Plan Review Details - Permit 22041189
Plan Review Stops For Permit 22041189
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 4 Status P Date 2023-07-24 Cont ID  
Sent By lmarchan Date 2023-07-24 Time 07:53 Rev Time 0.00
Received By lmarchan Date 2023-07-24 Time 07:53 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status F Date 2023-07-03 Cont ID  
Sent By jwitmer Date 2023-07-03 Time 13:32 Rev Time 0.00
Received By jwitmer Date 2023-07-03 Time 11:34 Sent To  
Notes
2023-07-03 13:32:44COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 16:41 Rev Time 0.00
Received By jwitmer Date 2023-02-28 Time   Sent To  
Notes
2023-02-28 16:41:14TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTORS LETTERHEAD, STATING THAT
 THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2022-12-14 Cont ID  
Sent By jwitmer Date 2022-12-14 Time 14:57 Rev Time  
Received By jwitmer Date 2022-12-14 Time   Sent To  
Notes
2022-12-14 14:57:50TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON THE CONTRACTOR???S LETTERHEAD, STATING
 THAT THE INSTRUCTIONS ON THE WEBSITE OF ASBESTOS
 PROGRAM COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM
 BEACH COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION
 WILL BE GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
 HTTPS://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVIC
 ES/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION
 -RENOVATION.HTML
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2023-07-03 Cont ID  
Sent By jwitmer Date 2023-07-03 Time 13:23 Rev Time 0.00
Received By jwitmer Date 2023-07-03 Time 11:16 Sent To  
Notes
2023-07-03 13:23:03WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22041189
 ADD: 2032 N DIXIE HWY.
 CONT: SOLID ROCK RENOVATION
 TEL: 561-577-3057
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. 7-03-23
 ACTION: DENIED
 1-4) COMPLIED, WINDOW & DOOR PERMIT 23030707. 2020
 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
  
 5) SHEET COVERSHEET. SCOPE OF WORK, COMMENTS:
  
 5A) 3RD REQUEST. SEMI-COMPLIED, NOTE # 2 INDICATES NEW
 VINYL FLOORING, PLEASE DESIGNATE THE LOCATIONS OF
 FLOORING REQUIRING UNDERLAYMENT IN THE 2ND STORY
 RESIDENTIAL UNITS AND MAIN CORRIDOR AND OVER THE 1ST
 FLOOR RESIDENTIAL OCCUPANCIES. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES. A WRITTEN ANALYSIS
 NEEDS TO ACCOMPANY THE PLANS AS TO HOW YOU ARE GOING TO
 ACHIEVE BOTH AN IIC & STC RATING OF 50 OR MORE. THE
 SHEET A-3 SHOWS A FLOOR CEILING ASSEMBLY GA FILE FC5250
 THAT SHOW A STC RATING OF 45 TO 49 DB RATING. THE SAME
 HOLDS TRUE FOR THE WALL RATING BETWEEN THE R2 TENANT
 SPACES FOR BOTH THE 1ST FLOOR UNITS AND WALL RATING FOR
 THE 2ND FLOOR R2 OCCUPANCIES BOTH FLOOR SYSTEM AND WALL
 SYSTEMS NEED TO ACHIEVE A MINIMUM OF 50 DB FOR IIC &
 STC RATINGS. SEE COMMENTS 5A & 5B.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A WOOD FLOOR JOIST SYSTEM 6-INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR BUILDINGS
 SHOWING COMPLIANCE WITH:
  
 5A)(1) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B)(2) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 5C)(3) COMPLIED 1 HOUR FIRE RATING ASSEMBLY FOR
 FLOORING AND WALL ASSEMBLIES.
 5B) COMPLIED, GA ASSOCIATION 1 HOUR FIRE RATING
 ASSEMBLIES FOR WALLS AND FLOORS.
  
 5B)(1) COMPLIED, GA ASSOCIATION 1 HOUR FIRE RATING
 ASSEMBLIES FOR WALLS AND FLOORS.
  
 5B)(2) 3RD REQUEST. SEE COMMENT 5A. BETWEEN DWELLING
 UNITS. FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 6) COMPLIED.
  
 7) SEMI-COMPLIED, THE CONTRACTOR HAS SUBMITTED WHERE
 THEY WILL MEET THEIR DISPROPORTIONATE COST IN THE 1ST
 FLOOR RESTROOM. 2ND REQUEST PROVIDE LETTER ON EITHER
 THE DESIGN PROFESSIONAL OR CONTRACTOR LETTER HEAD WHERE
 THESE FUNDS ARE TO BE SPENT. FIRST FLOOR. FLORIDA
 ACCESSIBILITY CODE SECTION: DISPROPORTIONATE COST
 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% DISPROPORTIONATE
 FUNDS LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING
 SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2020 ACCESSIBILITY CODE.
 SHEET A-2 STILL MISSING ACCESSIBLE ELEMENTS IN THE
 ELEVATION VIEWS:
 A) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE WATER
 CLOSET. SECTION 604.3
 B) CLEAR FLOOR SPACE DIAGRAM & DIMENSIONS FOR THE
 LAVATORIES. SECTION 606.2.
 C) TURNING SPACE DIAMETERS. SECTION 304.3
 D) TOILET FLUSH CONTROL SECTION 604.6 FLUSH CONTROLS TO
 BE LOCATED OPEN SIDE OF WATER CLOSET.
 E) CENTERLINES OF THE TOILET DISPENSER MEASURED FROM
 THE FRONTS OF THE WATER CLOSET. SECTION & FIGURE 604.7
 F) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE BOTTOM EDGE OF THE REFLECTIVE SURFACE, MIRRORS
 ABOVE SINKS. SECTION 606.3.
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 ENLARGING DOOR OPENINGS, INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COST
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COST ASSOCIATED WITH RELOCATING
 AN ACCESSIBLE DRINKING FOUNTAIN.
  
 8) COMPLIED.
  
 9) A NEW ARCHITECTURAL CANOPY HAS BEEN SUBMITTED, THERE
 IS NO LOCATION WHERE THIS IS TO BE INSTALLED, NO
 ENGINEERING SHEET NOR WIND LOAD OR FASTENING
 SCHEDULENOR HEIGHT OF THE BOTTOM OF CANOPY ABOVE
 GROUND, PROVIDE A SURVEY WITH LOCATION SHOWN ON THE
 SURVEY A SEPARATE PERMIT IS REQUIRED, PROVIDE VALUE FOR
 CANOPY. . 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. CONSTRUCTION DOCUMENTS SHALL BE SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 10) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2023-02-28 Cont ID  
Sent By jwitmer Date 2023-02-28 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2023-02-28 Time   Sent To  
Notes
2023-02-28 16:39:16WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22041189
 ADD: 2032 N DIXIE HWY.
 CONT: SOLID ROCK RENOVATION
 TEL: 561-577-3057
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. 2/28/2023
 ACTION: DENIED
 1) 2ND REQUEST. STOP WOK ORDERS WERE GIVEN ON 4/19/22
 FOR ALL TRADES, 8/23/22 STOP WORK ORDER WAS GIVEN FOR
 GAS WORK WITHOUT THE BENEFIT OF A PERMIT. WORK NOT
 INCLUDED IN THE SCOPE OF WORK NEW WINDOWS SHOWN ON
 GOGGLE MAPS. 2 PERMITS WERE REVOKED 12030175 REPLACE 3
 EXT. DOORS, 15070290 REVOKED VALUE $350.00 DOLLARS
 REPLACE BROKEN WINDOWS, 15010327 REISSUE 1212703 FOR
 REPLACE 3 EXTERIOR DOORS. NONE OF THESE PERMITS
 INDICATE NEW WINDOWS FOR THE 2ND STORY PLEASE INCLUDE
 IN THE SCOPE OF WORK. PLEASE PROVIDE THE FOLLOWING
 INFORMATION:
 2) 2ND REQUEST. 2020 FBC-B 1603.1.4 WIND DESIGN
 CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
  
