Plan Review Details - Permit 22041295
Plan Review Stops For Permit 22041295
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-05 Cont ID  
Sent By rmcdouga Date 2022-08-05 Time 14:09 Rev Time 0.00
Received By rmcdouga Date 2022-08-05 Time 14:09 Sent To  
Notes
2022-08-05 14:12:35THE DRAWING SHOWS THAT THE CANTILEVER FOOTING EXTENDS
 4" PAST THE WALL. THE FOOTING CAN NOT EXTEND PAST THE
 PROPERTY LINE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-17 Cont ID  
Sent By rmcdouga Date 2022-05-17 Time 12:47 Rev Time 0.00
Received By rmcdouga Date 2022-05-17 Time 12:47 Sent To  
Notes
2022-05-17 13:43:49PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE RETAINING WALL APPEARS TO BE SHOWN ON THE
 PROPERTY LINE. THE RETAINING WALL DETAIL SECTION SHOWS
 THE FOOTER EXTENDING BEYOND THE WALL. THE FOOTING FOR
 THE RETAINING WALL CAN NOT CROSS THE PROPERTY LINE. YOU
 WILL HAVE TO USE AN OFF SET FOOTING SO THAT IT DOES NOT
 EXTEND PAST THE PROPERTY LINE. FBC 107.2.1
  
 2) IT APPEARS THAT YOU INTEND TO FILL THE AREA BETWEEN
 THE EXISTING HOUSE AN THE RETAINING WALL. PLEASE
 CLARIFY. FBC 107.2.1
  
 3) SPECIFY THE ELEVATION OF THE EXISTING AREA THAT WILL
 BE BEHIND THE RETAINING WALL AND INDICATE HOW MUCH SOIL
 WILL BE ADDED. FBC 107.2.1
  
 4) PROVIDE A SURFACE WATER DRAINAGE PLAN FOR THE AREA
 THAT WILL BE FILLED WITH ELEVATIONS THAT SHOW
 COMPLIANCE WITH FBC-R401.3.
  
 5) IT APPEARS THAT THE FINISH GRADE ADJACENT TO THE
 HOUSE IS BEING INCREASED. SPECIFY THE TYPE OF
 FOUNDATION FOR THE HOUSE. IS IT A RAISED SLAB ON GRADE,
 DOES IT HAVE A CRAWL SPACE OR A BASEMENT? FBC 107.2.1
  
 6) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 7) FBC 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM SIZE,
 SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2022-08-02 Cont ID  
Sent By rrossano Date 2022-08-02 Time   Rev Time 0.00
Received By rrossano Date 2022-08-02 Time   Sent To  
Notes
2022-08-02 15:45:02PLEASE CLEARLY SHOW ON COPY OF PROPERTY SURVEY EXACTLY
 WHERE WALL IS BEING PLACED IN RELATION TO ANY EXISTING
 UTILITIES OR UTILITY EASEMENTS. THERE IS A 3 IN. WATER
 MAIN RUNNING ALONG THE WESTERN EDGE OF THE PROPERTY.
  
 THANKS,
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-05-23 Cont ID  
Sent By rrossano Date 2022-05-23 Time   Rev Time 0.00
Received By rrossano Date 2022-05-23 Time   Sent To I
Notes
2022-05-23 08:55:33PLEASE ADDRESS BUILDING COMMENTS.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By amhamilt Date 2022-08-10 Time 10:02 Rev Time 0.00
Received By amhamilt Date 2022-08-10 Time 10:02 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-05-11 Cont ID  
Sent By amhamilt Date 2022-05-11 Time 14:30 Rev Time 0.00
Received By amhamilt Date 2022-05-11 Time 14:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-08-10 Cont ID  
Sent By lmarchan Date 2022-08-10 Time 13:45 Rev Time 0.00
Received By lmarchan Date 2022-07-27 Time 15:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-24 Cont ID  
Sent By lmarchan Date 2022-05-24 Time 09:42 Rev Time 0.00
Received By lmarchan Date 2022-04-27 Time 09:38 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-07-28 Cont ID  
Sent By jgomez Date 2022-07-28 Time 17:05 Rev Time 0.00
Received By jgomez Date 2022-07-28 Time 17:02 Sent To  
Notes
2022-07-28 17:06:46HARD COPY DWGS SK1 AND SK2 HAVE ENGINEER'S EMBOSSED
 SEAL AND WET SIGNATURE. JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-04-27 Cont ID  
Sent By rmcdouga Date 2022-04-27 Time 13:10 Rev Time 0.00
Received By rmcdouga Date 2022-04-27 Time 13:10 Sent To  
Notes
2022-04-27 13:18:00SIGNED AND SEALED PAPER PLAN, FROM MICHEAL BABER, PE,
 SHEET SK1 WAS SENT TO STORAGE.

Review Stop Z ZONING
Rev No 2 Status P Date 2022-08-10 Cont ID  
Sent By amhamilt Date 2022-08-10 Time 10:02 Rev Time 0.00
Received By amhamilt Date 2022-08-10 Time 10:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-11 Cont ID  
Sent By amhamilt Date 2022-05-11 Time 14:29 Rev Time 0.00
Received By amhamilt Date 2022-05-11 Time 14:29 Sent To  
Notes
2022-05-11 14:30:20 
 ALL PORTIONS OF WALL SHALL BE LOCATED WITHIN PROPERTY
 LINE INCLUDING FOOTER
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428
  