Plan Review Details - Permit 22050412
Plan Review Stops For Permit 22050412
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status N Date 2022-07-22 Cont ID  
Sent By jleahy Date 2022-07-22 Time 10:24 Rev Time 0.00
Received By jleahy Date 2022-07-22 Time 10:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 09:11 Rev Time 0.00
Received By jleahy Date 2022-07-17 Time 09:11 Sent To  
Notes
2022-07-17 09:13:37PRE CAST SLAB NOT LISTED FOR THIS TYPE OF GENEREATOR.
  
 SUBMIT THIS AGAIN WITH SAME SLAB PLAN AND YOU WILL
 ASSESSED 4X PERMIT FEE FOR SAME REVIEW ITEM OVER AND
 OVER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2022-06-02 Cont ID  
Sent By jleahy Date 2022-06-02 Time 13:14 Rev Time 0.00
Received By jleahy Date 2022-06-02 Time 13:14 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-07-22 Cont ID  
Sent By jleahy Date 2022-07-22 Time 10:17 Rev Time 0.00
Received By jleahy Date 2022-07-22 Time 10:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 09:15 Rev Time 0.00
Received By jleahy Date 2022-07-17 Time 09:15 Sent To  
Notes
2022-07-17 09:17:08PRECAST SLAB DETAIL NOT FOR THIS GENERATOR. SUBMIT SAME
 PLAN AGAIN AND YOU WILL RECEIVE 4X FEE FOR SAME REVIEW
 ITEM AGAIN. JLEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 15:31 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 15:31 Sent To  
Notes
2022-06-10 15:32:45PRECAST SLAB DOES NOT LIST BRIGGS AND STRATON GENERATOR
 OR 26KW.??????

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-02 Cont ID  
Sent By jleahy Date 2022-06-02 Time 13:18 Rev Time 0.00
Received By jleahy Date 2022-06-02 Time 13:14 Sent To  
Notes
2022-06-02 13:20:10FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FEED FROM METER TO TRANSFER SWITCH (200 AND FEEDER TO
 PANEL (200) TO SMALL PER 310.15(B)(7).
  
 SLAB NOT LISTED FOR THIS GENERATOR. GENERATOR IN NOY
 LISTED ON PAD SPECS.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-05-21 Cont ID  
Sent By rwbrown Date 2022-05-21 Time 10:41 Rev Time 0.00
Received By rwbrown Date 2022-05-21 Time 10:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status P Date 2022-07-22 Cont ID  
Sent By jleahy Date 2022-07-22 Time 10:23 Rev Time 0.00
Received By jleahy Date 2022-07-19 Time 17:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 09:17 Rev Time 0.00
Received By jleahy Date 2022-07-14 Time 13:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 15:33 Rev Time 0.00
Received By jleahy Date 2022-06-07 Time 07:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-02 Cont ID  
Sent By jleahy Date 2022-06-02 Time 13:25 Rev Time 0.00
Received By jleahy Date 2022-05-13 Time 07:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-05-21 Cont ID  
Sent By rwbrown Date 2022-05-21 Time 10:40 Rev Time 0.00
Received By rwbrown Date 2022-05-21 Time 10:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-07-22 Cont ID  
Sent By jleahy Date 2022-07-22 Time 10:22 Rev Time 0.00
Received By jleahy Date 2022-07-22 Time 10:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-19 Cont ID  
Sent By jleahy Date 2022-07-19 Time 14:13 Rev Time 0.00
Received By jleahy Date 2022-07-19 Time 14:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-07-17 Cont ID  
Sent By jleahy Date 2022-07-17 Time 09:13 Rev Time 0.00
Received By jleahy Date 2022-07-17 Time 09:14 Sent To  
Notes
2022-07-17 09:15:13WRONG PLAN AGAIN FOR THE PRE CAST SLAB. JLEAHY
  
 SUBMIT THE SAME PRECAST SLAB PLAN AGAIN WILL GET YOU 4X
 FEE FOR REPEATED REVIEW ITEM.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-10 Cont ID  
Sent By jleahy Date 2022-06-10 Time 15:32 Rev Time 0.00
Received By jleahy Date 2022-06-10 Time 15:17 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-02 Cont ID  
Sent By jleahy Date 2022-06-02 Time 13:25 Rev Time 0.00
Received By jleahy Date 2022-06-02 Time 13:15 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-26 Cont ID  
Sent By vbroglia Date 2022-05-26 Time 15:38 Rev Time 0.00
Received By vbroglia Date 2022-05-26 Time 15:38 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy