IS INCOMPLETE, PROVIDE THE FOLLOWING
 ADDITIONAL INFORMATION: EVALUATION REPORT PAGES 1-5 TO
 INCLUDE LIMITATIONS PAGE(S). THE EVALUATION REPORTS CAN
 BE PRINTED FROM THE SUMMARY OF PRODUCTS LOCATED AT THE
 BOTTOM OF THE COVER PAGE. PRINT PAGES 1-5.
 3. FBC B 107.2.1 SUBMITTED PRODUCT APPROVAL FL10450-R13
 HAS BEEN REVISED TO FL10450-R15. PLEASE PROVIDE A
 COMPLETE SET; IT COVERS MULTIPLE PRODUCT TYPES; ROOF
 COVER OPTIONS; ALLOWABLE UNDERLAYMENT/TILE-ADHESIVE
 COMBINATIONS, ALLOWABLE SUBSTRATES & ATTACHMENT
 LIMITATIONS. SELECT OPTIONS FROM EACH CATEGORY TO BE
 USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 4. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 18-1105.02 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT
 SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING
 5. FBC B 107.2.1 MIAMI-DADE NOA?S & FLORIDA PRODUCT
 APPROVALS WERE BOTH SUBMITTED FOR THE ASPHALT SHINGLES,
 ROOF UNDERLAYMENT & ROOF VENT SYSTEMS; SELECT
 NOA/PRODUCT APPROVAL TO BE USED FOR EACH SYSTEM AND
 ENSURE NOA/PRODUCT APPROVAL ARE COMPLETE AND RESUBMIT
 THE LATEST VERSIONS. SUBMITTED NOA?S/PRODUCT APPROVALS
 DO NOT CROSS REFERENCE EACH OTHER.
 6. FBC B 107.2.1 FOR CLARITY PLEASE PROVIDE A ROOF
 DIAGRAM/SKETCH WITH THE AREAS TO RECEIVE NEW ROOFING
 CLEARLY IDENTIFIED ON DRAWING; INCLUDE ROOF SLOPE(S),
 MEAN ROOF HEIGHT(S).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-21 Cont ID  
Sent By jbrooks Date 2022-07-21 Time 09:54 Rev Time 0.00
Received By jbrooks Date 2022-07-08 Time 08:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-29 Cont ID  
Sent By jbrooks Date 2022-06-29 Time 13:06 Rev Time 0.00
Received By jbrooks Date 2022-06-18 Time 07:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-13 Cont ID  
Sent By jbrooks Date 2022-06-13 Time 08:59 Rev Time 0.00
Received By jbrooks Date 2022-06-10 Time 06:39 Sent To  
Notes
***NONE***