 3) 2ND REQUESST. COMPONENTS & CLADDING. PLEASE SUBMIT
 THE COMPONENTS AND CLADDING PRODUCT APPROVALS. 2020
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.4.1
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(B) WINDOWS & MULLIONS
  
 4) 2ND REQUEST. W. P. B. 107.3.4. PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY FLORIDA
 ADMINISTRATIVE CODE RULE 61G20 SHALL BE REVIEWED AND
 APPROVED IN WRITING (SHOP DRAWING STAMP OF APPROVAL) BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5) SHEET COVERSHEET. SCOPE OF WORK, COMMENTS:
 5A) 2ND REQUEST. NOTE # 2 INDICATES NEW VINYL FLOORING,
 PLEASE DESIGNATE THE LOCATIONS OF FLOORING IN
 RESIDENTIAL UNITS, 2ND STORY CORRIDOR AND STAIRS AND OR
 1ST FLOOR BUSINESS OCCUPANCIES. 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6-INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 5A)(1) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 5B)(2) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 5C)(3) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 (TILE & MARBLE) INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
 OR
 5C)(3) FBC-B 804.4.4.1 SOFT FLOOR FINISHES (LVT/ LPT OR
 LAMINATED OR ENGINEERED WOOD FLOORING) WITHIN TENANT
 SPACE. INTERIOR FLOOR COVERING MATERIALS SHALL COMPLY
 WITH THE REQUIREMENTS OF THE COC FF-1 ???PILL TEST???
 (CPSC 16 CFR PART 1630) OR WITH ASTM D2859.
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B. 804.2 & 804.3/ ASTM E648 OR NFPA 253
  
 5B) SEMI-COMPLIED SHOW AREAS WHERE TO BE REPLACED.
 NOTES 3 & 4 DEAL WITH REPLACEMENT OF DRYWALL BOTH 1/2
 INCH AND 5/8-INCH TYPE X EXACT LOCATIONS ARE NOT GIVEN
 NOR THE AMOUNT OF DRYWALL THAT IS TO BE INSTALLED. 2020
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1. DRAWINGS &
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC TO
 THE TECHNICAL CODES.
  
 5B)(1)THE PLANS ARE SILENT AS TO MAINTAINING 1-HOUR
 FIRE RATING SEE 2020 FBC-BUILDING CODE 420.2 SEPARATION
 WALLS AND 420.3 HORIZONTAL SEPARATION. FIRE RATED
 CORRIDORS AND STAIRWAY SECTION 1023.2, SECTION 707 AND
 OR SECTION 711. 1-HOUR FIRE RATING FOR BENEATH THE
 STAIRWAY 1011.7.3. 1ST FLOOR STOCKROOM.
  
 5B)(2) BETWEEN DWELLING UNITS. FBC-B 2020 1207.2
 AIR-BORNE SOUND. WALLS, PARTITIONS AND FLOOR/CEILING
 ASSEMBLIES SEPARATING DWELLING UNITS FROM EACH OTHER OR
 FROM PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND
 TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45 IF
 FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90.
  
 5C) 2ND REQUEST. PROVIDE LOCATIONS WHERE WOOD IS
 DAMAGED OR ROTTEN, IT IS UP TO THE DESIGN PROFESSIONAL
 TO GIVE THE CONTRACTORS DIRECTION, IF BEYOND YOUR SCOPE
 THEN AN ENGINEER SHOULD GET INVOLVED. NOTE 5 INDICATES
 REPLACE EXISTING DAMAGED FRAMING OR ROTTEN FRAMING
 ENCOUNTERED PER THE PRESCRIPTIVE METHOD OF THE EXISTING
 BUILDING CODE. PLEASE READ THE SECTIONS 401.2.2 AND
 401.2.2. IN BOTH CASES SUCH MATERIALS SHALL BE
 DETERMINED BY THE BUILDING OFFICIAL TO BE UNSAFE. AGAIN
 PLEASE PROVIDE THE AREAS WHERE DAMAGED OR ROTTEN
 FRAMING MEMBERS ARE LOCATED SIZE OF FRAMING MEMBERS,
 SPACING, SPANS, TYPE OF EXISTING FRAMING AND TYPE OF
 PROPOSED FRAMING, IF TO BE REMOVED, OR IF TO BE
 SISTERED AND THE LENGTH OF THE SISTERED FRAMING MEMBER
 VERSE THE OLD FRAMING MEMBER. PLEASE ALSO REVIEW IN THE
 2020 EXISTING BUILDING CODE 401.3 DANGEROUS CONDITIONS.
 THE BUILDING OFFICIAL SHALL HAVE THE AUTHORITY TO
 REQUIRE THE ELIMINATION OF CONDITIONS DEEMED DANGEROUS.
  
 6) 2ND REQUEST, THE DESIGN PROFESSIONAL GIVES DIRECTION
 TO AMOUNT OF DOORS SO THE CONTRACTOR KNOWS HOW TO BID
 THE PROJECT. NOTE 6 STATES THE GC SHALL REPLACE
 EXISTING INTERIOR DAMAGED INTERIOR DOORS. PLEASE
 PROVIDE LOCATIONS OF THESE DOORS, IF ENTRY DOORS INTO
 THE R2 RESIDENTIAL UNITS THEN THEY SHALL COMPLY WITH
 FBC-BUILDING TABLE 1020.1.
  
 7) 2ND REQUEST PROVIDE LETTER ON EITHER THE DESIGN
 PROFESSIONAL OR CONTRACTOR LETTER HEAD WHERE THESE
 FUNDS ARE TO BE SPENT. FIRST FLOOR. FLORIDA
 ACCESSIBILITY CODE SECTION: DISPROPORTIONATE COST
 202.4.1. PLEASE REVIEW HOW YOU ARE TO MEET
 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD ON THEIR LETTERHEAD NEED TO SHOW HOW
 THEY ARE GOING TO SPEND UP TO THE 20% DISPROPORTIONATE
 FUNDS LISTED FOR EACH ELEMENT WHERE THE FUNDS ARE BEING
 SPENT AND IN THE ORDER LISTED IN SECTION 202.4.1
 DISPROPORTIONATE COST OF THE 2020 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 ENLARGING DOOR OPENINGS, INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COST
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COST ASSOCIATED WITH RELOCATING
 AN ACCESSIBLE DRINKING FOUNTAIN.
  
 8) 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 8A) 2ND REQUEST. PLEASE STATE WHAT TYPE OF TILE BACKING
 BOARD IS TO BE INSTALLED IN RESTROOMS & BATHROOMS
 THROUGHOUT THE PROJECT.
 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF SERVICE
 SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT LESS
 THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
  
 10) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-12-21 Cont ID  
Sent By jwitmer Date 2022-12-21 Time 08:19 Rev Time 0.00
Received By jwitmer Date 2022-12-14 Time 14:58 Sent To  
Notes
2022-12-21 08:19:34WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22041189
 ADD: 2032 N DIXIE HWY.
 CONT: SOLID ROCK RENOVATION
 TEL: 561-577-3057
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. 12/21/2022
 ACTION: DENIED
 1) STOP WOK ORDERS WERE GIVEN ON 4/19/22 FOR ALL
 TRADES, 8/23/22 STOP WORK ORDER WAS GIVEN FOR GAS WORK
 WITHOUT THE BENEFIT OF A PERMIT. WORK NOT INCLUDED IN
 THE SCOPE OF WORK NEW WINDOWS SHOWN ON GOGGLE MAPS. 2
 PERMITS WERE REVOKED 12030175 REPLACE 3 EXT. DOORS,
 15070290 REVOKED VALUE $350.00 DOLLARS REPLACE BROKEN
 WINDOWS, 15010327 REISSUE 1212703 FOR REPLACE 3
 EXTERIOR DOORS. NONE OF THESE PERMITS INDICATE NEW
 WINDOWS FOR THE 2ND STORY PLEASE INCLUDE IN THE SCOPE
 OF WORK. PLEASE PROVIDE THE FOLLOWING INFORMATION:
 2) 2020 FBC-B 1603.1.4 WIND DESIGN CRITERIA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, VASD, AS
 DETERMINED IN ACCORDANCE WITH SECTION 1609.3.1.
  
 2. RISK CATEGORY.
  
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE. ASCE 7-16 TABLE 30.3.1.
  
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS SPECIFICALLY DESIGNED
 BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR
 THE DESIGN OF THE STRUCTURE, PSF.
  
 6. TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. ASCE 7-10 TABLE 30.3.1. 1609.3.1 WIND SPEED
 CONVERSION VULT TO VASD.
 3) COMPONENTS & CLADDING. PLEASE SUBMIT THE COMPONENTS
 AND CLADDING PRODUCT APPROVALS. 2020 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(B) WINDOWS & MULLIONS
  
 4) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 5) SHEET COVERSHEET. SCOPE OF WORK, COMMENTS:
 5A) NOTE # 2 INDICATES NEW VINYL FLOORING, PLEASE
 DESIGNATE THE LOCATIONS OF FLOORING IN RESIDENTIAL
 UNITS, 2ND STORY CORRIDOR AND STAIRS AND OR 1ST FLOOR
 BUSINESS OCCUPANCIES. 2020 WEST PALM BEACH AMENDMENTS
 TO THE FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES.
 5B) NOTES 3 & 4 DEAL WITH REPLACEMENT OF DRYWALL BOTH
 ?? INCH AND 5/8-INCH TYPE X EXACT LOCATIONS ARE NOT
 GIVEN NOR THE AMOUNT OF DRYWALL THAT IS TO BE
 INSTALLED. 2020 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.2.1. DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES.
 THE PLANS ARE SILENT AS TO MAINTAINING 1-HOUR FIRE
 RATING SEE 2020 FBC-BUILDING CODE 420.2 SEPARATION
 WALLS AND 420.3 HORIZONTAL SEPARATION. FIRE RATED
 CORRIDORS AND STAIRWAY SECTION 1023.2, SECTION 707 AND
 OR SECTION 711. 1 HOUR FIRE RATING FOR BENEATH THE
 STAIRWAY 1011.7.3. 1ST FLOOR STOCKROOM.
  
 5C) NOTE 5 INDICATES REPLACE EXISTING DAMAGED FRAMING
 OR ROTTEN FRAMING ENCOUNTERED PER THE PRESCRIPTIVE
 METHOD OF THE EXISTING BUILDING CODE. PLEASE READ THE
 SECTIONS 401.2.2 AND 401.2.2. IN BOTH CASES SUCH
 MATERIALS SHALL BE DETERMINED BY THE BUILDING OFFICIAL
 TO BE UNSAFE. AGAIN PLEASE PROVIDE THE AREAS WHERE
 DAMAGED OR ROTTEN FRAMING MEMBERS ARE LOCATED SIZE OF
 FRAMING MEMBERS, SPACING, SPANS, TYPE OF EXISTING
 FRAMING AND TYPE OF PROPOSED FRAMING, IF TO BE REMOVED,
 OR IF TO BE SISTERED AND THE LENGTH OF THE SISTERED
 FRAMING MEMBER VERSE THE OLD FRAMING MEMBER. PLEASE
 ALSO REVIEW IN THE 2020 EXISTING BUILDING CODE 401.3
 DANGEROUS CONDITIONS. THE BUILDING OFFICIAL SHALL HAVE
 THE AUTHORITY TO REQUIRE THE ELIMINATION OF CONDITIONS
 DEEMED DANGEROUS.
  
 6) NOTE 6 STATES THE GC SHALL REPLACE EXISTING INTERIOR
 DAMAGED INTERIOR DOORS. PLEASE PROVIDE LOCATIONS OF
 THESE DOORS, IF ENTRY DOORS INTO THE R2 RESIDENTIAL
 UNITS THEN THEY SHALL COMPLY WITH FBC-BUILDING TABLE
 1020.1.
  
 7) FIRST FLOOR. FLORIDA ACCESSIBILITY CODE SECTION:
 DISPROPORTIONATE COST 202.4.1. PLEASE REVIEW HOW YOU
 ARE TO MEET DISPROPORTIONATE COST. EITHER THE
 CONTRACTOR OR THE DESIGNER OF RECORD ON THEIR
 LETTERHEAD NEED TO SHOW HOW THEY ARE GOING TO SPEND UP
 TO THE 20% DISPROPORTIONATE FUNDS LISTED FOR EACH
 ELEMENT WHERE THE FUNDS ARE BEING SPENT AND IN THE
 ORDER LISTED IN SECTION 202.4.1 DISPROPORTIONATE COST
 OF THE 2020 ACCESSIBILITY CODE.
  
 202.4.1. DISPROPORTIONATE COST. ALTERATIONS MADE TO
 PROVIDE AN ACCESSIBLE PATH OF TRAVEL TO THE ALTERED
 AREA WILL BE DEEMED DISPROPORTIONATE TO THE OVERALL
 ALTERATION WHEN THE COST EXCEEDS 20% OF THE COST OF THE
 ALTERATION TO THE PRIMARY FUNCTION AREA. COST THAT MAY
 BE COUNTED AS EXPENDITURES REQUIRED TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL MAY INCLUDE: (I) COST
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUT TO THE ALTERED AREA; (II) COST
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 ENLARGING DOOR OPENINGS, INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COST
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COST ASSOCIATED WITH RELOCATING
 AN ACCESSIBLE DRINKING FOUNTAIN.
  
 8) 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS
 COMMENT IS A RESULT OF THE BUILDING OFFICIAL
 INTERPRETATION ON 06/2020. IN BATHROOMS, RESTROOMS &
 SERVICE SINK AREAS EPOXY PAINT IS NO LONGER CONSIDERED
 A SMOOTH HARD, NON-ABSORBENT SURFACE.
  
 8A) 1210.2.2 WALLS & PARTITIONS WITHIN 2 FEET OF
 SERVICE SINKS, URINALS, AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NON-ABSORBENT SURFACE TO A HEIGHT OF NOT
 LESS THAN 4 FEET ABOVE THE FLOOR, EXCEPT FOR STRUCTURAL
 ELEMENTS, THE MATERIAL USED IN SUCH WALLS SHALL BE OF A
 TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE.
  
