| 2022-07-22 11:31:04 | |
| | 2ND REVIEW FBC-2020 RES. GAS |
| | PERMIT- 22041543 |
| | 7/21/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #1, 3, 4, |
| | 5, & 6 FROM THE 1ST REVIEW STILL EXIST AND ARE COPIED |
| | BELOW. |
| | PLEASE NOTE I HAVE RESEARCHED APPROVED PLANS FOR THE |
| | RESIDENCE UNDER PERMITS- 18050348, 19040921, & 2110973 |
| | AND THE SPECS REQUESTED IN MY COMMENTS ARE NOT IN THE |
| | FILES. FURTHER IT WAS NOTED UNDER MASTER PERMIT |
| | 18050348 THAT GAS APPLIANCES WERE TO BE INSTALLED UNDER |
| | SEPARATE PERMIT. THOSE SEPARATE PERMITS INCLUDE |
| | 19040921 AND 2110973 WHICH HAVE WATER HEATER SPECS, BUT |
| | NO OTHERS SPECS. ALSO PLEASE NOTE YOUR PREVIOUS RISER |
| | DRAWINGS INDICATE A 2-INCH MAIN PE GAS PIPE AND NOT AN |
| | 1-1/4 PE PIPE WHICH YOU SHOW ON THIS RISER AND WHICH IS |
| | QUESTIONED IN MY COMMENT #1. PLEASE COMPLY WITH THE |
| | COMMENTS. |
| | |
| | 1) GAS RISER: THE 1-1/4-INCH PE IS UNDERSIZED FOR THE |
| | NEW 2,216,000 BTU LOAD AT A TOTAL DEVELOPED LENGTH OF |
| | 225 FT.- TABLE 402.4(22) FBC FG. PLEASE SEE SEC. 402.3 |
| | FOR ALTERNATIVE PIPE SIZING METHODS IF APPLICABLE. |
| | |
| | 3) PROVIDE A PLAN THAT SHOWS THE ACTUAL PHYSICAL |
| | LOCATIONS OF THE APPLIANCES- SEC. 107.2.1 WPB. |
| | |
| | 4) SUBMIT MANUFACTURER' SPECIFICATIONS FOR THE RANGE, |
| | GRILL, AND FIREPLACE THAT SHOW THE BTU GAS LOADS, INPUT |
| | PRESSURES, AND LISTINGS OF THE APPLIANCES- SECS. |
| | G2447.1 & G2432- G2435 FBC RES. |
| | |
| | 5) FIREPLACE: A COMPLETE REVIEW OF THE GAS PLANS CANNOT |
| | BE ACCOMPLISHED AT THIS TIME BECAUSE OF A LACK OF |
| | INFORMATION FOR THE FIREPLACE INCLUDING REQUIRED |
| | COMBUSTION AIR AND VENTING REQUIREMENTS- SEC. 107.2.1 |
| | WPB. COMBUSTION AIR CALCULATIONS AND A VENTING DIAGRAM |
| | ARE REQUIRED. |
| | |
| | 6) GRILL: A COMPLETE REVIEW OF THE GAS PLANS CANNOT BE |
| | ACCOMPLISHED AT THIS TIME BECAUSE OF A LACK OF |
| | INFORMATION FOR THE GRILL INCLUDING REQUIRED CLEARANCES |
| | TO COMBUSTIBLE AND OVERHEAD CONSTRUCTION, COMBUSTION |
| | AIR AND VENTILATION, AND EXHAUST VENTING GUIDELINES. |
| | PLEASE NOTE THAT AN EXHAUST HOOD AND DUCT SYSTEM MAY BE |
| | REQUIRED- SEC. G2448.1 FBC RES. PROVIDE PLAN DETAILS |
| | THAT REFLECT THE INSTALL MANUAL RECOMMENDATIONS AND |
| | RESTRICTIONS. A) SHOW THE CLEARANCE DISTANCES FROM THE |
| | GRILL EXHAUST TO GRAVITY AND MECHANICAL AIR INTAKES |
| | INTO THE BUILDING- SEC. R303.5.1 FBC RES. MINIMUM 10 |
| | FT. CLEARANCES REQUIRED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |