Plan Review Details - Permit 22050030
Plan Review Stops For Permit 22050030
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-10-25 Cont ID  
Sent By rmcdouga Date 2022-10-25 Time 14:27 Rev Time 0.00
Received By rmcdouga Date 2022-10-25 Time 10:34 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-22 Cont ID  
Sent By rmcdouga Date 2022-07-22 Time 13:37 Rev Time 0.00
Received By rmcdouga Date 2022-07-21 Time 15:48 Sent To  
Notes
2022-07-22 13:37:46BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: REVISION #22050030
 500 N. QUADRILLE BLVD.
 BUILDING PERMIT 30 STORY BLDG W/ TWO TOWERS
 CONSTRUCTION TYPE: 1A, SPRINKLERED
 MIXED OCCUPANCY: B, R-1, R-2, A-2, A4, S-2, M, E
  
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 FLORIDA BUILDING CODE,5TH EDITION (2014)
 FBC[AMENDED] = 2014 CHAPTER 1 WPB AMENDMENTS (SEE LINK
 BELOW)
 HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/
 BUILDING-PERMIT-FORMS
 FBC[B] = FBC BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
  
  
 BUILDING REVIEW COMMENTS:
  
 1) ON SHEETS A1.225 & A1.228 THE NOTE THAT REFERS TO
 ANOTHER SHEET FOR ADDITIONAL POOL INFORMATION DOES NOT
 SPECIFY THE SHEET NUMBER TO REFER TO. FBC 107.2.1
  
 2) ON SHEET A2.107 IT APPEARS THAT ONE OF THE LAYERS
 WAS NOT TURNED ON. THE RESTROOM FIXTURES, GYM EQUIPMENT
 AND FIXTURES IN THE UNITS ARE NOT SHOWN AS THEY WERE IN
 THE PREVIOUS VERSION OF THE DRAWING. FBC 107.2.1
  
 3) ON SHEET A2.225 THE DOORS AND SWINGS ARE NOT SHOWN
 BUT MAY IMPEDE TRAVEL IN THE CORRIDOR. FBC 1005.7.1
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 4) SEE FIRE REVIEW COMMENTS FOR DOOR SWINGS IN
 DIRECTION OF TRAVEL. 1010.1.2.1 DIRECTION OF SWING.
 PIVOT OR SIDE-HINGED SWINGING DOORS SHALL SWING IN THE
 DIRECTION OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA
 CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A
 GROUP H OCCUPANCY.
  
 5) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-10-17 Cont ID  
Sent By jleahy Date 2022-10-17 Time 08:17 Rev Time 0.00
Received By jleahy Date 2022-10-17 Time 07:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-06-30 Cont ID  
Sent By jleahy Date 2022-06-30 Time 07:54 Rev Time 0.00
Received By jleahy Date 2022-06-30 Time 07:02 Sent To  
Notes
2022-06-30 07:56:35FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 FIRE ALARM AND LOW VOLTAGE SYSTEMS PAGES TO BE
 SUBMITTED UNDER SEPARATE PERMITT REVISIONS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-09-19 Cont ID  
Sent By pleduc Date 2022-09-19 Time   Rev Time 0.00
Received By pleduc Date 2022-09-19 Time 13:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-06-10 Cont ID  
Sent By pleduc Date 2022-06-10 Time   Rev Time 0.00
Received By pleduc Date 2022-06-07 Time 12:39 Sent To  
Notes
2022-06-08 16:31:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF THE EXIT DOORS FROM THE
 AMENITY DECK SWINGING OUT AGAINST THE PATH OF EXIT
 TRAVEL
  
 PER NFPA 101 CH 12 & CH 7
  
 12.2.2.2 DOORS.
 12.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPAN CIES, AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT
  
  
  
 1A) THE DOOR HARDWARE OF THE EXIT DOORS FROM THE
 AMENNITY DECK SHALL COMPLY WITH NFPA 101 CH 12 & 7
  
 12.2.2.2.3 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA HAVING
 AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PRO VIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR LOCK IS PANIC HARDWARE OR
 FIRE EXIT HARDWARE COMPLYING WITH 7.2.1.7, UNLESS
 OTHERWISE PERMITTED
 BY ONE OF THE FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY TO DELAYED-EGRESS
 ELECTRICAL LOCK ING SYSTEMS AS PERMITTED IN 12.2.2.2.5.
 (2) THIS REQUIREMENT SHALL NOT APPLY TO SENSOR-RELEASE
 OF ELECTRICAL
 LOCKING SYSTEMS AS PERMITTED IN 12.2.2.2.6.
 12.2.2.2.4 LOCKING DEVICES COMPLYING WITH 7.2.1.5.5
 SHALL BE PERMITTED
 TO BE USED ON A SINGLE DOOR OR A SINGLE PAIR OF DOORS
 IF BOTH OF THE FOL LOWING CONDITIONS APPLY:
 (1) THE DOOR OR PAIR OF DOORS SERVE AS THE MAIN EXIT
 AND THE ASSEMBLY
 OCCUPANCY HAS AN OCCUPANT LOAD NOT GREATER THAN 500.
 (2) ANY LATCHING DEVICES ON SUCH A DOOR(S) FROM AN
 ASSEMBLY OCCU PANCY HAVING AN OCCUPANT LOAD OF 100 OR
 MORE ARE RELEASED BY
 PANIC HARDWARE OR FIRE EXIT HARDWARE
  
 7.2.1.7* PANIC HARDWARE AND FIRE EXIT HARDWARE
  
 7.2.1.7.1 WHERE A SIDE-HINGED OR PIVOTED-SWINGING DOOR
 ASSEMBLY IS
 REQUIRED TO BE EQUIPPED WITH PANIC OR FIRE EXIT
 HARDWARE, SUCH HARDWARE
 SHALL MEET ALL OF THE FOLLOWING CRITERIA:
 (1) IT SHALL CONSIST OF A CROSS BAR OR A PUSH PAD, WITH
 THE LENGTH OF THE
 ACTUATING PORTION OF THE CROSS BAR OR PUSH PAD NOT LESS
 THAN ONE-HALF
 OF THE WIDTH OF THE DOOR LEAF.
 (2) IT SHALL BE MOUNTED AS FOLLOWS:
 (A) NEW INSTALLATIONS SHALL BE NOT LESS THAN 34 IN.
 (865 MM), AND
 NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (B) EXISTING INSTALLATIONS SHALL BE NOT LESS THAN 30
 IN. (760 MM),
 AND NOT MORE THAN 48 IN. (1220 MM), ABOVE THE FLOOR.
 (3) IT SHALL BE CONSTRUCTED SO THAT A HORIZONTAL FORCE
 NOT TO EXCEED 15 LBF
 (66 N) ACTUATES THE CROSS BAR OR PUSH PAD AND LATCHES
  
 PLEASE REVIEW AND CORRECT
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2022-12-16 Cont ID  
Sent By rwbrown Date 2022-12-16 Time 09:21 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-12-27 Cont ID  
Sent By medwards Date 2022-12-27 Time 12:55 Rev Time 0.00
Received By medwards Date 2022-12-15 Time 07:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-12-05 Cont ID  
Sent By jgomez Date 2022-12-05 Time 15:23 Rev Time 0.00
Received By jgomez Date 2022-11-18 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-11-08 Cont ID  
Sent By aoliver Date 2022-11-08 Time 11:48 Rev Time 0.00
Received By aoliver Date 2022-09-09 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-08-29 Cont ID  
Sent By aoliver Date 2022-08-29 Time 07:18 Rev Time 0.00
Received By aoliver Date 2022-06-06 Time 10:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-12-27 Cont ID  
Sent By medwards Date 2022-12-27 Time 12:54 Rev Time 0.00
Received By medwards Date 2022-12-27 Time 12:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-12-01 Cont ID  
Sent By medwards Date 2022-12-01 Time 14:08 Rev Time 0.00
Received By medwards Date 2022-12-01 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-09-23 Cont ID  
Sent By medwards Date 2022-09-23 Time 10:42 Rev Time 0.00
Received By medwards Date 2022-09-23 Time 10:42 Sent To  
Notes
2022-09-23 10:42:312ND REVIEW FMC
 PERMIT: 22050030
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) IT IS UNCLEAR TO THIS REVIEWER BASED ON THE WORDING
 IN THE NARRATIVE, THE FOLLOWING IS THE NARRATIVE OF
 CHANGES ASOCIATED WITH THE ONE WEST PALM CCD #48
 CHANGES:
 NOTE: ITEMS IN RED HAVE BEEN UPDATED SINCE PREVIOUS
 SUBMISSIOM. AM I TO REVIEW ONLY THE ITEMS IN RED?
  
 2) PLEASE BE CLEAR AS TO THE SCOPE OF THE REVISION AND
 ONLY SEND RELEVANT DOCUMENTS. IF ONLY THE COMMENTS IN
 RED ARE TO BE REVIEWED IN THIS REVISION PLEASE REMOVE
 ALL THE OTHER COMMENTS. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-06-21 Cont ID  
Sent By medwards Date 2022-06-21 Time 08:47 Rev Time 0.00
Received By medwards Date 2022-06-21 Time 08:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-12-16 Cont ID  
Sent By rwbrown Date 2022-12-16 Time 09:14 Rev Time 0.00
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-09-26 Cont ID  
Sent By rwbrown Date 2022-09-26 Time 07:24 Rev Time 0.00
Received By rwbrown Date 2022-09-26 Time 07:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-09-26 Cont ID  
Sent By rwbrown Date 2022-06-07 Time 16:05 Rev Time  
Received By rwbrown Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-12-27 Cont ID  
Sent By medwards Date 2022-12-27 Time 12:54 Rev Time 0.00
Received By medwards Date 2022-12-27 Time 12:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2022-12-05 Cont ID  
Sent By jgomez Date 2022-12-05 Time 15:13 Rev Time 0.00
Received By jgomez Date 2022-12-05 Time 14:27 Sent To  
Notes
2022-12-05 15:13:58SIGNATURE REVIEW
  
 1- MECHANICAL DRAWINGS M.307B, M.M601, M603, M705 AND
 M.817 AND ALL PLUMBING DRAWINGS HAVE AN ENGINEER'S
 SELF-CERTIFIED DIGITAL SIGNATURE. ENGINEER CANNOT
 SELF-CERTIFY THE DIGITAL SIGNATURE. THIRD PARTY
 CERTIFICATION IS REQUIRED BY FAC 61G15-23.004. (NOTE:
 ENGINEER TO CONTACT THE BOARD OF ENGINEER'S FOR
 SELF-CERTIFIED DIGITAL SIGNATURE QUESTIONS).
 NOTE: PLEASE UPLOAD DRAWINGS TO PROJECTDOX WITH THIRD
 PARTY CERTIFIED DIGITAL SIGNATURE OR PROVIDE HARD COPY
 WITH ENGINEER'S WET SIGNATURE.
  
 ENGINEERS
 61G15-23.004 PROCEDURES FOR DIGITALLY SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2022-12-01 14:08:46MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-09-26 Cont ID  
Sent By rwbrown Date 2022-09-26 Time 07:37 Rev Time 0.00
Received By rwbrown Date 2022-09-26 Time 07:37 Sent To  
Notes
2022-09-26 07:56:56* PROFESSIONAL ENGINEERS- ALL ELECTRONIC SUBMISSIONS
 PREPARED BY AN ENGINEER MUST COMPLY WITH 61G15-23.001
 AND BE EITHER DIGITALLY SIGNED AND SEALED -OR-
 ELECTRONICALLY SIGNED AND SEALED, IN ACCORDANCE WITH
 61G15-23.004 AND 61G15-23.005 F.A.C. RESPECTIVELY.
 * ARCHITECTS- ALL ELECTRONIC SUBMISSIONS PREPARED BY AN
 ARCHITECT MUST COMPLY WITH 61G1-16.004 F.A.C. AND BE
 DIGITALLY SIGNED AND SEALED IN ACCORDANCE WITH
 61G1-16.005 F.A.C.
  
 PLUMBING AND MECHANICAL PAGES SIGNED BY CHAD WISLER ARE
 SELF CERTIFIED. THE BOARD OF PROFESSIONAL ENGINEERS
 REQUIRES THE DIGITAL SIGNATURES TO BE THIRD PARTY
 CERTIFIED.
2022-09-23 10:46:59MECHANICAL DESIGNER MUST HAVE THEIR DIGITAL SIGNATURE
 3RD PARTY VERIFIED, ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-07-21 Cont ID  
Sent By rmcdouga Date 2022-07-21 Time 15:48 Rev Time 0.00
Received By rmcdouga Date 2022-07-21 Time 15:48 Sent To  
Notes
2022-07-21 17:10:19THE LANDSCAPE PLANS ARE NOT DIGITALLY SIGNED BY THE
 LANDSCAPE ENGINEER. CHAD WISLER, THE ENGINEER THAT
 DIGITALLY SIGNED THE MECHANICAL AND PLUMBING SHEETS
 SELF-CERTIFIED HIS SIGNATURE. THE BOARD OF PROFESSIONAL
 ENGINEERS REQUIRES ENGINEERS TO USE AN APPROVED THIRD
 PARTY TO CERTIFY THEIR DIGITAL SIGNATURES.
 ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 &
 FAC 61G15
2022-06-30 07:59:04ELECTRICAL PAGES SIGNATURES ARE APPROVED.
  
 FIRE ALARM PAGES TO BE SUBMITTED UNDER FIRE ALARM
 PERMIT REVISION.
  
 LOW VOLTAGE SYSTEMS TO BE SUBMITTED UNDER LV PERMIT
 REVISION.
2022-06-21 08:53:39MECHANICAL ENGINEER WILL NEED TO HAVE HIS DIGITAL
 SIGNATURE THIRD PARTY VERIFIED. ME

Review Stop Z ZONING
Rev No 2 Status P Date 2022-11-07 Cont ID  
Sent By ckimmerl Date 2022-11-07 Time 12:13 Rev Time 0.00
Received By ckimmerl Date 2022-11-07 Time 12:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-08-26 Cont ID  
Sent By aaponte Date 2022-08-26 Time 16:14 Rev Time 0.00
Received By ckimmerl Date 2022-08-26 Time 16:09 Sent To  
Notes
2022-08-26 16:14:251. THE HARDSCAPE AND LANDSCAPE PLANS AS PART OF THIS
 PERMIT (L1-710) AND (L1-720) DO NOT MATCH THOSE OF THE
 APPROVED FORMAL SITE PLAN 15-06A FROM 12.1.20.
  
 - LANDSCAPE SPACES APPEAR TO HAVE CHANGED IN SIZE AND
 LOCATION.
 - PLEASE BE SURE PLANS MATCH WHAT WAS APPROVED.
  
 CHRIS KIMMERLY, AICP
 URBAN DESIGN PLANNER
 [email protected] 822.1426