  
 9) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2023-07-17 Cont ID  
Sent By mpeterso Date 2023-07-17 Time 13:37 Rev Time 0.00
Received By mpeterso Date 2023-07-17 Time 13:37 Sent To  
Notes
2023-07-17 13:41:10ELECTROCAL REVIEW FAILED
  
 IT APPEARS NONE OF THE PRIOR COMMENTS HAVE BEEN
 ADDRESSED. PROVIDE A WRITTEN NARRITIVE ADDRESSING EACH
 OF THE PRIOR 11 COMMENTS, ALONG WITH CORRECTED PLANS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 12:19 Rev Time 0.00
Received By mpeterso Date 2023-03-10 Time 08:17 Sent To  
Notes
2023-03-10 12:27:31ELECTRIC REVIEW FAILED
  
 1) PLEASE PROVIDE A COMPLETE RISER DIAGRAM. INCLUDE ALL
 EQUIPMENT, CONDUIT, WIREWAY, CONDUCTOR, SIZES AND
 NUMBER OF CONDUCTORS IN ALL RACE WAYS AND WIREWAYS. NEC
 215.5
  
 NEC 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER
 DETAILS SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF
 THE FEEDERS.
  
 2 ) IT APPEARS THERE ARE MULTIPLE CONDUCTORS IN
 CONDUITS BETWEEN WIREWAYS THAT WILL NEED TO BE DE RATED
 AS REQUIRED PER NEC 310.15(B)(3).
  
 310.15(B)(3). ADJUSTMENT FACTORS. MORE THAN THREE
 CURRENT-CARRYING CONDUCTORS. WHERE THE NUMBER OF
 CURRENT-CARRYING CONDUCTORS IN A RACEWAY OR CABLE
 EXCEEDS THREE, OR WHERE SINGLE CONDUCTORS OR
 MULTICONDUCTOR CABLES ARE INSTALLED WITHOUT MAINTAINING
 SPACING FOR A CONTINUOUS LENGTH LONGER THAN 600 MM (24
 IN.) AND ARE NOT INSTALLED IN RACEWAYS, THE ALLOWABLE
 AMPACITY OF EACH CONDUCTOR SHALL BE REDUCED AS SHOWN IN
 TABLE 310.15(B)(3)(A)
  
 3) PLEASE RESPOND TO PREVIOUS COMMENT. THE EXISTING
 ELECTRICAL SERVICE WAS PERMITTED AS 300-AMP. YOU DETAIL
 THE EXISTING SERVICE AS 400 AMP. PLEASE RESOLVE THIS
 CONFLICT. FBC 107.2
  
 FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 4) PLEASE DETAIL ELECTRIC WORK THAT IS EXISTING AND TO
 REMAIN AND WORK THAT IS NEW AND TO BE ADDED ON ALL
 ELECTRIC PLANS. FBC 107.2
  
 5) PLEASE DETAIL THE HVAC RECEPTACLES REQUIRED ON THE
 ROOF. NEC 210.63
  
 NEC 210.63 HEATING, AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT OUTLET. A 125-VOLT, SINGLE-PHASE, 15- OR
 20-AMPERE-RATED RECEPTACLE OUTLET SHALL BE INSTAL???LED
 AT AN ACCESSIBLE LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 7.5 M (25 FT) OF THE HEATING, AIR-CONDITIONING,
 AND REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET
 SHALL NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.
  
 6) DETAIL REQUIRED OUTSIDE RECEPTACLES AT OUTSIDE
 PORCHES AND ON THE SECOND FLOOR IF THEY ARE ACCESSIBLE
 FROM DWELLING UNITS. NEC 210.52 (E)(2) AND NEC (E)(3)
  
 NEC 210.52(2) MULTIFAMILY DWELLINGS. FOR EACH DWELLING
 UNIT OF A MULTIFAMILY DWELLING WHERE THE DWELLING UNIT
 IS LOCATED AT GRADE LEVEL AND PROVIDED WITH INDIVIDUAL
 EXTERIOR ENTRANCE/EGRESS, AT LEAST ONE RECEPTACLE
 OUTLET READILY ACCESSIBLE FROM GRADE AND NOT MORE THAN
 2.0 M (61???2 FT) ABOVE GRADE LEVEL SHALL BE INSTALLED
  
 NEC 210. (E)(3) BALCONIES, DECKS, AND PORCHES.
 BALCONIES, DECKS, AND PORCHES THAT ARE ATTACHED TO THE
 DWELLING UNIT AND ARE ACCESSIBLE FROM INSIDE THE
 DWELLING UNIT SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE FROM THE BALCONY, DECK, OR PORCH. THE
 RECEPTACLE OUTLET SHALL NOT BE LOCATED MORE THAN 2.0 M
 (61???2 FT) ABOVE THE BALCONY, DECK, OR PORCH WALKING
 SURFACE.
  
 7) PLEASE RESPOND TO PREVIOUS COMMENT. DETAIL THE
 REQUIRED SHOW WINDOW RECEPTACLES IN THE RETAIL SPACES.
 NEC 210.62
  
 NEC 210.62 SHOW WINDOWS. AT LEAST ONE 125-VOLT,
 SINGLE-PHASE, 15- OR 20-AMPERE-RATED RECEPTACLE OUTLET
 SHALL BE INSTALLED WITHIN 450 MM (18 IN.) OF THE TOP OF
 A SHOW WINDOW FOR EACH 3.7 LINEAR M (12 LINEAR FT) OR
 MAJOR FRACTION THEREOF OF SHOW WINDOW AREA MEASURED
 HORIZONTALLY AT ITS MAXIMUM WIDTH.
  
 8) PLEASE RESPOND TO PREVIOUS COMMENT, PLEASE INDICATE
 TYPE FIRE RESISTANCE RATING FOR BUILDING AND THE
 APPLICABLE WIRING METHODS TO BE USED. NEC 110.8, NEC
 CHAPTER 3 WIRING METHODS AND MATERIALS AND NEC TABLE
 ANNEX E
  
 NEC 110.8 WIRING METHODS. ONLY WIRING METHODS
 RECOGNIZED AS SUITABLE ARE INCLUDED IN THIS CODE. THE
 RECOGNIZED METHODS OF WIRING SHALL BE PERMITTED TO BE
 INSTALLED IN ANY TYPE OF BUILDING OR OCCUPANCY, EXCEPT
 AS OTHERWISE PROVIDED IN THIS CODE.
  
 9) PLEASE RESPOND TO PREVIOUS COMMENT. VALUE FOR WORK
 STATED ON PERMIT APPLICATION APPEARS LOW. PROVIDE A
 BREAKDOWN OF ALL MATERIALS AND LABOR, OR, AT YOUR
 DISCRETION, PROVIDE A SIGNED CONTRACTOR PROVIDE A
 REASONABLE VALUE. WPB F.B.C. 109.3
  
 FBC 109.3 THE APPLICANT FOR A PERMIT SHALL PROVIDE AN
 ESTIMATED PERMIT VALUE AT TIME OF APPLICATION. PERMIT
 VALUATIONS SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING
 MATERIALS AND LABOR, FOR WHICH THE PERMIT IS BEING
 ISSUED, SUCH AS ELECTRICAL, GAS, MECHANICAL, PLUMBING
 EQUIPMENT AND PERMANENT SYSTEMS. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE VALUATION IS UNDERESTIMATED
 ON THE APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS
 THE APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE
 APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING
 PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL
  
 10) PLEASE RESPOND TO PREVIOUS COMMENT. PLEASE INDICATE
 THE REQUIRED SIGN LIGHTING OUTLETS FOR EACH COMMERCIAL
 SPACE REQUIRED PER NEC 600.5(A)
  
 NEC 605(A) REQUIRED BRANCH CIRCUIT. EACH COMMERCIAL
 BUILDING AND EACH COMMERCIAL OCCUPANCY ACCESSIBLE TO
 PEDESTRIANS SHALL BE PROVIDED WITH AT LEAST ONE OUTLET
 IN AN ACCESSIBLE LOCATION AT EACH ENTRANCE TO EACH
 TENANT SPACE FOR SIGN OR OUTLINE LIGHTING SYSTEM USE.
 THE OUTLET(S) SHALL BE SUPPLIED BY A BRANCH CIRCUIT
 RATED AT LEAST 20 AMPERES THAT SUPPLIES NO OTHER LOAD.
 SERVICE HALLWAYS OR CORRIDORS SHALL NOT BE CONSIDERED
 ACCESSIBLE TO PEDESTRIANS.
  
