Plan Review Details - Permit 22041477
Plan Review Stops For Permit 22041477
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By jwitmer Date 2022-05-25 Time 12:55 Rev Time 0.00
Received By jwitmer Date 2022-05-25 Time 10:35 Sent To  
Notes
2022-05-25 12:55:21TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR?S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-25 Cont ID  
Sent By jwitmer Date 2022-05-25 Time 12:59 Rev Time 0.00
Received By jwitmer Date 2022-05-25 Time 10:36 Sent To  
Notes
2022-05-25 12:59:30WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22041477
 ADD: 3800 WASHINGTON RD # 812 / BUILT IN 1971
 CONT: INGECO CONTRACTORS LLC
 TEL: 561-601-2379
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 25TH/ 2022
 ACTION: DENIED
  
 1) SHEET D-101 THE DEMO FLOOR PLAN. STATES TO REMOVE
 FINISHES THROUGHOUT THE UNIT. SHEETA-101 NOTE # 10
 STATES A SOUND PROOFING MEMBRANE OF 72 OR GREATER SHALL
 BE USED, PROFLEX MEGA SOUND CONTROL MEMBRANE OR
 APPROVED EQUAL. PLEASE NOTE TO DATE WE HAVE NOT
 RECEIVED ACTUAL TEST REPORTS FOR PROFLEX MEGA SOUND
 CONTROL ON A 6 INCH CONCRETE SLAB, NO DROP CEILING!!!!
 THE FLOOR PLAN DOES NOT INDICATE WHAT THE FLOOR
 FINISHES ARE? POSSIBLY MORE THAN ONE FLOOR FINISH?
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 1D) LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253.
 2) SHEET A-101 SHOWS 6 OPENINGS WINDOWS AND DOORS TO BE
 REPLACED BUT THERE IS NO WIND DESIGN CRITERIA IN THIS
 PERMIT PACKAGE. 2020 FBC-B 1603.1.4 WIND DESIGN
 CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 2.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2.2. RISK CATEGORY.
  
 2.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 2.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 2.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 2.6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 2.7) 2020 FBC-B 1709.5.1 HABITAT SPACES, WATER
 INTRUSION. EXTERIOR DOORS AND WINDOWS. EXCEPTION # 2.
 SILL LIMITING FACTOR.
  
 3) 2020 FBC-BUILDING 1609.4.3. EXPOSURE CATEGORIES,
 EXPOSURE D. EXPOSURE D SHALL APPLY WHERE THE GROUND
 SURFACE ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D,
 PREVAILS IN THE UPWARD DIRECTION FOR A DISTANCE OF AT
 LEAST 5,000 FEET OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C , AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET OR 20 TIMES THE BUILDING HEIGHT,
 WHICHEVER IS GREATER, FROM AN EXPOSURE D CONDITION AS
 DEFINED IN THE PREVIOUS SENTENCE.
  
 4) BUILDING END ZONES (5). THE FLOOR PLAN LAYOUT
 INDICATES THE WORK TO BE PERFORMED UNDER THIS PERMIT IS
 A CORNER UNIT OF A HIGHRISE BUILDING. THE WIND LOAD
 CHART UNDER NOTES STATES WHAT IS CONSIDERED AN END ZONE
 10% OF THE LEAST HORIZONTAL DISTANCE OF THE BUILDING OR
 40% OF THE MRH, BUT NOT LESS THAN 4% OF THE LEAST
 HORIZONTAL DISTANCE OR 3 FT. THE CONTRACTOR HAS NOT
 IDENTIFIED WHAT THE LEAST HORIZONTAL DISTANCE IS FOR
 THE BUILDING NOR THE LOCATION OF THE UNIT IN
 RELATIONSHIP TO THE BUILDING AND THE INTERCOASTAL
 WATERWAY. EXAMPLE ONLY. IF THE BUILDING HEIGHT IS
 APPROXIMATELY 180 FT. (MRH.) X 0.40= 72 FEET. THIS
 WOULD PUT ALL OPENINGS IN WIND ZONE 5 OR 10% OF THE
 LEAST HORIZONTAL DISTANCE OF THE BUILDING, ALSO
 UNKNOWN.
  
