Plan Review Details - Permit 22041307
| Plan Review Stops For Permit 22041307 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-05-23 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-05-23 |
Time |
12:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-04-29 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-04-29 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-04-29 11:43:46 | FIRE COMMENTS: | | | IN CORRIDORS WHERE MORE THAN TWO VISIBLE NOTIFICATION | | | APPLIANCES ARE IN ANY FIELD OF VIEW, THEY SHALL FLASH | | | IN SYNCHRONIZATION. NFPA 72, 18.5.5.5.7 | | | THE AUTHORITY HAVING JURISDICTION FOR THIS LOCATION IS | | | WEST PALM BEACH FIRE DEPARTMENT, FIRE PREVENTION | | | BUREAU. | | | C. WALKER | | | 561-804-4762 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-05-23 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-04-28 |
Time |
06:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2022-05-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-11 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-11 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-05-23 |
|
|
Cont ID |
|
| Sent By |
ppetty |
Date |
2022-05-23 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
ppetty |
Date |
2022-05-23 |
Time |
13:17 |
Sent To |
|
|
| Notes |
|
|
|