Plan Review Details - Permit 22050384
Plan Review Stops For Permit 22050384
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2022-08-01 Time 16:44 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-07-22 Cont ID  
Sent By rmcphers Date 2022-07-22 Time 08:42 Rev Time 0.00
Received By rmcphers Date 2022-07-22 Time 08:42 Sent To  
Notes
2022-07-22 08:43:27REMOVING KITCHEN CABINETS IS DEMO - - PLEASE PROVIDE A
 SIGNED ACKNOWLEDGEMENT FROM THE CONTRACTOR, ON
 LETTERHEAD, STATING THAT
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND NOTIFICATION WILL BE GIVEN
 TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 10:16 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 10:16 Sent To  
Notes
2022-06-29 10:17:08PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT
  
 "THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND NOTIFICATION WILL BE GIVEN
 TIMELY"
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-08-01 Cont ID  
Sent By rmcphers Date 2022-08-01 Time 16:44 Rev Time 0.00
Received By rmcphers Date 2022-08-01 Time 16:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-22 Cont ID  
Sent By rmcphers Date 2022-07-22 Time 08:41 Rev Time 0.00
Received By rmcphers Date 2022-07-22 Time 08:37 Sent To  
Notes
2022-07-22 08:41:45CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) YOU HAVE A LETTER IN PROJECTDOX EXCLUDING ITEMS -
 BUT THE WORK DESCRIPTION ON THE PERMIT APPLICATION HAS
 NOT CHANGED - PLEASE REVISE THE PERMIT APPLICATION.
  
 2) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
 (NEED THE ACTUAL TEST REPORTS NOT THE MANUFACTURES SPEC
 SHEET)
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 10:18 Rev Time 0.00
Received By rmcphers Date 2022-06-29 Time 10:17 Sent To  
Notes
2022-06-29 10:18:07CONDO REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED -
  
 1) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 2). YOU CAN EMAIL ME THE PROPOSED TEST REPORTS TO
 VERIFY THAT THEY ARE TEST REPORTS BEFORE RESUBMITTING
 TO PROJECTDOX ( [email protected] )
  

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 08:38 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 08:38 Sent To  
Notes
2022-08-04 08:39:30NO ELECTRIC WORK SHOWN, REVIEWED OR APPROVED

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 09:50 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 09:50 Sent To  
Notes
2022-07-25 09:52:59PROJECT VALUE STILL NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-08 Cont ID  
Sent By mpeterso Date 2022-06-08 Time 15:25 Rev Time 0.00
Received By mpeterso Date 2022-06-08 Time 15:25 Sent To  
Notes
2022-06-08 15:34:28ELECTRIC REVIEW FAILED
 1) CONTACT SUBMITTED STATES AN ELECTRIC RECEPTACLE TO
 BE RELOCATED, NOT IN THIS CONTRACT. PLEASE PROVIDE
 CLARITY AS TO WHETHER THIS RECEPTACLEIS TO BE RELOCATED
 BEFORE WORK ON THIS PROJECT WILL BE COMPLETED. FBC
 107.2
 2) PLEASE PROVIDE A KITCHEN PLAN DETAILING CHANGES IN
 LAYOUT AND WHETHER ANY ELECTRICAL MODIFICATIONS NEED TO
 BE MADE TO COMPLY WITH NEC CODES. FBC 107.2
 3) VALUE STATED ON PERMIT APPLICATION IS $25,000. VALUE
 STATED ON CONTRACT SUBMITTED STATES A VALUE OF $48,358.
 PLEASE PROVIDE CLARITY FOR THIS DISCREPANCY. WPB AND
 FBC 109.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-07-29 Cont ID  
Sent By pleduc Date 2022-07-29 Time   Rev Time 0.00
Received By pleduc Date 2022-07-29 Time 10:27 Sent To  
Notes
2022-07-29 10:31:27FIRE PROVISO:
  
 ENSURE FIRE RATED TENANT/CORRIDOR SEPARATION WALLS
 ARE MAINTAINED & REPAIRED IF DAMAGED.
  
 PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-20 Cont ID  
Sent By pleduc Date 2022-05-20 Time   Rev Time 0.00
Received By pleduc Date 2022-05-20 Time 12:26 Sent To  
Notes
2022-05-20 12:31:09FIRE PROVISO:
  
 WITH DRYWAL REMOVAL/REPAIR, ENSURE FIRE RATED TENANT
 SEPARATION/CORRIDOR
 WALLS ARE REPAIRED TO THE EXISTING FIRE RATED
 SEPARATION.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 08:39 Rev Time 0.00
Received By mpeterso Date 2022-07-28 Time 07:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 09:53 Rev Time 0.00
Received By mpeterso Date 2022-07-13 Time 09:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-29 Cont ID  
Sent By rmcphers Date 2022-06-29 Time 10:18 Rev Time 0.00
Received By rmcphers Date 2022-05-19 Time 06:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-07-29 Cont ID  
Sent By rwbrown Date 2022-07-29 Time 07:47 Rev Time 0.00
Received By rwbrown Date 2022-07-29 Time 07:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-26 Cont ID  
Sent By rwbrown Date 2022-05-26 Time 14:20 Rev Time 0.00
Received By rwbrown Date 2022-05-26 Time 14:20 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-07-22 Cont ID  
Sent By rmcphers Date 2022-07-22 Time 08:43 Rev Time 0.00
Received By rmcphers Date 2022-07-22 Time 08:43 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-06-08 Cont ID  
Sent By mpeterso Date 2022-06-08 Time 15:34 Rev Time 0.00
Received By mpeterso Date 2022-06-08 Time 15:34 Sent To  
Notes
***NONE***