Plan Review Details - Permit 22040988
Plan Review Stops For Permit 22040988
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-08-19 Cont ID  
Sent By cthroop Date 2022-08-19 Time 07:13 Rev Time 0.00
Received By cthroop Date 2022-08-19 Time 07:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-07-07 Cont ID  
Sent By cthroop Date 2022-07-07 Time 07:54 Rev Time 0.00
Received By cthroop Date 2022-07-07 Time 07:49 Sent To  
Notes
2022-07-07 07:56:12PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE DETAIL FOR STRUCTURAL RE-INFORCING OF COLUMN
 PAD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE DETAIL FOR 4X4 STEEL POST TO COLUMN PAD.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-08-04 Cont ID  
Sent By mpeterso Date 2022-08-04 Time 14:19 Rev Time 0.00
Received By mpeterso Date 2022-08-04 Time 14:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-19 Cont ID  
Sent By mpeterso Date 2022-05-19 Time 13:38 Rev Time 0.00
Received By mpeterso Date 2022-05-19 Time 13:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-04-25 Cont ID  
Sent By mpeterso Date 2022-04-25 Time 08:29 Rev Time 0.00
Received By mpeterso Date 2022-04-25 Time 08:29 Sent To  
Notes
2022-04-25 08:30:59ELECTRIC REVIEW FAILED
 1) INCORRECT PLANS. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-04-26 Cont ID  
Sent By pleduc Date 2022-04-26 Time   Rev Time 0.00
Received By pleduc Date 2022-04-26 Time 11:41 Sent To  
Notes
2022-04-26 11:49:17FIRE PROVISO:
  
 A KNOX KEY SWITCH IS REQUIRED FOR 24HR
 EMERGENCY ACCESS FOR THE FIRE DEPARTMENT.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-04-22 Cont ID  
Sent By pleduc Date 2022-04-22 Time   Rev Time 0.00
Received By pleduc Date 2022-04-22 Time 11:41 Sent To  
Notes
2022-04-22 11:50:19THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN ADDRESS INDICATION ON THE APPLICATION OF
 205 N DIXIE HWY, HOWEVER, THE SINGLE PLAN SHEET
 SUBMITTAL INDICATES 300 PALM BEACH LAKES BLVD.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE CORRECT
 LOCATION AND CORRECT THE APPLICABLE DOCUMENT.
  
  
 2) THERE ARE NO DOCUMENT/MANUFACTURES SPEC SHEETS
 INDICATING THE PROPOSED GATES.
  
 PLEASE PROVIDE.
  
  
 2A) THERE ARE NO DOCUMENT/MANUFACTURES SPEC SHEETS
 INDICATING THE CARD READERS AND APPLICABLE ASSOCIATED
 EQUIPMENT..
  
 PLEASE PROVIDE.
  
  
 3) THERE IS AN INDICATION OF FIRE SPRINKLER HEAD
 RELOCATION DUE TO THE GATE INSTALLATIONS, HOWEVER,
 THERE IS NO INDICATION THAT THE FIRE SPRINKLER WORK
 SHALL BE SUBMITTED UNDER SEPARATE PERMIT AND DSHOP
 DRAWINGS.
  
 PLEASE PROVIDE THE APPLICABLE NOTE THAT THE FIRE
 SPRINKLER WORK SHALL BE SUBMITTED UNDER SEPARATE PERMIT
 AND DSHOP DRAWINGS.
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dbattles Date 2023-02-01 Time 13:52 Sent To  
Notes
2023-02-01 13:52:58ADDING MISSED ZONING REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-19 Cont ID  
Sent By cthroop Date 2022-08-19 Time 07:13 Rev Time 0.00
Received By cthroop Date 2022-07-29 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-07 Cont ID  
Sent By cthroop Date 2022-07-07 Time 07:56 Rev Time 0.00
Received By cthroop Date 2022-04-25 Time 14:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-25 Cont ID  
Sent By mpeterso Date 2022-04-25 Time 08:32 Rev Time 0.00
Received By mpeterso Date 2022-04-21 Time 06:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2022-05-19 Cont ID  
Sent By mpeterso Date 2022-05-19 Time 13:39 Rev Time 0.00
Received By mpeterso Date 2022-05-19 Time 13:39 Sent To  
Notes
2022-05-19 13:40:35CONTRACTOR PLANS NOT REQUIRED

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-04-25 Cont ID  
Sent By mpeterso Date 2022-04-25 Time 08:31 Rev Time 0.00
Received By mpeterso Date 2022-04-25 Time 08:31 Sent To  
Notes
2022-04-25 08:32:11SIGNATURE REVIEW FAILED
 1) INCORRECT PLANS FOR PROJECT. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop Z ZONING
Rev No 1 Status P Date 2023-02-08 Cont ID  
Sent By ajones Date 2023-02-08 Time 13:35 Rev Time 0.00
Received By ajones Date 2023-02-08 Time 13:35 Sent To  
Notes
***NONE***