 5) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, MULLIONS & ROOF HATCHES.
 (B) WINDOWS & MULLIONS
  
  
 6) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
  
 7) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY IN THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, SILL HEIGTH, TYPE
 OF GLAZING, MULLION SIZE, LENGTH IF UNREINFORCED OR
 REINFORCED INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2020 FBC-B
 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL BE
 INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S
 INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE
 PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED
 BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS.
  
 8) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By jleahy Date 2022-06-03 Time 15:04 Rev Time 0.00
Received By jleahy Date 2022-06-03 Time 13:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-20 Cont ID  
Sent By   Date 2022-05-20 Time   Rev Time 0.00
Received By bdolan Date 2022-05-20 Time 10:49 Sent To  
Notes
2022-05-20 10:53:07ANY REMOVAL AND/OR CONSTRUCTION OF THE CEILING/WALL
 AREAS MAY REQUIRE AN EVALUATION OR MODIFICATION OF THE
 FIRE SPRINKLER AND FIRE ALARM SYSTEMS (IF PRESENT) FOR
 CODE COVERAGE AND COMPLIANCE BY CERTIFIED CONTRACTORS.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-03 Cont ID  
Sent By jleahy Date 2022-06-03 Time 15:05 Rev Time 0.00
Received By jleahy Date 2022-05-19 Time 06:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2022-05-24 Cont ID  
Sent By medwards Date 2022-05-24 Time 13:18 Rev Time 0.00
Received By medwards Date 2022-05-24 Time 13:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-20 Cont ID  
Sent By jesmith Date 2022-05-20 Time 12:32 Rev Time 0.00
Received By jesmith Date 2022-05-20 Time 11:36 Sent To  
Notes
2022-05-20 12:30:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22041477 3800 WASHINGTON RD 812
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 PLUMBING
  
 1. PER WPB FBC 107.2.1, PROVIDE A CROSS-SECTION SHOWER
 WALL/FLOOR/DRAIN AND THRESHOLD DETAIL SHOWING
 COMPLIANCE WITH FBC PL 421.5.2 AS FOLLOWS:
 ***A) LINERS SHALL TURN UP ON ALL SIDES NOT LESS THAN 2
 INCHES ABOVE THE FINISHED THRESHOLD LEVEL
 ***B) LINERS SHALL BE RECESSED AND FASTENED TO AN
 APPROVED BACKING
 ***C) LINERS SHALL NOT BE NAILED OR PERFORATED AT ANY
 POINT LESS THAN 1 INCH ABOVE THE FINISHED THRESHOLD
 ***D) LINERS SHALL BE PITCHED ONE-FOURTH UNIT VERTICAL
 IN 12 UNITS HORIZONTAL (2-PERCENT SLOPE) AND SHALL BE
 SLOPED TOWARD THE FIXTURE DRAIN
 ***E) LINERS SHALL BE SECURELY FASTENED TO THE WASTE
 OUTLET AT THE SEEPAGE ENTRANCE, MAKING A WATER-TIGHT
 JOINT BETWEEN THE LINER AND THE OUTLET
 ***F) FLOORS OR RECEPTORS UNDER SHOWER COMPARTMENTS
 SHALL BE LAID ON, AND SUPPORTED BY, A SMOOTH AND
 STRUCTURALLY SOUND BASE.
  
 2. PER WPB FBC 107.2.1,SPECIFY LINER MATERIAL COMPLYING
 WITH ONE OF THE FOLLOWING FBC PL SECTIONS-421.5.2.1,
 421.5.2.2, 421.5.2.3, 421.5.2.4, 421.5.2.5 OR
 421.5.2.6. NOTE THAT FBC PL 421.5.2.1 PLASTICIZED
 POLYVINYL CHLORIDE (PVC) SHEETS MEETING THE
 REQUIREMENTS OF ASTM D4551 IS A COMMON LINER USED AND
 IS APPROVED.
  
 3. FBC PL 421.4.1: WALLS IN SHOWER COMPARTMENTS SHALL
 BE CONSTRUCTED OF SMOOTH, CORROSION-RESISTANT AND
 NONABSORBENT WATERPROOF MATERIALS NOT LESS THAN 6 FEET
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 ABOVE THE DRAIN OF THE SHOWER. PER WPB FBC 107.2.1,
 PROVIDE A NOTE STATING THE SAME.
  
 4. FBC PL 421.4.1 AND 421.5: FLOOR SURFACES SHALL BE
 CONSTRUCTED OF IMPERVIOUS, NONCORROSIVE, NONABSORBENT
 AND WATERPROOF MATERIALS. PER WPB FBC 107.2.1, PROVIDE
 A NOTE STATING THE SAME.
  
 5. THE REPLACEMENT OF THE BATHTUB WITH A SHOWER AND THE
 REPLACEMENT OF THE SHOWER WITH A BATHTUB REQUIRES NEW
 FLOOR PENETRATIONS. PER WPB FBC 107.2.1, PROVIDE
 APPLICABLE RATED FLOOR DETAILS FOR PLUMBING
 PENETRATIONS COMPLYING WITH THE REQUIREMENTS OF FBC
 CHAPTER 7.
  
 6. PER WPB FBC 107.2.1, PROVIDE DETAIL OF WATER HEATER
 SHOWING HEATER W/STORAGE CAPACITY, PIPING INCLUDING CW,
 HW, VALVES (INCLUDING VACUUM RELIEF VALVE IF APPLICABLE
 FBC PL 504.2) , THERMAL EXPANSION CONTROL DEVICE
 (INCLUDING SIZE), T&P DISCHARGE (INCLUDING TERMINATION)
 AND WATER HEATER PAN AND DRAIN (INCLUDING TERMINATION)
 PER WPB FPC 107.2.1; COMPLY WITH FBC PL 607.3, 503.1,
 504.1, 504.4, 504.4.1, 504.5, 504.6, 504.7, 504.7.1 AND
 504.7.2.
 PLEASE NOTE; PER FBC PL 504.7.2, WHERE A PAN DRAIN WAS
 NOT PREVIOUSLY INSTALLED, A PAN DRAIN SHALL NOT BE
 REQUIRED FOR A REPLACEMENT WATER HEATER INSTALLATION.
 IF THIS IS THE CASE, PER WPB FBC 107.2.1, PLEASE NOTE
 ON DETAIL.
  
 7.PER WPB FBC 107.2.1 AND FBC PL 409.4, PROVIDE NOTE
 STATING "THE WASTE CONNECTION OF A RESIDENTIAL
 DISHWASHER SHALL CONNECT DIRECTLY TO A WYE BRANCH
 FITTING ON THE TAILPIECE OF THE KITCHEN SINK, DIRECTLY
 TO THE DISHWASHER CONNECTION OF A FOOD WASTE DISPOSER,
 OR THROUGH AN AIR BREAK TO A STANDPIPE. THE WASTE LINE
 OF A RESIDENTIAL DISHWASHER SHALL RISE AND BE SECURELY
 FASTENED TO THE UNDERSIDE OF THE SINK RIM OR
 COUNTERTOP."
  
 8. PER WPB FBC 107.2.1 AND FBC PL 412.3, PROVIDE NOTE
 STATING "INDIVIDUAL SHOWER AND TUB-SHOWER COMBINATION
 VALVES SHALL BE BALANCED-PRESSURE, THERMOSTATIC OR
 COMBINATION BALANCED-PRESSURE/THERMOSTATIC VALVES THAT
 CONFORM TO THE REQUIREMENTS OF ASSE 1016/ASME
 A112.1016/CSA B125.16 OR ASME A112.18.1/CSA B125.1 AND
 SHALL BE INSTALLED AT THE POINT OF USE. SHOWER AND
 TUB-SHOWER COMBINATION VALVES SHALL BE EQUIPPED WITH A
 MEANS TO LIMIT THE MAXIMUM SETTING OF THE VALVE TO 120
 DEGREES F, WHICH SHALL BE FIELD ADJUSTED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTRUCTIONS."
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-06-03 Cont ID  
Sent By jleahy Date 2022-06-03 Time 15:10 Rev Time 0.00
Received By jleahy Date 2022-06-03 Time 15:10 Sent To  
Notes
2022-05-25 10:49:26ARCITECTURAL SHEETS ARE OK, ARCHITECTS CAN SELF
 CERTIFY. JW 5/25/2022
2022-05-24 13:19:17MECHANICAL DIGITAL SIGNATURES APPROVED ME
  
2022-05-20 11:41:14SIGNATURES FOR PLUMBING ARE VALID. JS