Plan Review Details - Permit 22041012
Plan Review Stops For Permit 22041012
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-04-25 Cont ID  
Sent By cpuell Date 2022-04-25 Time 16:12 Rev Time 0.00
Received By cpuell Date 2022-04-25 Time 16:12 Sent To  
Notes
2022-04-25 16:12:42422 & 424 EL PRADO BOTH BEING REROODED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2022-04-20 Cont ID  
Sent By cpuell Date 2022-04-20 Time 09:03 Rev Time 0.00
Received By cpuell Date 2022-04-20 Time 09:03 Sent To  
Notes
2022-04-20 09:04:28TWO BUILDINGS ON PARCEL, 422 AND 424 EL PRADO WHICH
 BUILDING IS THE REROOF FOR? PLEASE RESPOND TO
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-05-19 Cont ID  
Sent By jbrooks Date 2022-05-19 Time 13:13 Rev Time 0.00
Received By jbrooks Date 2022-05-19 Time 08:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By jbrooks Date 2022-05-09 Time 11:05 Rev Time 0.00
Received By jbrooks Date 2022-05-09 Time 10:01 Sent To  
Notes
2022-05-09 11:05:55JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected].
  
 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 HAS BEEN REVISED TO FL16709-R10.
 PLEASE PROVIDE THE FOLLOWING: INCLUDE COVER PAGE,
 EVALUATION REPORT PAGES 1-4 AND INSTALLATION
 INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS
 AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE
 PRODUCT APPROVAL DRAWINGS.
 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R9 SELECTED SYSTEM NO W-5; EXPOSURE
 (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (20 < H < 30);
 ULTIMATE WIND SPEED (180), IS NOT CORRECT. THE CORRECT
 EXPOSURE FOR THE LISTED ADDRESS IS EXPOSURE C. THE
 ULTIMATE WIND SPEED FOR THE LISTED ADDRESS IS 170
 (MPH). PLEASE SELECT THE CORRECT OPTIONS.
 3. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL11698.6-R6 COVERS MULTIPLE INSTALLATION
 OPTIONS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT
 CORRECT INSTALLATION OPTION FROM PAGE #5 OF THE
 EVALUATION REPORT THAT MEET OR EXCEED THE MINIMUM
 DESIGN PRESSURE REQUIREMENT FOR ZONE 3 EXPOSURE
 CATEGORY C AREAS. (-133.1). ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-19 Cont ID  
Sent By jbrooks Date 2022-05-19 Time 13:13 Rev Time 0.00
Received By jbrooks Date 2022-05-11 Time 08:12 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-09 Cont ID  
Sent By jbrooks Date 2022-05-09 Time 11:06 Rev Time 0.00
Received By jbrooks Date 2022-05-06 Time 08:22 Sent To  
Notes
***NONE***