| 2022-05-11 15:00:22 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THE APPLICATION STATES "REPAIRS TO EXISTING |
| | CONTRACTOR BATHROOM. |
| | |
| | THERE IS NO FLOOR PLAN SUBMITTED THAT INDICATES THE |
| | LOCATION OF THE BATHROOM OR IF THERE IS A UNIT #. |
| | |
| | PLEASE ALSO INDICATE WHAT FLOOR THE PROPOSED WORK IS |
| | ON. |
| | |
| | PER NFPA 1 |
| | |
| | 1.7.12 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.12.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.12.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4. |
| | |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE A FLOOR PLAN |
| | INDICATING THE LOCATION OF THE BATHROOM. AND A NOTE OF |
| | ACKNOWLEDGEMENT TO MAINTAIN THE FIRE RATING OF THE |
| | BATHROOM WALL IF APPLICABLE. |
| | |
| | |
| | 2) THE PLAN SHEET SUBMITTAL INDICATES "REMOVE AND |
| | REPLACE.....TILE FLOORING" |
| | |
| | TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT |
| | CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE |
| | VINYL/LAMINATE ETC AND IS MANUFACTURED FROM AROUND THE |
| | WORLD AND NOT ALL ARE TESTED AND MEETING LISTED AND |
| | NFPA STANDARDS. |
| | |
| | CERAMIC/PORCELAIN/MARBLE/CEMENT TILE DOES NOT REQUIRE A |
| | SPEC SHEET. |
| | |
| | PER NFPA 101, CH 30 |
| | |
| | 30.3.3.3 INTERIOR FLOOR FINISH. |
| | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| | ACCORDANCE WITH |
| | SECTION 10.2. |
| | |
| | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| | 10.2.2.2 |
| | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| | HAVE A |
| | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC |
| | TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED |
| | FINISHED FLOORING INDICATING THE FIRE BEHAVIOR RATING. |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |