Plan Review Details - Permit 22041299
Plan Review Stops For Permit 22041299
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-07-11 Cont ID  
Sent By cpuell Date 2022-07-11 Time 10:22 Rev Time 0.00
Received By cpuell Date 2022-07-11 Time 10:22 Sent To  
Notes
2022-07-11 10:22:40WORK IS ON 263 BANYAN BLVD, CONTACTOR STATED THAT THE
 SUITE 4 WILL NOT BE ISSUED AND IS NOT APPROPRIATE FOR
 THE PROJECT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-06-23 Cont ID  
Sent By cpuell Date 2022-06-23 Time 12:42 Rev Time 0.00
Received By cpuell Date 2022-06-23 Time 12:42 Sent To  
Notes
2022-06-23 12:43:20PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-05-21 Cont ID  
Sent By cpuell Date 2022-05-21 Time 11:18 Rev Time 0.00
Received By cpuell Date 2022-05-21 Time 11:18 Sent To  
Notes
2022-05-21 11:19:51263 BANYAN VLVD SUITE 4 IS NOT AN APPROVED ADDRESS263
 BANYAN BLVD WAS ASSIGNED TO THAT SUITE BUT NOT 4 WAS
 ASSIGNED, PLEASE CORRECT PLANS OR CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS
 ADDRESSING OPTIONS.

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2022-05-19 Cont ID  
Sent By shill Date 2022-05-19 Time 17:46 Rev Time 0.00
Received By shill Date 2022-05-19 Time 17:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By jwitmer Date 2022-06-27 Time 16:25 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-24 Cont ID  
Sent By jwitmer Date 2022-05-24 Time 15:20 Rev Time 0.00
Received By jwitmer Date 2022-05-24 Time 14:38 Sent To  
Notes
2022-05-24 15:20:13WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22041299
 ADD: 263 BANYAN BLVD.
 CONT: TYCON MANAGEMENT
 TEL: 561-860-1663
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 24TH/ 2022
 ACTION: DENIED
  
 1) SHEET A200 DETAIL 4 IS LABELED WRONG LISTED AS
 RESTROOM INTERIOR ELEVATION BUT IS A BREAK ROOM
 ELEVATION. PLEASE NOTE THE ELEVATION SHOW A FUTURE
 MICROWAVE AND SHELF, THE BOTTOM OF THE SHELF
 IS AT AN ELEVATION OF 4 FEET 8 INCHES ABOVE FINISH
 FLOOR. PLEASE SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTIONS:
 1A) 308 REACH RANGES. 308.2 FORWARD REACH/ 308.2.1
 UNOBSTRUCTED/ 308.2.2 OBSTRUCTED HIGH REACH.
 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2
 OBSTRUCTED HIGH REACH.
  
 1B) 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS
 SHALL BE PLACED WITHIN ONE OR MORE OF THE REACH RANGES
 SPECIFIED IN 308. 309.4 OPERATION. OPERABLE PARTS SHALL
 BE OPERABLE WITH ONE HAND AND SHALL NOT REQUIRE TIGHT
 GRASPING, PINCHING, OR TWISTING OF THE WRIST. THE FORCE
 REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS
 MAXIMUM.
  
 2) SHEET A100 SHOWS AN ACCESSIBLE RESTROOM # 110 WITH
 SHOWER AND ACCESSED BY A CORRIDOR # 107. THE EXCEPTION
 FOR PRIVATE RESTROOMS IS FOUND WHEN ACCESS TO THE
 PRIVATE RESTROOM IS THROUGH A PRIVATE OFFICE, UNDER ONE
 PERSON?S CONTROL, NOT A CORRIDOR. THIS EXCEPTION IS
 FOUND UNDER THE HEADING OF GRAB BARS SECTIONS 607.4
 EXCEP. 1, & 608.3 EXCEP. 1.
  