 11) PLEASE RESPOND TO PREVIOUS COMMENT. PLEASE INDICATE
 COMPLIANCE WITH THE F.B.C.E.C. C405.2 FOR LIGHTING
 CONTROLS IN COMMERCIAL SPACES. FBCEC 405.2 LIGHTING
 CONTROLS MANDATORY
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-12-19 Cont ID  
Sent By mpeterso Date 2022-12-19 Time 13:27 Rev Time 0.00
Received By mpeterso Date 2022-12-19 Time 09:28 Sent To  
Notes
2022-12-19 13:29:17ELECTRIC REVIEW FAILED
 1) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
 2) PLEASE PROVIDE CLARITY AS TO RISER DIAGRAM
 INDICATING A HOUSE PANEL IS NOT METERED AND WITHOUT
 MAIN OVERCURRENT PROTECTION. NEC 215.5
 3) PLEASE PROVIDE CLARITY AS TO SERVICE RISER INDICATES
 A 400 AMP MAIN, (19) METERS/DISCONNECTS, HOUSE PANEL
 AND UNDERGROUND SERVICE WHEN PREVIOUS ELECTRICAL
 SERVICE, PERMITTED PREVIOUSLY ONLY INDICATES A 300 AMP
 SERVICE WITH (18) METERS AND DISCONNECTS. IF THIS IS
 NEW WORK PLEASE INDICATE ALL EXISTING ELECTRIC AND NEW
 PROPOSED ELECTRIC WORK TO BE DONE. FBC 107.2 AND NEC
 215.5
 4) PANEL SCHEDULES INDICATE SPLIT SYSTEM AIR
 CONDITIONING. PLEASE DETAIL THE OUTDOOR CONDENSER UNITS
 ON ELECTRIC FLOOR PLAN. FBC 107.2
 5) PLEASE INDICATE TYPE FIRE RESISTANCE RATING FOR
 BUILDING AND THE APPLICABLE WIRING METHODS TO BE USED.
 FBC 107.2
 6) PLEASE INDICATE VIA NOTE ON PLAN THAT FIRE ALARM AND
 OTHER LOW VOLTAGE SYSTEMS REQUIRE A SEPARATE PERMIT.
 7) PLEASE INDICATE APPLICABLE CIRCUITS TO COMPLY WITH
 NEC 210.12 ARC FAULT PROTECTION ON PANEL SCHEDULES AND
 FLOOR PLANS.
 8) PLEASE INDICATE COMPLIANCE WITH NEC 210.62 FOR SHOW
 WINDOW RECEPTACLES IN COMMERCIAL SPACES.
 9) PLEASE INDICATE THE REQUIRED SIGN LIGHTING OUTLETS
 REQUIRED PER NEC 600.5 FOR EACH COMMERCIAL SPACE
 10) PLEASE INDICATE COMPLIANCE WITH THE F.B.C.E.C.
 C405.2 FOR LIGHTING CONTROLS IN COMMERCIAL SPACES
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2023-07-10 Cont ID  
Sent By pleduc Date 2023-07-10 Time   Rev Time 0.00
Received By pleduc Date 2023-07-06 Time 15:49 Sent To  
Notes
2023-07-10 14:54:13THERE ARE NO INDICATIONS THAT THE PREVIOUS COMMENTS
 FROM FIRE WERE SPECIFICALY ADDRESSED AND ARE
 REUSUBMITTED BELOW:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF WORK INVOLVING A 2 STORY
 APARTMENT BUILDING OF 15 LIVING UNITS; HOWEVER, THERE
 IS NO INDICATIONS OF AN EXISTING OR NEW FIRE ALARM
 SYSTEMS.
  
 PER NFPA 101 CH 31 EXISTING APARTMENT BUILDINGS.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 PLEASE REVIEW AND PROVIDE PER THE REQUIREMENT.
  
  
 2) THE 2ND FLOOR MEANS OF EGRESS ARRANGEMENT DOES NOT
 APPEAR TO MEET THE MINIMUM REQUIREMENT ****40' IS
 INDICATED IN THE CORRIDOR
  
 31.2.5 ARRANGEMENT OF MEANS OF EGRESS
  
 31.2.5.3.1 NO COMMON PATH OF TRAVEL SHALL EXCEED 35 FT
 (10.7 M) IN
 BUILDINGS NOT PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH 31.3.5.
 TRAVEL WITHIN A
 DWELLING UNIT SHALL NOT BE INCLUDED WHEN CALCULATING
 COMMON PATH OF
 TRAVEL.
  
  
 3) ADDRESSED
  
  
  
 4) THERE ARE INDCATIIONS OF A FIRE ESCAPE STAIR WITH
 EXPOSURE TO WINDOWS
  
 31.2.2.9 FIRE ESCAPE STAIRS. FIRE ESCAPE STAIRS
 COMPLYING WITH 7.2.8
 SHALL BE PERMITTED
  
 7.2.8.2 PROTECTION OF OPENINGS. FIRE ESCAPE STAIRS
 SHALL BE EXPOSED
 TO THE SMALLEST POSSIBLE NUMBER OF WINDOW AND DOOR
 OPENINGS, AND EACH
 OPENING SHALL BE PROTECTED WITH APPROVED FIRE DOOR OR
 FIRE WINDOW ASSEM BLIES WHERE THE OPENING OR ANY
 PORTION OF THE OPENING IS LOCATED AS
 FOLLOWS:
 (1) HORIZONTALLY, WITHIN 15 FT (4570 MM) OF ANY
 BALCONY, PLATFORM, OR
 STAIRWAY CONSTITUTING A COMPONENT OF THE FIRE ESCAPE
 STAIR
 (2) BELOW, WITHIN THREE STORIES OR 36 FT (11 M) OF ANY
 BALCONY, PLATFORM,
 WALKWAY, OR STAIRWAY CONSTITUTING A COMPONENT OF THE
 FIRE ESCAPE
 STAIR, OR WITHIN TWO STORIES OR 24 FT (7320 MM) OF A
 PLATFORM OR
 WALKWAY LEADING FROM ANY STORY TO THE FIRE ESCAPE STAIR
 (3) ABOVE, WITHIN 10 FT (3050 MM) OF ANY BALCONY,
 PLATFORM, OR WALK WAY, AS MEASURED VERTICALLY, OR
 WITHIN 10 FT (3050 MM) OF ANY STAIR
 TREAD SURFACE, AS MEASURED VERTICALLY
 (4) FACING A COURT SERVED BY A FIRE ESCAPE STAIR, WHERE
 THE LEAST DIMEN SION OF THE COURT DOES NOT EXCEED
 ONE-THIRD OF THE HEIGHT TO THE
 UPPERMOST PLATFORM OF THE FIRE ESCAPE STAIR, MEASURED
 FROM THE
 FINISHED GROUND LEVEL
 (5) FACING AN ALCOVE SERVED BY A FIRE ESCAPE STAIR,
 WHERE THE WIDTH OF
 THE ALCOVE DOES NOT EXCEED ONE-THIRD, OR THE DEPTH OF
 THE ALCOVE
 DOES NOT EXCEED ONE-FOURTH, OF THE HEIGHT TO THE
 UPPERMOST PLATFORM
 OF THE FIRE ESCAPE STAIR, MEASURED FROM THE FINISHED
 GROUND LEVEL
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR THE REQUIREMENT.
  
  
 5) ON THE 1ST FLOOR MIDDLE BUSINESS SPACE THERE APPEARS
 TO BE A STORAGE UNDER THE EXIT STAIR.
  
 31.2.2.3.1 STAIRS. STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE SAME
 FIRE RESISTANCE AS THE EXIT ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE
 STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3)
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 6) ON THE 1ST FLOOR BUSINESSES, 2 OF THE BUSINESS STOCK
 ROOMS DO NOT HAVE EXIT SIGNS THAT WILL LEAD PEOPLE TO
 THAT DOOR TO EXIT INTO THE MAIN ARA.
  
 31.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS
 REQUIRING MORE
 THAN ONE EXIT
  
 7.10.1.2 EXITS.
  
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2023-02-24 Cont ID  
Sent By pleduc Date 2023-02-24 Time   Rev Time 0.00
Received By pleduc Date 2023-02-24 Time 12:24 Sent To  
Notes
2023-02-24 12:41:41SEVERAL OF THE PREVIOUS COMMENTS FROM FIRE DO NOT
 APPEAR TO BE ADDRESSES AND ARE REUSUBMITTED BELOW:
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF WORK INVOLVING A 2 STORY
 APARTMENT BUILDING OF 15 LIVING UNITS; HOWEVER, THERE
 IS NO INDICATIONS OF AN EXISTING OR NEW FIRE ALARM
 SYSTEMS.
  
 PER NFPA 101 CH 31 EXISTING APARTMENT BUILDINGS.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 PLEASE REVIEW AND PROVIDE PER THE REQUIREMENT.
  
  
 2) THE 2ND FLOOR MEANS OF EGRESS ARRANGEMENT DOES NOT
 APPEAR TO MEET THE MINIMUM REQUIREMENT ****40' IS
 INDICATED IN THE CORRIDOR
  
 31.2.5 ARRANGEMENT OF MEANS OF EGRESS
  
 31.2.5.3.1 NO COMMON PATH OF TRAVEL SHALL EXCEED 35 FT
 (10.7 M) IN
 BUILDINGS NOT PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH 31.3.5.
 TRAVEL WITHIN A
 DWELLING UNIT SHALL NOT BE INCLUDED WHEN CALCULATING
 COMMON PATH OF
 TRAVEL.
  
  
 3) ADDRESSED
  
  
  
 4) THERE ARE INDCATIIONS OF A FIRE ESCAPE STAIR WITH
 EXPOSURE TO WINDOWS
  
 31.2.2.9 FIRE ESCAPE STAIRS. FIRE ESCAPE STAIRS
 COMPLYING WITH 7.2.8
 SHALL BE PERMITTED
  
 7.2.8.2 PROTECTION OF OPENINGS. FIRE ESCAPE STAIRS
 SHALL BE EXPOSED
 TO THE SMALLEST POSSIBLE NUMBER OF WINDOW AND DOOR
 OPENINGS, AND EACH
 OPENING SHALL BE PROTECTED WITH APPROVED FIRE DOOR OR
 FIRE WINDOW ASSEM BLIES WHERE THE OPENING OR ANY
 PORTION OF THE OPENING IS LOCATED AS
 FOLLOWS:
 (1) HORIZONTALLY, WITHIN 15 FT (4570 MM) OF ANY
 BALCONY, PLATFORM, OR
 STAIRWAY CONSTITUTING A COMPONENT OF THE FIRE ESCAPE
 STAIR
 (2) BELOW, WITHIN THREE STORIES OR 36 FT (11 M) OF ANY
 BALCONY, PLATFORM,
 WALKWAY, OR STAIRWAY CONSTITUTING A COMPONENT OF THE
 FIRE ESCAPE
 STAIR, OR WITHIN TWO STORIES OR 24 FT (7320 MM) OF A
 PLATFORM OR
 WALKWAY LEADING FROM ANY STORY TO THE FIRE ESCAPE STAIR
 (3) ABOVE, WITHIN 10 FT (3050 MM) OF ANY BALCONY,
 PLATFORM, OR WALK WAY, AS MEASURED VERTICALLY, OR
 WITHIN 10 FT (3050 MM) OF ANY STAIR
 TREAD SURFACE, AS MEASURED VERTICALLY
 (4) FACING A COURT SERVED BY A FIRE ESCAPE STAIR, WHERE
 THE LEAST DIMEN SION OF THE COURT DOES NOT EXCEED
 ONE-THIRD OF THE HEIGHT TO THE
 UPPERMOST PLATFORM OF THE FIRE ESCAPE STAIR, MEASURED
 FROM THE
 FINISHED GROUND LEVEL
 (5) FACING AN ALCOVE SERVED BY A FIRE ESCAPE STAIR,
 WHERE THE WIDTH OF
 THE ALCOVE DOES NOT EXCEED ONE-THIRD, OR THE DEPTH OF
 THE ALCOVE
 DOES NOT EXCEED ONE-FOURTH, OF THE HEIGHT TO THE
 UPPERMOST PLATFORM
 OF THE FIRE ESCAPE STAIR, MEASURED FROM THE FINISHED
 GROUND LEVEL
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR THE REQUIREMENT.
  
  
 5) ON THE 1ST FLOOR MIDDLE BUSINESS SPACE THERE APPEARS
 TO BE A STORAGE UNDER THE EXIT STAIR.
  
 31.2.2.3.1 STAIRS. STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE SAME
 FIRE RESISTANCE AS THE EXIT ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE
 STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3)
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 6) ON THE 1ST FLOOR BUSINESSES, 2 OF THE BUSINESS STOCK
 ROOMS DO NOT HAVE EXIT SIGNS THAT WILL LEAD PEOPLE TO
 THAT DOOR TO EXIT INTO THE MAIN ARA.
  
 31.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS
 REQUIRING MORE
 THAN ONE EXIT
  
 7.10.1.2 EXITS.
  
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-11-21 Cont ID  
Sent By pleduc Date 2022-11-21 Time   Rev Time 0.00
Received By pleduc Date 2022-11-21 Time 12:13 Sent To  
Notes
2022-11-21 13:08:08THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF WORK INVOLVING A 2 STORY
 APARTMENT BUILDING OF 15 LIVING UNITS; HOWEVER, THERE
 IS NO INDICATIONS OF AN EXISTING OR NEW FIRE ALARM
 SYSTEMS.
  
 PER NFPA 101 CH 31 EXISTING APARTMENT BUILDINGS.
  
