| Plan Review Stops For Permit 22041417 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2022-04-27 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-04-27 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-04-27 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2022-04-27 13:08:47 | OWNER UPDATE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-29 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-29 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2022-09-29 16:43:01 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | ADDITIONAL PERMITS ARE REQUIRED FOR DEMOLITION AND FOR | | | SITE-WALL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-14 |
Time |
07:49 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-14 |
Time |
07:49 |
Sent To |
|
|
| Notes |
| 2022-09-14 07:51:22 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | ADDITIONAL PERMITS ARE REQUIRED FOR DEMOLITION AND | | | SITE-WALL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-08-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-05 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-04 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2022-08-05 10:34:31 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | ADDITIONAL PERMITS ARE REQUIRED FOR SITEWALL AND FOR | | | DEMOLITION. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-06-11 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-06-11 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-06-09 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2022-06-11 11:51:02 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC R 806.5, PLEASE PROVIDE SPECIFIC DETAILS FOR | | | THE UNVENTED AIR SPACES, AS IT APPEARS THAT ICENYNE IS | | | TO BE USED FOR THE UNDERSIDE OF ROOF SHEATHING | | | INSULATION. PER CODE SECTION FBC R 806.5 THERE ARE | | | SEVERAL OPTIONS TO BE USED DEPENDING ON ALL OF THE | | | PROPOSED AND EXISTING VARIABLES INCLUDING THE AIR | | | PERMIABILITY OF THE INSULATION. | | | 2.) FBC B 107.2.1, PLEASE PROVIDE A DRAINAGE PLAN FOR | | | THE SITE. | | | 3.) FBC B 107.2.1, PROVIDE CONFIRMATION OF A SITE WALL | | | PERMIT. | | | 4.) FBC B 107.2.1, PROVIDE DETAILS FOR A STORM WATER | | | PREVENTION PLAN DURING CONSTRUCTION. | | | 5.) FBC B 107.2.1, PROVIDE CONFIRMATION IF ONE OF THE | | | APPROVED ROLL OFF/FRANCHISE HAULERS WILL BE USED FOR | | | REMOVAL OF DEBRIS. | | | 6.) FBC B 107.2.1, IT APPEARS THAT THERE IS AN EXISTING | | | ONE STORY BUILDING AND EXTERIOR SECTIONS OF OTHER | | | STRUCTURES THAT ARE TO BE DEMILISHED. IF THIS IS | | | ACCURATE, PROVIDE CONFIRMATION OF A DEMO PERMIT. | | | 7.) FBC R 311 & R 312, PROVIDE LOCATION AND DETAILS FOR | | | HANDRAILS AND GUARDS ON PLAN SHEETS. | | | 8.) FBC B 107.3.4.1, PLEASE LIST ALL OF THE PROPOSED | | | DEFERRED SUBMITTALS(PRODUCT APPROVALS & SHOP DRAWINGS) | | | ON PLAN SHEETS. PLEASE INCLUDE: HANDRAILS, & PERGOLA. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-05-17 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-05-17 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-17 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-04 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-04 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-26 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-26 |
Time |
08:19 |
Sent To |
|
|
| Notes |
| 2022-09-26 08:22:02 | 4TH GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2020 FRC G2415.8.1 - THE CONDUIT FOR THE GAS SLEEVE | | | TO THE FIREPLACE MUST TERMINATE IN AN "OCCUPIABLE | | | PORTION" OF THE BUILDING. BEHIND AN ACCESS PANEL IS NOT | | | "OCCUPIABLE". CONSIDER USING ANOTHER PORTION OF THE | | | BUILDING FOR THE SLEEVE TO ENTER THE STRUCTURE AND THEN | | | CONTINUING OVERHEAD FOR THE REMAINDER OF THE RUN. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-01 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-01 |
Time |
07:50 |
Sent To |
|
|
| Notes |
| 2022-09-01 13:02:34 | 3RD REVIEW FBC-2020 RES. GAS | | | PERMIT- 22041417 | | | 9/1/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-1 & P-4: THE TRACPIPE CSST PS-II | | | PRE-SLEEVED GAS PIPING IS APPROVED FOR | | | UNDERGOUND/UNDERSLAB INSTALLATION, HOWEVER THE SLEEVED | | | PIPE AND VENT PORT SHALL TERMINATE IN OCCUPIABLE | | | PORTIONS OF THE BUILDING PER SEC. G2415.8.1 FBC RES | | | (404.14.1 FBC FG). THE SLEEVE SHALL EXTEND A MINIMUM OF | | | 2-INCHES INTO THE SPACE. THE RESUBMITTED PLAN APPEARS | | | TO SHOW THE TERMINATIONS INSIDE THE WALLS ADJACENT TO | | | THE FIREPLACE AND THE RANGE. | | | | | | A) PLEASE NOTE THAT THE AC CLOSET ADJACENT TO THE | | | FIREPLACE CANNOT BE THE OCCUPIABLE SPACE FOR | | | TERMINATION BECAUSE IT IS A PLENUM CLOSET- SEC. G2415.3 | | | FBC RES (404.3 FBC FG). | | | | | | B) CONCERNING THE RANGE, THE SLEEVED TRACPIPE SHALL | | | TERMINATE MINIMUM 2-INCHES ABOVE THE FLOOR BEHIND THE | | | RANGE OR IN AN ADJACENT CABINET. PLEASE NOTE A FLEXIBLE | | | CONNECTOR IS REQUIRED FOR THE RANGE. | | | | | | 2) M-1: IN RESPONSE TO COMMENT #8 FROM THE 1ST GAS | | | REVIEW, THE ENGINEER IS SPECIFYING A TYPE B FLUE VENT | | | SYSTEM WHICH IS NOT APPROVED FOR USE BY THE | | | MANUFACTURER- SEC. G2427.2.1 FBC RES. PLEASE SEE PAGE | | | 21 OF THE CRAVE 4836 HEATILATOR INSTALLATION MANUAL FOR | | | APPROVED FLUE VENT- HEARTH & HOME TECHNOLOGIES DVP | | | VENTING SYSTEMS. PLEASE NOTE B VENTS ARE TYPICALLY USED | | | FOR NATURAL DRAFT APPLIANCES- SEE TABLE G2427.4 FBC | | | RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-07-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-14 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-14 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2022-07-14 11:28:10 | | | | 2ND REVIEW FBC-2020 RES. GAS | | | PERMIT- 22041417 | | | 7/14/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. THERE WERE NO CORRECTIONS | | | TO THE PLANS OR RESPONSES PROVIDED TO ADDRESS THE 1ST | | | REVIEW COMMENTS PRINTED BELOW. PLEASE COMPLY WITH THE | | | COMMENTS. PLEASE NOTE THAT GAS CAN BE UNDER A SEPARATE | | | PERMIT IF REQUESTED. | | | | | | 1) SHEETS P1 & P4: NOTE 9 ON P1 INDICATES A 2 PSI | | | REGULATOR, THE RISER ON P4 SHOWS A 0.5 PSI REGULATOR- | | | WHICH IS IT? | | | | | | 2) P1 & P4: PIPING TO THE GAS DRYER NOT SHOWN- SEC. | | | G413.1 FBC RES. | | | | | | 3) P1, P2, P4: REFER TO SECS. G2411.1 & G2411.2- | | | G2411.3 AND PROVIDE ELECTRICAL BONDING DETAILS AND | | | NOTES FOR THE METALLIC AND CSST PIPING. | | | | | | 4) P1 & P3: PER NOTE #18 PLEASE REFER TO SEC. G2415.14 | | | AND INDICATE THE TYPE AND SIZE OF FACTORY SLEEVE AND | | | SUBMIT SPECIFICATIONS FOR THE SLEEVE TO VERIFY LISTING | | | COMPLIANCE. PLEASE NOTE THAT COMPLETE INSTALLATION | | | GUIDELINES FOR THE CSST PIPING SHALL BE SUBMITTED FOR | | | REVIEW, OR CAN BE A DEFERRED SUBMITTAL- SEC. G2425.5.4 | | | FBC RES AND 107.3.4.1 WPB. | | | | | | 5) P1 & P3: PER NOTE #18 PROVIDE A VENT PORT DETAIL FOR | | | THE CSST SLEEVES AND INDICATE HOW THE SLEEVES WILL BE | | | SEALED AT THE TERMINATION LOCATIONS INSIDE THE | | | BUILDING- SEC. G2415.8.1 FBC RES. | | | | | | 6) P1 & P3: PROVIDE TANKLESS WATER HEATER CONDENSATE | | | DISPOSAL PLANS INCLUDING INSTALLATION OF THE | | | MANUFACTURER'S RECOMMENDED NEUTRALIZING DEVICE PER SEC. | | | G2408.1 FBC RES. INCLUDE THE SPECS FOR THE DEVICES IN | | | THE EQUIPMENT SCHEDULE AND MODIFY THE DRAWINGS TO SHOW | | | TYPE AND SIZE OF PIPING, PIPING RUN AND DISCHARGE | | | LOCATIONS- SECS. 307.2-307.3 FBC FG. | | | | | | 7) P1 & P3: SHOW THE REQUIRED INSTALLATION CLEARANCES | | | FOR THE GAS WATER HEATERS- SECS. G2427.1 & G2448.1 FBC | | | RES. | | | | | | 7) P1 & P4 GAS RANGE: SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE NEW RANGE THAT SHOW THE BTU GAS | | | LOAD, INPUT PRESSURE, AND LISTING OF THE APPLIANCE- | | | SEC. G2447.1 FBC RES. A) PROVIDE COMBUSTION AIR | | | CALCULATIONS FOR THE RANGE- SEC. G2407.1 FBC RES. | | | | | | 8) P1 & P4 GAS FIREPLACE: PROVIDE A DIRECT VENTING | | | DIAGRAM SHOWING THE TYPES AND SIZES OF AIR INLET AND | | | EXHAUST VENT DUCTS, DUCT RUNS AND TERMINATION | | | LOCATIONS- SEC. SUBMIT SPECS FOR THE VENT DUCTS- | | | G2427.2.1 & G2427.8 ITEM #3 FBC RES. | | | | | | 9) P1 & P4 BBQ: SUBMIT COMPLETE SPECIFICATIONS AND | | | INSTALLATION MANUAL FOR THE BBQ GRILL- G2448.1 FBC RES. | | | THE SPECS SHALL SHOW THE BTU LOAD, GAS INPUT PRESSURE, | | | CLEARANCES TO COMBUSTIBLE AND OVERHEAD CONSTRUCTION, | | | COMBUSTION AIR AND VENTILATION, AND EXHAUST VENTING | | | GUIDELINES. PLEASE NOTE THAT AN EXHAUST HOOD AND DUCT | | | SYSTEM MAY BE REQUIRED- SEC. G2448.1 FBC RES. PROVIDE | | | PLAN DETAILS THAT REFLECT THE INSTALL MANUAL | | | RECOMMENDATIONS AND RESTRICTIONS. A) SHOW THE CLEARANCE | | | DISTANCES FROM THE GRILL EXHAUST TO GRAVITY AND | | | MECHANICAL AIR INTAKES INTO THE BUILDING- SEC. R303.5.1 | | | FBC RES. MINIMUM 10 FT. CLEARANCES REQUIRED. | | | | | | 10) P1 &P4 GAS DRYER: THE GAS DRYER SUBMITTAL IS | | | INCOMPLETE. PROVIDE COMPLETE SPECIFICATIONS AND | | | INSTALLATION GUIDELINES- G2438.1 FBC RES. THE SPECS | | | SHALL SHOW THE BTU LOAD, INPUT PRESSURE AND SHOW | | | GUIDELINES FOR COMBUSTION AIR, MAKEUP, AND EXHAUST | | | VENTING. PROVIDE DETAILS ON THE PLAN IN ACCORDANCE WITH | | | THE SPECS AND SEC. G2439.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-05-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-06 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-06 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2022-05-06 11:07:18 | | | | 1ST REVIEW FBC-2020 RES. GAS | | | PERMIT- 22041417 | | | 5/6/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P1 & P4: NOTE 9 ON P1 INDICATES A 2 PSI | | | REGULATOR, THE RISER ON P4 SHOWS A 0.5 PSI REGULATOR- | | | WHICH IS IT? | | | | | | 2) P1 & P4: PIPING TO THE GAS DRYER NOT SHOWN- SEC. | | | G413.1 FBC RES. | | | | | | 3) P1, P2, P4: REFER TO SECS. G2411.1 & G2411.2- | | | G2411.3 AND PROVIDE ELECTRICAL BONDING DETAILS AND | | | NOTES FOR THE METALLIC AND CSST PIPING. | | | | | | 4) P1 & P3: PER NOTE #18 PLEASE REFER TO SEC. G2415.14 | | | AND INDICATE THE TYPE AND SIZE OF FACTORY SLEEVE AND | | | SUBMIT SPECIFICATIONS FOR THE SLEEVE TO VERIFY LISTING | | | COMPLIANCE. PLEASE NOTE THAT COMPLETE INSTALLATION | | | GUIDELINES FOR THE CSST PIPING SHALL BE SUBMITTED FOR | | | REVIEW, OR CAN BE A DEFERRED SUBMITTAL- SEC. G2425.5.4 | | | FBC RES AND 107.3.4.1 WPB. | | | | | | 5) P1 & P3: PER NOTE #18 PROVIDE A VENT PORT DETAIL FOR | | | THE CSST SLEEVES AND INDICATE HOW THE SLEEVES WILL BE | | | SEALED AT THE TERMINATION LOCATIONS INSIDE THE | | | BUILDING- SEC. G2415.8.1 FBC RES. | | | | | | 6) P1 & P3: PROVIDE TANKLESS WATER HEATER CONDENSATE | | | DISPOSAL PLANS INCLUDING INSTALLATION OF THE | | | MANUFACTURER'S RECOMMENDED NEUTRALIZING DEVICE PER SEC. | | | G2408.1 FBC RES. INCLUDE THE SPECS FOR THE DEVICES IN | | | THE EQUIPMENT SCHEDULE AND MODIFY THE DRAWINGS TO SHOW | | | TYPE AND SIZE OF PIPING, PIPING RUN AND DISCHARGE | | | LOCATIONS- SECS. 307.2-307.3 FBC FG. | | | | | | 7) P1 & P3: SHOW THE REQUIRED INSTALLATION CLEARANCES | | | FOR THE GAS WATER HEATERS- SECS. G2427.1 & G2448.1 FBC | | | RES. | | | | | | 7) P1 & P4 GAS RANGE: SUBMIT MANUFACTURER'S | | | SPECIFICATIONS FOR THE NEW RANGE THAT SHOW THE BTU GAS | | | LOAD, INPUT PRESSURE, AND LISTING OF THE APPLIANCE- | | | SEC. G2447.1 FBC RES. A) PROVIDE COMBUSTION AIR | | | CALCULATIONS FOR THE RANGE- SEC. G2407.1 FBC RES. | | | | | | 8) P1 & P4 GAS FIREPLACE: PROVIDE A DIRECT VENTING | | | DIAGRAM SHOWING THE TYPES AND SIZES OF AIR INLET AND | | | EXHAUST VENT DUCTS, DUCT RUNS AND TERMINATION | | | LOCATIONS- SEC. SUBMIT SPECS FOR THE VENT DUCTS- | | | G2427.2.1 & G2427.8 ITEM #3 FBC RES. | | | | | | 9) P1 & P4 BBQ: SUBMIT COMPLETE SPECIFICATIONS AND | | | INSTALLATION MANUAL FOR THE BBQ GRILL- G2448.1 FBC RES. | | | THE SPECS SHALL SHOW THE BTU LOAD, GAS INPUT PRESSURE, | | | CLEARANCES TO COMBUSTIBLE AND OVERHEAD CONSTRUCTION, | | | COMBUSTION AIR AND VENTILATION, AND EXHAUST VENTING | | | GUIDELINES. PLEASE NOTE THAT AN EXHAUST HOOD AND DUCT | | | SYSTEM MAY BE REQUIRED- SEC. G2448.1 FBC RES. PROVIDE | | | PLAN DETAILS THAT REFLECT THE INSTALL MANUAL | | | RECOMMENDATIONS AND RESTRICTIONS. A) SHOW THE CLEARANCE | | | DISTANCES FROM THE GRILL EXHAUST TO GRAVITY AND | | | MECHANICAL AIR INTAKES INTO THE BUILDING- SEC. R303.5.1 | | | FBC RES. MINIMUM 10 FT. CLEARANCES REQUIRED. | | | | | | 10) P1 &P4 GAS DRYER: THE GAS DRYER SUBMITTAL IS | | | INCOMPLETE. PROVIDE COMPLETE SPECIFICATIONS AND | | | INSTALLATION GUIDELINES- G2438.1 FBC RES. THE SPECS | | | SHALL SHOW THE BTU LOAD, INPUT PRESSURE AND SHOW | | | GUIDELINES FOR COMBUSTION AIR, MAKEUP, AND EXHAUST | | | VENTING. PROVIDE DETAILS ON THE PLAN IN ACCORDANCE WITH | | | THE SPECS AND SEC. G2439.1. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-06-01 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-06-01 |
Time |
12:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-10-04 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-03 |
Time |
16:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-29 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-23 |
Time |
09:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-09-14 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-09-14 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-08-31 |
Time |
09:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-08-16 |
|
|
Cont ID |
|
| Sent By |
aoliver |
Date |
2022-08-16 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-07-13 |
Time |
06:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-06-11 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-06-11 |
Time |
12:50 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-05-05 |
Time |
07:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-04 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-10-03 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2022-10-04 08:29:54 | RECEIPT MU-2022-042088 - $546.52 PAID | | 2022-10-03 16:08:09 | 10/3/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2022-06-11 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-06-11 |
Time |
12:18 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-06-11 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2022-06-11 12:20:42 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | IMPACT FEES - DIGITAL SUBMITTALS | | | | | | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON | | | APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO | | | YOUR PROJECT OR EMAIL IT TO [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-01 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-01 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-07-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-14 |
Time |
08:05 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-14 |
Time |
08:05 |
Sent To |
|
|
| Notes |
| 2022-07-14 08:05:46 | 2ND REVIEW FMC | | | PERMIT: 22041417 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENERGY CALCULATIONS SUBMITTED THIS CYCLE SHOWS | | | ON PAGE 2 THAT THERE ARE 3 AHU?S FOR THE HOUSE AND THE | | | COTTAGE. AHU-1 IS FOR 1166 SQUARE FEET AND CONDITIONS | | | THE LIVING-DINING. AHU-2 IS FOR 1102 SQUARE FEET AND | | | CONDITIONS THE MASTER-KITCHEN. AHU-3 IS FOR 300 SQUARE | | | FEET AND CONDITIONS THE COTTAGE. NOTHING ON PAGE 2 OF | | | THE ENERGY CALCULATIONS INDICATES THE GARAGE AS BEING | | | CONDITIONED. THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS SPECIFIES 5 UNITS FOR THE PROJECT WHICH | | | INCLUDES THE HOUSE, GARAGE AND CABANA. THE AHU?S LISTED | | | ON THE EQUIPMENT SIZING CALCULATIONS ARE- AHU-1, AHU-2, | | | AHU-3, AHU-4 AND AHU-5. SHEET M-1 AND M-2 LISTS AHU-1A, | | | AHU-B, AHU-2A, AHU-2B AND AHU-3 | | | PLEASE PROVIDE DOCUMENTS THAT ARE CONSISTENT WITH EACH | | | OTHER. PLEASE ALSO PROVIDE AN ENERGY CALCULATIONS THAT | | | SHOWS THE MECHANICAL SYSTEMS CONSISTENT WITH THE | | | MECHANICAL SIZING CALCULATIONS AND THE MECHANICAL | | | DRAWINGS. | | | | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-09 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-09 |
