Plan Review Details - Permit 22050039
Plan Review Stops For Permit 22050039
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-12 Cont ID  
Sent By shill Date 2022-05-12 Time 10:03 Rev Time 0.00
Received By shill Date 2022-05-12 Time 10:03 Sent To  
Notes
2022-05-12 10:03:30NEW VINYL FLOORING PROPOSED, OVER LV200 UNDERLAYMENT
 (ISSUED WITH ORIGINAL PERMIT)
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-11 Cont ID  
Sent By pvalenti Date 2022-05-11 Time 13:42 Rev Time 0.00
Received By pvalenti Date 2022-05-11 Time 13:42 Sent To  
Notes
2022-05-11 13:46:18PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-03 Cont ID  
Sent By pleduc Date 2022-05-03 Time   Rev Time 0.00
Received By pleduc Date 2022-05-03 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-11 Cont ID  
Sent By pvalenti Date 2022-05-11 Time 13:46 Rev Time 0.00
Received By pvalenti Date 2022-05-02 Time 13:08 Sent To  
Notes
***NONE***