 3) SHEET A100 OFFICE 103 ENTRY DOOR 02, THE PLAN SHOWS
 A DIMENSION 3 FEET ELEVEN ONE-HALF INCHES. PLEASE SEE
 FIGURE 404.2.4.1(H) A MINIMUM OF 48 INCHES IS REQUIRED.
  
 4) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-07-06 Cont ID  
Sent By jleahy Date 2022-07-06 Time 08:13 Rev Time 0.00
Received By jleahy Date 2022-07-06 Time 08:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 17:30 Rev Time 0.00
Received By jleahy Date 2022-05-26 Time 17:30 Sent To  
Notes
2022-05-26 17:31:21FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLEASE PROVIDE A RISER DIAGRAM AND LOAD CALCULATION FOR
 THE INSTALLATION 215.5
  
  

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2022-07-06 Cont ID  
Sent By jleahy Date 2022-07-06 Time 08:17 Rev Time 0.00
Received By jleahy Date 2022-07-06 Time 08:17 Sent To  
Notes
2022-07-06 08:18:18VOICE AND DATA AS PER PLANS JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-16 Cont ID  
Sent By pleduc Date 2022-05-16 Time   Rev Time 0.00
Received By pleduc Date 2022-05-16 Time 13:30 Sent To  
Notes
2022-05-16 15:55:54FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-06 Cont ID  
Sent By jleahy Date 2022-07-06 Time 08:18 Rev Time 0.00
Received By jleahy Date 2022-06-21 Time 14:32 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 17:32 Rev Time 0.00
Received By jleahy Date 2022-05-16 Time 05:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-06-23 Cont ID  
Sent By medwards Date 2022-06-23 Time 09:54 Rev Time 0.00
Received By medwards Date 2022-06-23 Time 09:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-23 Cont ID  
Sent By medwards Date 2022-05-23 Time 14:45 Rev Time 0.00
Received By medwards Date 2022-05-23 Time 14:45 Sent To  
Notes
2022-05-23 15:00:59PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS
 FOR THE 2 NEW AHU'S. FEC C403.2.1
 PROVIDE A DRAWING SHOWING THE CONDENSING UNITS LOCATION
 AND THE TIE DOWN METHOD. FBC 107.2.1
  
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-06-22 Cont ID  
Sent By rwbrown Date 2022-06-22 Time 14:29 Rev Time 0.00
Received By rwbrown Date 2022-06-22 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-05-21 Cont ID  
Sent By rwbrown Date 2022-05-21 Time 07:51 Rev Time 0.00
Received By rwbrown Date 2022-05-21 Time 07:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-07 Cont ID  
Sent By jleahy Date 2022-07-06 Time 08:15 Rev Time 0.00
Received By jleahy Date 2022-07-06 Time 08:06 Sent To  
Notes
2022-07-06 08:16:38NOT ALL PAGES WITH TITLE BLOCK SIGNED AND SEALED BY THE
 PERSON RESPONSIBLE FOR THE DESIGN. JLEAHY
2022-06-23 09:55:16MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By jleahy Date 2022-05-26 Time 17:31 Rev Time 0.00
Received By jleahy Date 2022-05-26 Time 17:31 Sent To  
Notes
2022-05-26 17:34:15FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NEED TO BE SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN.
  
 PER THE WPB AMENDMENTS TO THE FBC, EACH SHEET OF PLAN
 IS REQUIRED TO BE SIGNED BY PERSON RESPONSIBLE FOR THE
 DESIGN. PROVIDE CORRECTION. FS 481.229; WPB FBC 107.1,
 107.2.1, 107.3.5.1.2
  
 PLAN FOR 480 VOLT SYSTEMS ARE REQUIRED TO BE DESIGNED,
 DRAWN, AND SIGNED/SEALED BY A LICENSED ENGINEER.
 PROVIDE CORRECTION. FS 471.003(2)(H)(2)(A).
  
2022-05-23 15:02:12MECHANICAL PLANS ARE NOT DIGITALLY SIGNED BY THE
 DESIGNER. ME
2022-05-21 07:53:31PLMG PAGES NOT SIGNED
  