Plan Review Details - Permit 22041024
Plan Review Stops For Permit 22041024
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-05-04 Cont ID  
Sent By cpuell Date 2022-05-04 Time 12:31 Rev Time 0.00
Received By cpuell Date 2022-05-04 Time 12:31 Sent To  
Notes
2022-05-04 12:32:26UPDATED ADDRESS

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-07 Cont ID  
Sent By ppetty Date 2022-06-07 Time 10:37 Rev Time 0.00
Received By ppetty Date 2022-06-07 Time 10:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-19 Cont ID  
Sent By ppetty Date 2022-05-19 Time 12:42 Rev Time 0.00
Received By ppetty Date 2022-05-19 Time 11:51 Sent To  
Notes
2022-05-19 12:44:41CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1.PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET
 OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE
 SIGNED AND SEALED BY A DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE
 CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 SINCERELY,
  
 PHIL PETTY
 CHIEF ELECTRICAL INSPECTOR , ELECTRICAL PLANS EXAMINER
  
 561-805-6742
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-23 Cont ID  
Sent By cwalker Date 2022-05-23 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
2022-05-23 10:56:54SEE PREVIOUS PROVISO COMMENTS

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-04 Cont ID  
Sent By cwalker Date 2022-05-04 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2022-05-04 10:39:42FIRE COMMENTS:
 (1) AFTER INSTALLATION COMPLETED, THE CONTRACTOR SHALL
 PROVIDE A SIGNED AND DATED RECORD OF COMPLETION.
 (2) A 24- HOUR BATTERY TEST WILL BE REQUIRED FOR THE
 FACP AND VERIFIED BY AN INSPECTOR FROM THE WEST PALM
 BEACH FIRE PREVENTION BUREAU.
 (3) WIRELESS MONITORING WILL BE VERIFIED BY AN
 INSPECTOR FROM THE WEST PALM BEACH FIRE PREVENTION
 BUREAU UNDER NORMAL POWER AND UNDER BATTERY POWER.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-07 Cont ID  
Sent By ppetty Date 2022-06-07 Time 10:38 Rev Time 0.00
Received By ppetty Date 2022-05-22 Time 15:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-19 Cont ID  
Sent By ppetty Date 2022-05-19 Time 12:45 Rev Time 0.00
Received By ppetty Date 2022-05-03 Time 07:12 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2022-05-17 Cont ID  
Sent By medwards Date 2022-05-17 Time 07:00 Rev Time 0.00
Received By medwards Date 2022-05-17 Time 07:00 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-05-19 Cont ID  
Sent By ppetty Date 2022-05-19 Time 12:44 Rev Time 0.00
Received By ppetty Date 2022-05-19 Time 12:44 Sent To  
Notes
***NONE***