| 2022-05-03 08:26:33 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 22041348 |
| | 5/3/22 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) A1.1.1. & A201: SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| | W/ DIMENSIONS AT THE ACCESSIBLE SINK, DISHWASHER, |
| | REFRIGERATOR AND ICE MAKER- SEC. 606.2 & 804.6 FBC ACC. |
| | |
| | 2) P0.1: SHOW THE LOCATION OF THE REQUIRED DEDICATED |
| | SHUT OFF VALVE FOR THE IWH UNDER THE SINK- SEC 503.1 |
| | FBC P. |
| | |
| | 3) P0.1: REMOVE THE PUBLIC LAVATORY LABELING AT THE |
| | SINK AND LABEL IT ACCORDING TO THE PLANS WHICH |
| | INDICATES A COFFEE ROOM SINK- SEC. 107.2.1 WPB. |
| | |
| | 4) P0.1: HOT WATER, NOT TEMPERED WATER IS REQUIRED AT |
| | THE COFFEE ROOM SINK. REMOVE THE TEMPERED WATER MIXING |
| | VALVE AND ALL REFERENCES TO TEMPERED WATER- SECS 419.5 |
| | AND 607.1.2 FBC. PROVIDE A MIXING VALVE THAT WILL LIMIT |
| | THE HOT WATER TEMPERATURE IN ACCORDANCE WITH SEC. |
| | 607.1.1. |
| | |
| | 5) P1.1: INSTALLATION OF THE NEW FLOOR DRAIN WILL |
| | REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| | REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| | PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| | WILL BE MET- SECTION 107.2.1 WPB. |
| | |
| | 6) P.1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| | SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| | SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| | APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |