| 2022-05-24 11:20:57 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | 1. 2017 WPB AMENDS 107.2.1 -- PLEASE DESCRIBE THE |
| | INTENDED SEWER AND WATER CONNECTIONS FOR THE TRAILER. |
| | IF CONNECTING TO THE POTABLE WATER SUPPLY, A BACKFLOW |
| | DEVICE WILL BE REQUIRED (PER THE UTILITIES DEPARTMENT |
| | GUIDELINES AND THE CROSS CONNECTION CONTROL MANUAL). |
| | PLEASE PULL A TEMPORARY WATER PERMIT WITH BACKFLOW |
| | DEVICE FOR THE JOB TRAILER. |
| | |
| | 2. 2017 WPB AMEND - 107.3 - ALSO, DUE TO A CHANGE IN |
| | PROCESS, THE BACKFLOW PERMIT AND THE INTERCEPTOR PERMIT |
| | FOR THE BUILDING HAVE NOT BEEN PULLED YET AND ARE |
| | REQUIRED. PLEASE SUBMIT FOR SEPARATE PERMITS FOR THE |
| | BACKFLOWS AND THE INTERCEPTOR REQUIRED FOR THE |
| | BUILDING. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |
| | RYAN W. BROWN |
| | CHIEF PLUMBING INSPECTOR |
| | OFFICE: 561-805-6692 |
| | CELL: 561-517-4293 |
| | EMAIL: [email protected] |
| | |