 31.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 31.3.4.1 GENERAL.
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH
 MORE THAN 11 DWELLING UNITS, OTHER THAN THOSE MEETING
 THE REQUIREMENTS
 OF 31.3.4.1.2, SHALL BE PROVIDED WITH A FIRE ALARM
 SYSTEM IN ACCORDANCE
 WITH SECTION 9.6, EXCEPT AS MODIFIED BY 31.3.4.2
 THROUGH 31.3.4.5.
  
 PLEASE REVIEW AND PROVIDE PER THE REQUIREMENT.
  
  
 2) THE 2ND FLOOR MEANS OF EGRESS ARRANGEMENT DOES NOT
 APPEAR TO MEET THE MINIMUM REQUIREMENT
  
 31.2.5 ARRANGEMENT OF MEANS OF EGRESS
  
 31.2.5.3.1 NO COMMON PATH OF TRAVEL SHALL EXCEED 35 FT
 (10.7 M) IN
 BUILDINGS NOT PROTECTED THROUGHOUT BY AN APPROVED,
 SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH 31.3.5.
 TRAVEL WITHIN A
 DWELLING UNIT SHALL NOT BE INCLUDED WHEN CALCULATING
 COMMON PATH OF
 TRAVEL.
  
  
 3) THE 2ND FLOOR EXIT EXTERIOR STAIR APPEAR TO LAND
 INTO AN FENCE ENCLOSED AREA WITH RESTRICTED EXITING
 CAPACITY AND A GATE.
  
 THERE IS NO INDICATION OF EXIT HARDWARE OR
 LOCKS/LATCHING THAT MEET THE MINIMUM REQUIRMENT FOR AN
 EXIT.
  
 31.2.2.2 DOORS
  
 31.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH
 30.2.2.2.2.1,
 30.2.2.2.2.2, 30.2.2.2.2.3, OR 31.2.2.2.2.4.
 31.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE
 LOCKED AGAINST
 EGRESS WHEN THE BUILDING IS OCCUPIED
  
  
  
 4) THERE ARE INDCATIIONS OF A FIRE ESCAPE STAIR WITH
 EXPOSURE TO TO WINDOWS
  
 31.2.2.9 FIRE ESCAPE STAIRS. FIRE ESCAPE STAIRS
 COMPLYING WITH 7.2.8
 SHALL BE PERMITTED
  
 7.2.8.2 PROTECTION OF OPENINGS. FIRE ESCAPE STAIRS
 SHALL BE EXPOSED
 TO THE SMALLEST POSSIBLE NUMBER OF WINDOW AND DOOR
 OPENINGS, AND EACH
 OPENING SHALL BE PROTECTED WITH APPROVED FIRE DOOR OR
 FIRE WINDOW ASSEM BLIES WHERE THE OPENING OR ANY
 PORTION OF THE OPENING IS LOCATED AS
 FOLLOWS:
 (1) HORIZONTALLY, WITHIN 15 FT (4570 MM) OF ANY
 BALCONY, PLATFORM, OR
 STAIRWAY CONSTITUTING A COMPONENT OF THE FIRE ESCAPE
 STAIR
 (2) BELOW, WITHIN THREE STORIES OR 36 FT (11 M) OF ANY
 BALCONY, PLATFORM,
 WALKWAY, OR STAIRWAY CONSTITUTING A COMPONENT OF THE
 FIRE ESCAPE
 STAIR, OR WITHIN TWO STORIES OR 24 FT (7320 MM) OF A
 PLATFORM OR
 WALKWAY LEADING FROM ANY STORY TO THE FIRE ESCAPE STAIR
 (3) ABOVE, WITHIN 10 FT (3050 MM) OF ANY BALCONY,
 PLATFORM, OR WALK WAY, AS MEASURED VERTICALLY, OR
 WITHIN 10 FT (3050 MM) OF ANY STAIR
 TREAD SURFACE, AS MEASURED VERTICALLY
 (4) FACING A COURT SERVED BY A FIRE ESCAPE STAIR, WHERE
 THE LEAST DIMEN SION OF THE COURT DOES NOT EXCEED
 ONE-THIRD OF THE HEIGHT TO THE
 UPPERMOST PLATFORM OF THE FIRE ESCAPE STAIR, MEASURED
 FROM THE
 FINISHED GROUND LEVEL
 (5) FACING AN ALCOVE SERVED BY A FIRE ESCAPE STAIR,
 WHERE THE WIDTH OF
 THE ALCOVE DOES NOT EXCEED ONE-THIRD, OR THE DEPTH OF
 THE ALCOVE
 DOES NOT EXCEED ONE-FOURTH, OF THE HEIGHT TO THE
 UPPERMOST PLATFORM
 OF THE FIRE ESCAPE STAIR, MEASURED FROM THE FINISHED
 GROUND LEVEL
  
 PLEASE REVIEW AND PROVIDE DETAILS FOR THE REQUIREMENT.
  
  
 5) ON THE 1ST FLOOR MIDDLE BUSINESS SPACE THERE APPEARS
 TO BE A STORAGE UNDER THE EXIT STAIR.
  
 31.2.2.3.1 STAIRS. STAIRS COMPLYING WITH 7.2.2 SHALL BE
 PERMITTED.
  
 7.2.2.5.3.2 ENCLOSED, USABLE SPACE SHALL BE PERMITTED
 UNDER STAIRS, PROVIDED THAT BOTH OF THE FOLLOWING
 CRITERIA ARE MET:
 (1) THE SPACE SHALL BE SEPARATED FROM THE STAIR
 ENCLOSURE BY THE SAME
 FIRE RESISTANCE AS THE EXIT ENCLOSURE.
 (2) ENTRANCE TO THE ENCLOSED, USABLE SPACE SHALL NOT BE
 FROM WITHIN THE
 STAIR ENCLOSURE. (SEE ALSO 7.1.3.2.3)
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 6) ON THE 1ST FLOOR BUSINESSES, 2 OF THE BUSINESS STOCK
 ROOMS DO NOT HAVE EXIT SIGNS THAT WILL LEAD PEOPLE TO
 THAT DOOR TO EXIT INTO THE MAIN ARA.
  
 31.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS
 REQUIRING MORE
 THAN ONE EXIT
  
 7.10.1.2 EXITS.
  
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 PLEASE REVIEW AND PROVIDE PRETECTION DETAILS.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2023-06-30 Cont ID  
Sent By rwbrown Date 2023-06-30 Time 12:33 Rev Time 0.00
Received By rwbrown Date 2023-06-30 Time 12:33 Sent To  
Notes
2023-06-30 12:33:17 
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2023-03-10 Cont ID  
Sent By rwbrown Date 2023-03-10 Time 05:59 Rev Time 0.00
Received By rwbrown Date 2023-03-10 Time 05:59 Sent To  
Notes
2023-03-10 05:59:202ND GAS REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.5 GAS PLANS NOT SHOWN.
 PLEASE SHOW GAS MODIFICTIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-12-08 Cont ID  
Sent By rwbrown Date 2022-12-08 Time 09:13 Rev Time 0.00
Received By rwbrown Date 2022-12-08 Time 09:13 Sent To  
Notes
2022-12-08 09:14:541ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.3.5.1.5 GAS PLANS NOT SHOWN.
 PLEASE SHOW GAS MODIFICTIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2023-07-25 Cont ID  
Sent By jleahy Date 2023-07-25 Time 12:13 Rev Time 0.00
Received By jleahy Date 2023-06-29 Time 08:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 12:29 Rev Time 0.00
Received By mpeterso Date 2023-02-23 Time 09:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2023-01-04 Cont ID  
Sent By lmarchan Date 2023-01-04 Time 09:52 Rev Time 0.00
Received By lmarchan Date 2022-11-18 Time 09:12 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-12-21 Cont ID  
Sent By jwitmer Date 2022-12-21 Time 08:20 Rev Time 0.00
Received By jwitmer Date 2022-12-14 Time 14:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2023-07-21 Cont ID  
Sent By cmontell Date 2023-07-21 Time 13:44 Rev Time 0.00
Received By cmontell Date 2023-07-21 Time 13:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2023-02-27 Cont ID  
Sent By medwards Date 2023-02-27 Time 17:12 Rev Time 0.00
Received By medwards Date 2023-02-27 Time 17:12 Sent To  
Notes
2023-02-27 17:14:232ND ATTEMPT:
  
