| Plan Review Stops For Permit 22041590 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
P |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-08-08 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-08-08 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2022-08-08 14:08:50 | HALF ADDRESS READDREDDED FROM 239 1/2 E LAKEWOOD RD TO | | | 241 E LAKEWOOD RD |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-02 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-08-02 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-08-02 |
Time |
16:31 |
Sent To |
|
|
| Notes |
| 2022-08-02 16:32:38 | READ RESPONCE TO COMMENTS LETTER, HALF ADDRESS ISSUE | | | HAS NOT BEEN RESOLVED. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2022-07-07 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-07-07 |
Time |
07:53 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-07-07 |
Time |
07:53 |
Sent To |
|
|
| Notes |
| 2022-07-07 07:55:31 | WHICH BUILDING IS THE WORK TO BE DONE, NORTH OR SOUTH? | | | THE NORTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED | | | TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT | | | [email protected] OR CALL 561-805-6659 TO READDRESS | | | THE HALF ADDRESS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-08 |
Time |
17:02 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-08 |
Time |
16:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-06 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-06 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2022-07-06 15:27:43 | PLAN REVIEW BUILDING | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. WINDOW NOA 20-1223.05 IS FOR NON-IMPACT RATED | | | WINDOWS. (OPENING PROTECTION REQUIRED). PLANS SPECIFY | | | IMPACT RATED WINDOWS. PLEASE CLARIFY? | | | | | | PROVIDE THE FL PRODUCT APPROVALS OR MIAMI-DADE NOA FOR | | | THE PROPOSED WINDOWS. | | | FL PRODUCT APPROVALS SHALL INCLUDE THE COVER SHEETS, | | | EVALUATION REPORT AND INSTALLATIONS INSTRUCTIONS. | | | NOTE: NOA?S DO NOT HAVE COVER SHEETS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-07-29 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2022-07-29 |
Time |
19:37 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2022-07-29 |
Time |
19:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-05-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-05-20 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-05-20 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-22 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-22 |
Time |
11:38 |
Sent To |
|
|
| Notes |
| 2022-07-22 13:16:20 | SEPARATE PERMIT REQUIRED FOR GAS PIPING AND GAS | | | APPLIANCE INSTALLATIONS. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-04 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-04 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2022-05-04 13:53:47 | 1ST REVIEW FBC-2020 RES. FUEL GAS | | | PERMIT- 22041590 | | | 5/4/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-2: PROVIDE A GAS RISER DRAWING THAT INCLUDES | | | THE NEW PIPING TO THE RANGE AND THE EXISTING GAS PIPING | | | AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & | | | G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- | | | THE RISER SHALL INDICATE: | | | A) TYPE OF GAS- NATURAL OR LP. | | | B) DELIVERY PRESSURE AT THE METER. | | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | D) TYPES AND SIZES OF PIPING. | | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | | UNIONS. | | | H) OUTLET PRESSURES AT REGULATORS. | | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | K) PIPE SIZING TABLES. | | | | | | 2) A-2: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE | | | RANGE- SEC. G2447.1 FBC RES. | | | | | | 3) A-2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE | | | RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. | | | G2407.1 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-08 |
Time |
17:24 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-21 |
Time |
14:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-06 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-05-03 |
Time |
06:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2022-05-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-10 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-10 |
Time |
13:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-07-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-22 |
Time |
13:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-22 |
Time |
11:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-05-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-04 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-04 |
Time |
12:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-08-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-08-08 |
Time |
17:23 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-08-08 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2022-08-04 06:00:22 | ALL PAGES ARE NOT ELECTRONICALLY SIGNED/SEALED - PAGE | | | A2 NEEDS A SIGNATURE | | | | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-07-06 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-07-06 |
Time |
15:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-07-06 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2022-07-06 15:35:04 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 1ST REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | SUBMIT PLANS WITH A VALID DIGITAL SIGNATURE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | | | | |
|
|