| Plan Review Stops For Permit 22050030 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-10-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-10-25 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-10-25 |
Time |
10:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-22 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-21 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2022-07-22 13:37:46 | BUILDING REVIEW COMMENTS: | | | | | | W.P.B. PERMIT: REVISION #22050030 | | | 500 N. QUADRILLE BLVD. | | | BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS | | | CONSTRUCTION TYPE: 1A, SPRINKLERED | | | MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E | | | | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | FLORIDA BUILDING CODE,5TH EDITION (2014) | | | FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | | BELOW) | | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | | BUILDING-PERMIT-FORMS | | | FBC[B] = FBC BUILDING | | | FBC[A] = FBC ACCESSIBILITY | | | FBC[E] = FBC ENERGY CONSERVATION | | | | | | | | | BUILDING REVIEW COMMENTS: | | | | | | 1) ON SHEETS A1.225 & A1.228 THE NOTE THAT REFERS TO | | | ANOTHER SHEET FOR ADDITIONAL POOL INFORMATION DOES NOT | | | SPECIFY THE SHEET NUMBER TO REFER TO. FBC 107.2.1 | | | | | | 2) ON SHEET A2.107 IT APPEARS THAT ONE OF THE LAYERS | | | WAS NOT TURNED ON. THE RESTROOM FIXTURES, GYM EQUIPMENT | | | AND FIXTURES IN THE UNITS ARE NOT SHOWN AS THEY WERE IN | | | THE PREVIOUS VERSION OF THE DRAWING. FBC 107.2.1 | | | | | | 3) ON SHEET A2.225 THE DOORS AND SWINGS ARE NOT SHOWN | | | BUT MAY IMPEDE TRAVEL IN THE CORRIDOR. FBC 1005.7.1 | | | DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED | | | WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY | | | POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE | | | THAN ONE-HALF. | | | | | | 4) SEE FIRE REVIEW COMMENTS FOR DOOR SWINGS IN | | | DIRECTION OF TRAVEL. 1010.1.2.1 DIRECTION OF SWING. | | | PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE | | | DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA | | | CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A | | | GROUP H OCCUPANCY. | | | | | | 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-10-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-10-17 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-10-17 |
Time |
07:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-06-30 |
Time |
07:54 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-06-30 |
Time |
07:02 |
Sent To |
|
|
| Notes |
| 2022-06-30 07:56:35 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | FIRE ALARM AND LOW VOLTAGE SYSTEMS PAGES TO BE | | | SUBMITTED UNDER SEPARATE PERMITT REVISIONS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-09-19 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-09-19 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-09-19 |
Time |
13:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2022-06-10 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-06-10 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-06-07 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2022-06-08 16:31:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE ARE INDICATIONS OF THE EXIT DOORS FROM THE | | | AMENITY DECK SWINGING OUT AGAINST THE PATH OF EXIT | | | TRAVEL | | | | | | PER NFPA 101 CH 12 & CH 7 | | | | | | 12.2.2.2 DOORS. | | | 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE | | | PERMITTED | | | | | | 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES | | | REQUIRED TO BE OF | | | THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN | | | THE DIRECTION | | | OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS: | | | (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD | | | OF 50 OR MORE, | | | EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS: | | | (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE | | | REQUIRED TO SWING | | | IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY | | | 7.2.4.3.8.1 | | | OR 7.2.4.3.8.2. | | | (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED | | | TO SWING | | | IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH | | | CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19. | | | (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT | | | ENCLOSURE, UNLESS THE | | | DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT | | | OPENS DIRECTLY | | | INTO AN EXIT ENCLOSURE | | | (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD | | | CONTENTS AREA | | | | | | PLEASE REVIEW AND CORRECT | | | | | | | | | | | | 1A) THE DOOR HARDWARE OF THE EXIT DOORS FROM THE | | | AMENNITY DECK SHALL COMPLY WITH NFPA 101 CH 12 & 7 | | | | | | 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM | | | AN AREA HAVING | | | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE | | | PERMITTED TO BE PRO VIDED WITH A LATCH OR LOCK ONLY IF | | | THE LATCH OR LOCK IS PANIC HARDWARE OR | | | FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS | | | OTHERWISE PERMITTED | | | BY ONE OF THE FOLLOWING: | | | (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS | | | ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5. | | | (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE | | | OF ELECTRICAL | | | LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6. | | | 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5 | | | SHALL BE PERMITTED | | | TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS | | | IF BOTH OF THE FOL LOWING CONDITIONS APPLY: | | | (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT | | | AND THE ASSEMBLY | | | OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500. | | | (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN | | | ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR | | | MORE ARE RELEASED BY | | | PANIC HARDWARE OR FIRE EXIT HARDWARE | | | | | | 7.2.1.7* PANIC HARDWARE AND FIRE EXIT HARDWARE | | | | | | 7.2.1.7.1 WHERE A SIDE-HINGED OR PIVOTED-SWINGING DOOR | | | ASSEMBLY IS | | | REQUIRED TO BE EQUIPPED WITH PANIC OR FIRE EXIT | | | HARDWARE, SUCH HARDWARE | | | SHALL MEET ALL OF THE FOLLOWING CRITERIA: | | | (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, WITH | | | THE LENGTH OF THE | | | ACTUATING PORTION OF THE CROSS BAR OR PUSH PAD NOT LESS | | | THAN ONE-HALF | | | OF THE WIDTH OF THE DOOR LEAF. | | | (2) IT SHALL BE MOUNTED AS FOLLOWS: | | | (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN. | | | (865 MM), AND | | | NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. | | | (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30 | | | IN. (760 MM), | | | AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR. | | | (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE | | | NOT TO EXCEED 15 LBF | | | (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND LATCHES | | | | | | PLEASE REVIEW AND CORRECT | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2022-12-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-16 |
Time |
09:21 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-27 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-15 |
Time |
07:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-12-05 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-11-18 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-11-08 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-09-09 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-08-29 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-08-29 |
Time |
07:18 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-06-06 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-27 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-27 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-12-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-01 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-01 |
Time |
14:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-09-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-23 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-23 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2022-09-23 10:42:31 | 2ND REVIEW FMC | | | PERMIT: 22050030 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) IT IS UNCLEAR TO THIS REVIEWER BASED ON THE WORDING | | | IN THE NARRATIVE, THE FOLLOWING IS THE NARRATIVE OF | | | CHANGES ASOCIATED WITH THE ONE WEST PALM CCD #48 | | | CHANGES: | | | NOTE: ITEMS IN RED HAVE BEEN UPDATED SINCE PREVIOUS | | | SUBMISSIOM. AM I TO REVIEW ONLY THE ITEMS IN RED? | | | | | | 2) PLEASE BE CLEAR AS TO THE SCOPE OF THE REVISION AND | | | ONLY SEND RELEVANT DOCUMENTS. IF ONLY THE COMMENTS IN | | | RED ARE TO BE REVIEWED IN THIS REVISION PLEASE REMOVE | | | ALL THE OTHER COMMENTS. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2022-06-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-06-21 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-06-21 |
Time |
08:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-12-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-12-16 |
Time |
09:14 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-26 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-26 |
Time |
07:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-06-07 |
Time |
16:05 |
Rev Time |
|
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-12-27 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-12-27 |
Time |
12:54 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-12-27 |
Time |
12:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-12-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2022-12-05 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2022-12-05 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2022-12-05 15:13:58 | SIGNATURE REVIEW | | | | | | 1- MECHANICAL DRAWINGS M.307B, M.M601, M603, M705 AND | | | M.817 AND ALL PLUMBING DRAWINGS HAVE AN ENGINEER'S | | | SELF-CERTIFIED DIGITAL SIGNATURE. ENGINEER CANNOT | | | SELF-CERTIFY THE DIGITAL SIGNATURE. THIRD PARTY | | | CERTIFICATION IS REQUIRED BY FAC 61G15-23.004. (NOTE: | | | ENGINEER TO CONTACT THE BOARD OF ENGINEER'S FOR | | | SELF-CERTIFIED DIGITAL SIGNATURE QUESTIONS). | | | NOTE: PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH THIRD | | | PARTY CERTIFIED DIGITAL SIGNATURE OR PROVIDE HARD COPY | | | WITH ENGINEER'S WET SIGNATURE. | | | | | | ENGINEERS | | | 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND | | | SEALING ELECTRONICALLY TRANSMITTED PLANS, | | | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | 2022-12-01 14:08:46 | MECHANICAL DIGITAL SIGNATURES APPROVED ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-26 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-26 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2022-09-26 07:56:56 | * PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS | | | PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001 | | | AND BE EITHER DIGITALLY SIGNED AND SEALED -OR- | | | ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH | | | 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY. | | | * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN | | | ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE | | | DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH | | | 61G1-16.005 F.A.C. | | | | | | PLUMBING AND MECHANICAL PAGES SIGNED BY CHAD WISLER ARE | | | SELF CERTIFIED. THE BOARD OF PROFESSIONAL ENGINEERS | | | REQUIRES THE DIGITAL SIGNATURES TO BE THIRD PARTY | | | CERTIFIED. | | 2022-09-23 10:46:59 | MECHANICAL DESIGNER MUST HAVE THEIR DIGITAL SIGNATURE | | | 3RD PARTY VERIFIED, ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-07-21 |
Time |
15:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-07-21 |
Time |
15:48 |
Sent To |
|
|
| Notes |
| 2022-07-21 17:10:19 | THE LANDSCAPE PLANS ARE NOT DIGITALLY SIGNED BY THE | | | LANDSCAPE ENGINEER. CHAD WISLER, THE ENGINEER THAT | | | DIGITALLY SIGNED THE MECHANICAL AND PLUMBING SHEETS | | | SELF-CERTIFIED HIS SIGNATURE. THE BOARD OF PROFESSIONAL | | | ENGINEERS REQUIRES ENGINEERS TO USE AN APPROVED THIRD | | | PARTY TO CERTIFY THEIR DIGITAL SIGNATURES. | | | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | | THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM. | | | YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND | | | SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC | | | PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | | TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & | | | FAC 61G15 | | 2022-06-30 07:59:04 | ELECTRICAL PAGES SIGNATURES ARE APPROVED. | | | | | | FIRE ALARM PAGES TO BE SUBMITTED UNDER FIRE ALARM | | | PERMIT REVISION. | | | | | | LOW VOLTAGE SYSTEMS TO BE SUBMITTED UNDER LV PERMIT | | | REVISION. | | 2022-06-21 08:53:39 | MECHANICAL ENGINEER WILL NEED TO HAVE HIS DIGITAL | | | SIGNATURE THIRD PARTY VERIFIED. ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-11-07 |
|
|
Cont ID |
|
| Sent By |
ckimmerl |
Date |
2022-11-07 |
Time |
12:13 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-11-07 |
Time |
12:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2022-08-26 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
ckimmerl |
Date |
2022-08-26 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2022-08-26 16:14:25 | 1. THE HARDSCAPE AND LANDSCAPE PLANS AS PART OF THIS | | | PERMIT (L1-710) AND (L1-720) DO NOT MATCH THOSE OF THE | | | APPROVED FORMAL SITE PLAN 15-06A FROM 12.1.20. | | | | | | - LANDSCAPE SPACES APPEAR TO HAVE CHANGED IN SIZE AND | | | LOCATION. | | | - PLEASE BE SURE PLANS MATCH WHAT WAS APPROVED. | | | | | | CHRIS KIMMERLY, AICP | | | URBAN DESIGN PLANNER | | | [email protected] 822.1426 |
|
|