Plan Review Details - Permit 22040888
Plan Review Stops For Permit 22040888
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2022-04-18 Cont ID  
Sent By cpuell Date 2022-04-18 Time 14:54 Rev Time 0.00
Received By cpuell Date 2022-04-18 Time 14:54 Sent To  
Notes
2022-04-18 14:54:41OWNER UPDATED
2022-04-18 09:22:30OWNER

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2022-05-12 Cont ID  
Sent By rmcphers Date 2022-05-12 Time 09:45 Rev Time 0.00
Received By rmcphers Date 2022-05-12 Time 09:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-26 Cont ID  
Sent By mpeterso Date 2022-05-26 Time 10:52 Rev Time 0.00
Received By mpeterso Date 2022-05-26 Time 10:52 Sent To  
Notes
2022-05-26 10:53:48ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE AN ELECTRIC RISER DIAGRAM AND
 UPSTREAM PANEL LOAD CALCULATIONS IF APPROPRIATE. NEC
 215.5
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rrossano Date 2022-05-09 Time   Rev Time 0.00
Received By rrossano Date 2022-05-09 Time   Sent To  
Notes
2022-05-09 08:55:20COMMENTS PER RICK ROSSANO, PROJ. COORDINATOR, ENG.
 SERVICES, [email protected]:
  
 ADDRESS ALL COMMENTS FROM PLUMBING AND PUBLIC
 UTILITIES.
  
 PROJECT ENGINEER SHOULD REACH OUT TO DEVELOPMENT
 SERVICES AND THE FDOH REGARDING ANY PERMIT REQUIREMENTS
 AND/COMPLIANCE AS PART OF THEIR DUE DILIGENCE.
  
  
 COMMENTS PER MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  
 -CANNOT USE HYDRANT METER WATER FOR TRAILER PLUMBING.
  
 -TRAILER MUST BE OUT OF UTILITY EASEMENTS.
  
 -PER WPB PLANNING DEPT., TRAILER MAY NOT BE CLOSE TO
 CLEARWATER FRONTAGE WITHOUT SCREENING.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2022-05-02 Cont ID  
Sent By cwalker Date 2022-05-02 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-02 Cont ID  
Sent By aoliver Date 2022-06-02 Time 09:52 Rev Time 0.00
Received By aoliver Date 2022-04-29 Time 07:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-06 Cont ID  
Sent By ccole Date 2022-05-05 Time 11:33 Rev Time 0.00
Received By ccole Date 2022-05-05 Time 11:32 Sent To  
Notes
2022-05-05 11:40:282ND PLUMBING REVIEW FBC-2020 PLUMBING
 PERMIT-22040888
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE PLUMBING SITE PLAN SHOWING THE POTABLE WATER
 CONNECTION TO THE HYDRANT METER IS CURRENTLY NOT
 APPROVED BY THE WPB UTILITES DEPARTMENT PER EMAIL FROM
 FIELD SERVICE SUPERVISOR MARK HURLEY. FINAL APPROVAL OF
 THE PLUMBING SITE PLAN REQUIRES APPROVAL BY THE WPB
 UTILITIES DEPT.
 2) THE PLAN SHALL BEAR THE SIGNATURE AND SEAL OF THE
 FL. LICENSED ENGINEER WHO PREPARED THE DRAWING, OR THE
 FL. LICENSED PLUMBING CONTRACTOR OF RECORD FOR THE
 PROJECT- FL. STATUTE 471.003(2)(H) & 471.025.
 3) A PLUMBING SUB-PERMIT APPLICATION IS REQUIRED- SEC.
 105.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
 1) FINAL APPROVAL OF THE PLUMBING SITE PLAN REQUIRES
 APPROVAL OF THE WPB UTILITIES DEPT.
 2) THE PLAN SHALL BEAR THE SIGNATURE AND SEAL OF THE
 FL. LICENSED ENGINEER WHO PREPARED THE DRAWING, OF THE
 FL. LICENSED PLUMBING CONTRACTOR OF RECORD FOR THE
 PROJECT- FL. STATUTE
 3) A PLUMBING SUB-PERMIT APPLICATION IS REQUIRED- SEC.
 105.1 WPB.

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-05-04 Cont ID  
Sent By ccole Date 2022-05-04 Time 17:34 Rev Time 0.00
Received By ccole Date 2022-05-04 Time 17:09 Sent To  
Notes
2022-05-04 17:35:031ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040888
 5/4/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE POTABLE WATER SERVICE LINE DETAILS FOR THE
 OFFICE TRAILER- SECS. 301.4 & 602.1 FBC P. PLEASE
 INCLUDE A SITE PLAN SHOWING THE LOCATIONS OF SERVICE
 LINE, POINT OF CONNECTION TO THE MAIN SERVICE LINE,
 WATER METER AND BACKFLOW PREVENTER. INDICATE THE TYPE
 AND SIZE OF WATER LINE AND BURIAL DEPTH- SEC. 605.3
 FBC.
  
 2) IN ACCORDANCE WITH SEC. E WPB UTILITIES CROSS
 CONNECTION MANUAL AN RPZ BACKFLOW PREVENTER FOR THE
 POTABLE WATER SERVICE LINE IS REQUIRED. THE
 INSTALLATION SHALL BE UNDER SEPARATE PERMIT- SEC. 105.1
 & 107.2.1 WPB.
  
 A FL. LICENSED PLUMBING CONTRACTOR SHALL OBTAIN A
 SEPARATE PERMIT FOR INSTALLATION OF THE BACKFLOW
 PREVENTERS IN ACCORDANCE WITH SECTION 105.1 WPB AND
 SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PU PUBLIC UTILITIES
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2022-06-02 Time   Rev Time 0.00
Received By   Date 2022-06-02 Time   Sent To  
Notes
2022-06-02 10:13:33SEE ENGINEERING COMMENTS
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-12 Cont ID  
Sent By rmcphers Date 2022-05-12 Time 09:46 Rev Time 0.00
Received By rmcphers Date 2022-05-12 Time 09:45 Sent To  
Notes
2022-05-12 09:48:22SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWING RS-1 DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE A VERIFIABLE ELECTRONIC OR DIGITAL SIGNATURE -
 YOU CAN DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-31 Cont ID  
Sent By ckimmerl Date 2022-05-31 Time 09:13 Rev Time 0.00
Received By ckimmerl Date 2022-05-31 Time 09:10 Sent To  
Notes
***NONE***