| 2022-04-29 11:47:37 | JONATHAN BROOKS JR. |
| | BUILDING PLANS EXAMINER |
| | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| | PHONE (561) 805-6656 |
| | EMAIL: [email protected] |
| | |
| | 1ST REVIEW: FBC 2020 7TH EDITION |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| | CITY HALL, OR EMAIL [email protected]. |
| | |
| | 1. SUBMITTED PRODUCT APPROVAL FL2533-R26 HAS BEEN |
| | REVISED TO FL2533-R27. PLEASE PROVIDE A COMPLETE SET. |
| | INCLUDE COVER PAGE, EVALUATION REPORTS AND INSTALLATION |
| | INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| | AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| | PRODUCT APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. AS PER RULE 61G20-3. |
| | 2. SUBMITTED FLORIDA DBPR PRODUCT APPROVAL FL27499.1-R3 |
| | HAS BEEN REVISED TO FL27499.1-R4 IT COVERS MULTIPLE |
| | INSTALLATION OPTIONS TO MEET DESIGN UPLIFT PRESSURES. |
| | PLEASE SELECT CORRECT INSTALLATION OPTION FROM PAGE #2 |
| | OF THE EVALUATION REPORT THAT MEET OR EXCEED THE |
| | MINIMUM DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE |
| | CATEGORY C AREAS. (-108.17). ALL APPLICABLE DETAILS AND |
| | ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT |
| | APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT |
| | SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED |
| | SITE-SPECIFIC ENGINEERING. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| | |