Plan Review Details - Permit 22040897
Plan Review Stops For Permit 22040897
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-06-09 Cont ID  
Sent By pvalenti Date 2022-06-09 Time 05:49 Rev Time 0.00
Received By pvalenti Date 2022-06-09 Time 05:49 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-06-08 Cont ID  
Sent By pvalenti Date 2022-06-08 Time 14:50 Rev Time 0.00
Received By pvalenti Date 2022-06-08 Time 14:00 Sent To  
Notes
2022-06-08 14:57:29PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW APPROVED WITH PROVISO:
  
 OPERABLE OPENINGS (WINDOWS/DOORS) MUST BE AT 10' AWAY
 FROM EXHAUST TERMINATION OF GENERATOR AS PER FBC R
 303.5 OF THE FLORIDA BUILDING CODE (RESIDENTIAL).

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-25 Cont ID  
Sent By mpeterso Date 2022-04-25 Time 09:51 Rev Time 0.00
Received By mpeterso Date 2022-04-25 Time 09:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-09 Cont ID  
Sent By pvalenti Date 2022-06-09 Time 05:50 Rev Time 0.00
Received By pvalenti Date 2022-06-08 Time 16:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-08 Cont ID  
Sent By pvalenti Date 2022-06-08 Time 15:35 Rev Time 0.00
Received By pvalenti Date 2022-04-19 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-06-09 Cont ID  
Sent By pvalenti Date 2022-06-09 Time 05:50 Rev Time 0.00
Received By pvalenti Date 2022-06-09 Time 05:50 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-08 Cont ID  
Sent By pvalenti Date 2022-06-08 Time 14:57 Rev Time 0.00
Received By pvalenti Date 2022-06-08 Time 14:00 Sent To  
Notes
2022-06-08 15:35:03SIGNATURE REVIEW DENIED:
  
 THE SIGNED/SEALED PRECAST PAD SHEET, BY FRANK BENNARDO
 P.E., NEEDS TO HAVE THE SHEET AND DIGITAL SIGNATURE
 UPDATED AS NOTE STATES THAT THIS DOCUMENT IS ONLY VALID
 AT OTHER ZIP CODE (34994) AND THAT SIGNATURE IS ONLY
 VALID FOR 14 DAYS OF DIGITAL SIGNATURE.
  
  
 FS 471/FS 481 DOCUMENTS PREPARED BY AN
 ENGINEER/ARCHITECT AND SUBMITTED FOR PUBLIC RECORD ARE
 TO BE SIGNED, SEALED & DATED ORIGINALS. A SCAN OF A
 SIGNED/SEALED PLAN IS NOT CONSIDERED AN ORIGINAL.
 UPLOAD OR EMAIL A DIGITALLY SIGNED (THIRD PARTY
 VERIFIED) PLAN OR YOU CAN DELIVER AN ORIGINAL
 SIGNED/SEALED PAPER ORIGINAL TO:
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER II
 BUILDING DIVISION
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 FEEL FREE TO CONTACT ME AT 561 805 6673.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-26 Cont ID  
Sent By vbroglia Date 2022-04-26 Time 16:53 Rev Time 0.00
Received By vbroglia Date 2022-04-26 Time 16:53 Sent To  
Notes
***NONE***