 SHEET A-1 INDICATES MECHANICAL SHEETS M-1, M-2 AND M-3,
 THESE SHEETS WERE NOT SUBMITTED IN THIS SUBMITTAL.
 PLEASE SUBMIT A COMPLETE MECHANICAL DESIGN FOR THE
 SCOPE OF WORK BEING COMPLETED UNDER THIS PERMIT,
 INCLUDING MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC
 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-12-16 Cont ID  
Sent By medwards Date 2022-12-16 Time 08:28 Rev Time 0.00
Received By medwards Date 2022-12-16 Time 08:28 Sent To  
Notes
2022-12-16 08:28:39SHEET A-1 INDICATES MECHANICAL SHEETS M-1, M-2 AND M-3,
 THESE SHEETS WERE NOT SUBMITTED IN THIS SUBMITTAL.
 PLEASE SUBMIT A COMPLETE MECHANICAL DESIGN FOR THE
 SCOPE OF WORK BEING COMPLETED UNDER THIS PERMIT,
 INCLUDING MECHANICAL EQUIPMENT SIZING CALCULATIONS. FBC
 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2023-06-30 Cont ID  
Sent By rwbrown Date 2023-06-30 Time 12:31 Rev Time 0.00
Received By rwbrown Date 2023-06-30 Time 12:31 Sent To  
Notes
2023-06-30 12:31:343RD PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 912.1 - THERE IS ONE BATHROOM GROUP AT THE
 TOP OF THE PAGE AND ONE ON THE BOTTOM LEFT OF THE PAGE
 THAT IS NOT VENTED TO CODE. THE SHOWER AND WATER CLOSET
 ARE BOTH ON THE HIGH SIDE OF THE VENTED FIXTURE
 CONNECTION AND ARE NOT ALLOWED TO BE. ONLY ONE WET
 VENTED FIXTURE IS ALLOWED ON THE HIGH SIDE OF THE
 VENTED FIXTURE CONNECTION. EITHER CHANGE THE VENTING
 METHOD FROM WET VENT TO ANOTHER METHOD OR RECONFIGURE
 THE CONNECTIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2023-02-24 Cont ID  
Sent By rwbrown Date 2023-02-24 Time 07:41 Rev Time 0.00
Received By rwbrown Date 2023-02-24 Time 07:41 Sent To  
Notes
2023-02-24 07:44:152ND PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 PREVIOUS COMMENTS NOT ADDRESSED AND CHANGES NOT MADE
  
 1. 2020 FPC 912.1 - THERE IS ONE BATHROOM GROUP AT THE
 TOP OF THE PAGE AND ONE ON THE BOTTOM LEFT OF THE PAGE
 THAT IS NOT VENTED TO CODE. THE SHOWER AND WATER CLOSET
 ARE BOTH ON THE HIGH SIDE OF THE VENTED FIXTURE
 CONNECTION AND ARE NOT ALLOWED TO BE. ONLY ONE WET
 VENTED FIXTURE IS ALLOWED ON THE HIGH SIDE OF THE
 VENTED FIXTURE CONNECTION. EITHER CHANGE THE VENTING
 METHOD FROM WET VENT TO ANOTHER METHOD OR RECONFIGURE
 THE CONNECTIONS. THERE ARE SEVERAL BRANCHES THAT ARE
 NON-COMPLIANT. "SINKS" CANNOT WET VENT BATHROOM GROUP
 FIXTURES, ONLY "OTHER BATHROOM GROUP FIXTURES" CAN LIKE
 LAVATORIES.
  
 PLEASE RECONFIGURE THE ISORMETRIC DRAWING TO ADDRESS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-12-08 Cont ID  
Sent By rwbrown Date 2022-12-08 Time 08:48 Rev Time 0.00
Received By rwbrown Date 2022-12-08 Time 08:48 Sent To  
Notes
2022-12-08 09:13:151ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 912.1 - THERE IS ONE BATHROOM GROUP AT THE
 TOP OF THE PAGE AND ONE ON THE BOTTOM LEFT OF THE PAGE
 THAT IS NOT VENTED TO CODE. THE SHOWER AND WATER CLOSET
 ARE BOTH ON THE HIGH SIDE OF THE VENTED FIXTURE
 CONNECTION AND ARE NOT ALLOWED TO BE. ONLY ONE WET
 VENTED FIXTURE IS ALLOWED ON THE HIGH SIDE OF THE
 VENTED FIXTURE CONNECTION. EITHER CHANGE THE VENTING
 METHOD FROM WET VENT TO ANOTHER METHOD OR RECONFIGURE
 THE CONNECTIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2023-07-25 Cont ID  
Sent By jleahy Date 2023-07-25 Time 12:12 Rev Time 0.00
Received By jleahy Date 2023-07-25 Time 12:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2023-03-10 Cont ID  
Sent By mpeterso Date 2023-03-10 Time 12:29 Rev Time 0.00
Received By mpeterso Date 2023-03-10 Time 12:29 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-12-21 Cont ID  
Sent By jwitmer Date 2022-12-21 Time 08:25 Rev Time  
Received By jwitmer Date 2022-12-21 Time   Sent To  
Notes
2022-12-21 08:25:12ARCHITECT OR INTERIOR DECORATOR, DIGITAL SIGNING &
 SEALING PLANS. 61G1-16.005 PROCEDURES FOR DIGITALLY
 SIGNING AND SEALING AND FOR ELECTRONICALLY TRANSMITTING
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.

Review Stop Z ZONING
Rev No 3 Status P Date 2023-07-19 Cont ID  
Sent By llouie Date 2023-07-19 Time   Rev Time 0.00
Received By llouie Date 2023-07-19 Time   Sent To  
Notes
2023-07-19 14:56:50** INTERIOR MODIFICATIONS ONLY. ANY EXTERIOR WORK WILL
 REQUIRE SEPARATE PERMITS. **

Review Stop Z ZONING
Rev No 2 Status P Date 2023-03-03 Cont ID  
Sent By llouie Date 2023-03-03 Time   Rev Time 0.00
Received By llouie Date 2023-03-03 Time   Sent To  
Notes
2023-03-03 11:51:24** INTERIOR MODIFICATIONS ONLY. ANY EXTERIOR WORK WILL
 REQUIRE SEPARATE PERMITS. **
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-01-04 Cont ID  
Sent By llouie Date 2023-01-04 Time   Rev Time  
Received By llouie Date 2023-01-04 Time   Sent To  
Notes
2023-01-04 09:37:58REMODEL OF EXISTING INTERIOR SPACE ONLY. DOES NOT
 TRIGGER 50% THRESHOLD FOR LANDSCAPE IMPROVEMENTS.