Time |
16:58 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-09 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2022-05-09 16:58:53 | 1ST REVIEW FMC | | | PERMIT: 22041417 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THERE ARE 2 ENERGY CALCULATIONS SUBMITTED PLEASE | | | REMOVE ONE SO THAT WE ONLY HAVE ONE. YOU CAN EMAIL THE | | | PERMIT LIBRARIAN AND ASK THEM TO LOCK THE ONE THAT | | | WOULD NOT APPLY. FBC 107 | | | | | | 2) PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING | | | CALCULATIONS. FEC R403.7.1 | | | | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-04 |
Time |
10:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-04 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-09-26 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-26 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-09-01 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-09-01 |
Time |
07:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-07-14 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-14 |
Time |
11:29 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-14 |
Time |
10:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-05-06 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-06 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-06 |
Time |
06:52 |
Sent To |
|
|
| Notes |
| 2022-05-06 09:10:39 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22041417 | | | 5/6/2022 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P1- P4: A SEPARATE PERMIT IS REQUIRED FOR THE | | | PROPOSED BATH/CABANA SEC. 107.2.1 WPB. | | | | | | 2) P1- P4: TWO DWELLING UNITS ON THE SAME LOT | | | (MULTI-FAMILY) REQUIRES INSTALLATION OF AN RPZ BACKFLOW | | | PREVENTER IN ACCORDANCE WITH SECTION E. TABLE 1.1 WPB | | | UTILITIES CROSS-CONNECTION MANUAL. THE PROPOSED POOL | | | AND IRRIGATION SYSTEM EACH UNDER SEPARATE PERMIT WILL | | | ALSO TRIGGER THE NEED FOR THE BACKFLOW UNDER SEC. D. E. | | | AND TABLE 1.1. THE BACKFLOW INSTALLATION SHALL BE DONE | | | UNDER A SEPARATE PERMIT. PLEASE PROVIDE A NOTE ON THE | | | PLAN SHOWING COMPLIANCE WILL BE MET- SECS. 105.1 & | | | 107.2.1 WPB. | | | | | | A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A | | | SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW | | | PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB AND SEC. | | | 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE | | | TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT | | | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. | | | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS | | | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION' | | | | | | 3) P1 & P2: PROVIDE A CLEANOUT AT THE JUNCTION OF THE | | | CABANA BUILDING DRAIN/SEWER- SEC. P3005.2.3 FBC RES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-29 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-29 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2022-09-29 16:30:43 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ROOFING REVIEW APPROVED: | | | | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF | | | WORK. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2022-08-05 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-08-05 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-08-04 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2022-08-05 10:30:20 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ROOFING REVIEW APPROVED: | | | | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF | | | WORK. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-06-11 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-06-11 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-06-11 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2022-06-11 12:17:07 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | ROOFING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, PROVIDE ON PLANS THE ROOFING | | | MATERIAL (PRODUCT APPROVALS) THAT WILL BE USED. | | | 2.) FBC TABLE R 905.1.1, IT APPEARS THAT DUE TO THE | | | ROOF SLOPE TWO LAYERS OF ROOFING UNDERLAYMENT WILL BE | | | REQUIRED. PLEASE INDICATE THAT INFORMATION ON ROOFING | | | PLAN SHEETS. | | | NOTE: A ROOFING SUB-PERMIT IS REQUIRED PRIOR TO ROOF | | | WORK. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-10-04 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-10-04 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-10-04 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-29 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-29 |
Time |
16:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-09-14 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-09-14 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2022-09-14 08:01:45 | SIGNATURE REVIEW DENIED: | | | | | | THE STRUCTURAL PLAN SHEETS NEED TO HAVE A THIRD PARTY | | | VERIFIABLE SIGNATURE BY ENGINEER. | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-08-03 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-08-03 |
Time |
06:07 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-08-03 |
Time |
06:07 |
Sent To |
|
|
| Notes |
| 2022-08-03 06:07:50 | ALL PAGES ARE NOT ELECTRONICALLY SIGNED/SEALED | | | | | | ALL ELECTRONIC DOCUMENTS PREPARED BY ARCHITECTS OR | | | ENGINEERS MUST BE DIGITALLY SIGNED, IN ACCORDANCE WITH | | | 61G1-16 AND 61G15, F.A.C | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-06-10 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-06-10 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-06-09 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2022-06-10 13:54:03 | SIGNATURE REVIEW DENIED: | | | | | | THE MAJORITY OF PLAN SHEETS ARE SCANS OF DIGITAL | | | SIGNATURES. THESE PLAN SHEETS DO NOT HAVE 3RD PARTY | | | VERIFIED DIGITAL SIGNATURES. PLEASE REVIEW AND SUBMIT | | | WITH 3RD PARTY VERIFIABLE DIGITAL SIGNATURES. | | | | | | FS 471/FS 481 DOCUMENTS PREPARED BY AN | | | ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE | | | TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A | | | SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL. | | | UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY | | | VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL | | | SIGNED/SEALED PAPER ORIGINAL TO: | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | BUILDING DIVISION | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | FEEL FREE TO CONTACT ME AT 561 805 6673. | | | | | 2022-05-09 16:59:34 | DIGITAL SIGNATURES FOR THE MECHANICAL DOCUMENTS | | | APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-09-01 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-09-01 |
Time |
15:41 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-09-01 |
Time |
15:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-08-15 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2022-08-15 |
Time |
11:32 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-08-15 |
Time |
11:32 |
Sent To |
|
|
| Notes |
| 2022-08-15 11:35:18 | COMMENTS FROM FIRST REVEIW NOT ADDRESSED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
ahamilto |
Date |
2022-06-01 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2022-06-01 |
Time |
12:51 |
Sent To |
|
|
| Notes |
| 2022-06-01 12:51:33 | REQUIRES A SEPERATE LANDSCPE PERMIT, DRIVEWAY PERMIT, | | | MECHANICAL PERMIT |
|
|