Plan Review Details - Permit 22040875
Plan Review Stops For Permit 22040875
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status P Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 14:18 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 12:43 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-03 Cont ID  
Sent By rbrown Date 2022-06-03 Time 11:13 Rev Time 0.00
Received By rbrown Date 2022-06-03 Time 11:13 Sent To  
Notes
2022-06-03 11:14:45ROOFING PRODUCT APPROVAL DEFERRAL STATEMENT ADDED TO
 SHEET A-4, ROOF PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 16:33 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 16:33 Sent To  
Notes
2022-06-01 16:35:41RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A-4 REVISION - MISSING FROM PROJECTDOX
 (DEFERRED ROOFING)

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 15:25 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 12:43 Sent To  
Notes
2022-05-09 15:25:30RENOVATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) NEW STAIR SHOULD SHOW HAND RAILS ON BOTH SIDES FBC
 1011.11 HANDRAILS.
 FLIGHTS OF STAIRWAYS SHALL HAVE HANDRAILS ON EACH SIDE
 AND SHALL COMPLY WITH SECTION 1014.
  
 2) PLEASE SHOW HAND RAIL DETAILS (ATTACHMENTS, HEIGHT
 ETC.) FBC 1014
  
 3) PLEASE SHOW STAIR RISER AND TREAD SIZES FBC 1011.5.2
  
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING - ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE DESIGNER OF RECORD FBC WPB 107.3.4
  
 5) PROJECT IS A SUBSTANTIAL IMPROVEMENT - A VARIANCE IS
 REQUIRED -- THE CONSTRUCTION BOARD OF ADJUSTMENT AND
 APPEALS GRANTS THE EXCEPTION TO THE FLOOD ELEVATION
 REQUIREMENT FOR HISTORIC PROPERTIES. - ORDINANCE NO.
 4729-17 SEC. 18-286 (D) HISTORIC BUILDINGS. A VARIANCE
 IS AUTHORIZED TO BE ISSUED FOR THE REPAIR, IMPROVEMENT,
 OR REHABILITATION OF A HISTORIC BUILDING THAT IS
 DETERMINED ELIGIBLE FOR THE EXCEPTION TO THE FLOOD
 RESISTANT CONSTRUCTION REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, EXISTING BUILDING, CHAPTER 12 HISTORIC
 BUILDINGS,
  
 6) ROOFING SYSTEM PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-06-02 Cont ID  
Sent By mpeterso Date 2022-06-02 Time 09:22 Rev Time 0.00
Received By mpeterso Date 2022-06-02 Time 09:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-05-18 Cont ID  
Sent By mpeterso Date 2022-05-18 Time 12:37 Rev Time 0.00
Received By mpeterso Date 2022-05-18 Time 11:38 Sent To  
Notes
2022-05-18 12:39:27ELECTRIC REVIEW FAILED
 1) PLEASE PROVIDE LOCATIONS FOR ALL EQUIPMENT ON SITE
 PLAN, INCLUDING TRANSFER SWITCH, PANEL HMP AND PANEL A.
 NEC 215.5 FBC 107.2
 2) PLEASE PROVIDE CLARITY AND NEC CODES DETAILING
 COMPLIANCE AS TO THE FEEDERS FOR PANELS HMP AND PANEL
 A, ARE THESE TAPS FROM THE 300-AMP TRANSFER SWITCH AND
 MAIN BREAKER AT THE GARAGE? NEC 215.5
 3) PLEASE PROVIDE GROUNDING ELECTRODE SYSTEM DETAIL AT
 MAIN HOUSE AS PER NEC 250.32
 4) PLEASE PROVIDE AN ACCURATE ELECTRIC FLOOR PLAN
 DETAILING WHICH ELECTRICAL WIRING IS TO REMAIN AND
 WHICH IS TO BE MODIFIED, REPAIRED OR ADDED. FBC 107.2
 5) PLEASE DETAIL SHEET E-3 AND E-4 AS ELECTRIC
 DEMOLITION, IF THAT IS WHAT THE DRAWING DEPICTS. IT
 APPEARS, AS PER NOTE ALL TERMINAL DEVICES, IE
 RECEPTACLES SWITCHES ETC. ARE TO BE REMOVED. PLEASE
 PROVIDE CLARITY IN NOTES AS TO WHETHER THE ELECTRIC
 WIRING TO THESE DEVICES IS TO REMAIN. NOTE 1 AND 3
 APPEAR REDUNDANT. FBC 107.2
 6) PLEASE PROVIDE CLARITY FOR NOTE 4 SHEET E-4. FBC
 107.2
 7) PLEASE PROVIDE CLARITY OF THE LIMITED SCOPE ON SHEET
 E-4. FBC 107.2
 8) PLEASE DETAIL CORRECT DISCONNECT LOCATIONS FOR ALL
 CU AIR CONDITIONING UNITS TO SHOW COMPLIANCE WITH NEC
 422.31(B)
 9) PLEASE DETAIL COMPLIANCE WITH MEETING/CONFERENCE
 ROOMS FLOOR AND WALL RECEPTACLES. NEC 210.71
 10) PLEASE PROVE DETAIL TO SHOW COMPLIANCE WITH NEC
 406.12 TAMPER RESISTANT RECEPTACLES
 11) PLEASE PROVIDE A NOTE THAT FIRE ALARM, LOW VOLTAGE,
 SIGNS AND GENERATORS REQUIRE A SEPARATE PERMIT.
  
 WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION
 CLOUDS AND A NUMBERED NARRATIVE RESPONSES TO THE ABOVE.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-06-03 Cont ID  
Sent By pleduc Date 2022-06-03 Time   Rev Time 0.00
Received By pleduc Date 2022-06-03 Time 10:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By pleduc Date 2022-05-27 Time   Rev Time 0.00
Received By pleduc Date 2022-05-27 Time 12:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2022-04-29 Cont ID  
Sent By pleduc Date 2022-04-29 Time   Rev Time 0.00
Received By pleduc Date 2022-04-28 Time 12:00 Sent To  
Notes
2022-04-28 12:32:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF EXIT SIGNS ALONG THE
 EXIT PATHS NOR EXITS.
  
 PER NFPA 101, CH 13 EXISTING ASSEMBY OCCUPANCIES AND CH
 7 MEANS OF EGRESS, THEY ARE REQUIRED:
  
 13.2.10 MARKING OF MEANS OF EGRESS.
 13.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS
 IN ACCORDANCE
 WITH SECTION 7.10
  
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN ACCOR DANCE WITH SECTION 7.10 WHERE REQUIRED
 IN CHAPTERS 11 THROUGH 4
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 PLEASE REVIEW AND CORRECT/PROVIDE.
  
  
 2) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING.
  
 13.2.9 EMERGENCY LIGHTING.
 13.2.9.1 EMERGENCY LIGHTING, OTHER THAN THAT PERMITTED
 BY 13.2.9.3,
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 7.9.
 13.2.9.2 PRIVATE PARTY TENTS NOT EXCEEDING 1200 FT2
 (112 M2
 ) SHALL NOT
 BE REQUIRED TO HAVE EMERGENCY LIGHTING.
 13.2.9.3 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD NOT
 EXCEEDING
 300 AND USED EXCLUSIVELY FOR A PLACE OF WORSHIP SHALL
 NOT BE REQUIRED TO
 HAVE EMERGENCY LIGHTING
  
 7.9 EMERGENCY LIGHTING
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN
 SECTION 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH
 THE FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLO SURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS IN
 ACCORDANCE
 WITH 7.2.1.6.2
  
 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL
 INCLUDE ONLY DES IGNATED STAIRS, AISLES, CORRIDORS,
 RAMPS, ESCALATORS, AND PASSAGEWAYS
 LEADING TO AN EXIT. FOR THE PURPOSES OF 7.9.1.1, EXIT
 DISCHARGE SHALL
 INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES,
 WALKWAYS, AND ESCALATORS
 LEADING TO A PUBLIC WAY
  
 PLEASE REVIEW AND CORRECT/PROVIDE.
  
  
  
 3) THERE ARE INDICATIONS OF THE INSTALLATION OF A FIRE
 ALARM SYSTEM.
  
 THE FIRE ALARM SYSTEM SHALL BE INSTALLED UNDER SEPARATE
 PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
 4) SHEET E 10, GENERAL NOTE # 2. DUCT DETECTORS SHALL
 BE INSTALLED PER NFPA 90A AND CAN INITIATE SUPERVISORY
 PER NFPA 72
  
 PER NFPA 90 A , CHAPTER 6 CONTROLS
 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL.
 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE
 TESTED AT LEAST ANNUALLY.
 6.4.2* LOCATION.
 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR
 DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS:
 (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY
 BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A
 CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN)
 (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON
 RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR
 INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A
 CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND
 SERVING MORE THAN ONE STORY
  
 PER NFPA 72
  
 PER NFPA 72, 2013 ED
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET
 THE REQUIREMENTS OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A
 CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION
 SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL.
 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM
 SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES,
 OR STANDARDS.
  
 PLEASE PROGRAM ACCORDINGLY FOR SUPERVISORY ACTIVATION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2022-05-13 Cont ID  
Sent By amhamilt Date 2022-05-13 Time 16:15 Rev Time 0.00
Received By amhamilt Date 2022-05-13 Time 16:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-03 Cont ID  
Sent By shill Date 2022-06-03 Time 12:03 Rev Time 0.00
Received By shill Date 2022-06-02 Time 14:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-06-02 Cont ID  
Sent By mpeterso Date 2022-06-02 Time 09:22 Rev Time 0.00
Received By mpeterso Date 2022-05-26 Time 15:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-18 Cont ID  
Sent By mpeterso Date 2022-05-18 Time 12:39 Rev Time 0.00
Received By mpeterso Date 2022-05-18 Time 12:39 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-27 Cont ID  
Sent By medwards Date 2022-05-27 Time 10:36 Rev Time 0.00
Received By medwards Date 2022-05-27 Time 10:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-05-05 Cont ID  
Sent By medwards Date 2022-05-05 Time 07:40 Rev Time 0.00
Received By medwards Date 2022-05-05 Time 07:40 Sent To  
Notes
2022-05-05 07:40:521ST REVIEW FMC
 PERMIT: 22040875
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FEC C403.2.1 AND FMC 312.1
  
 2) SHEET M-2: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS FOR THE NO. OF PEOPLE BASED OF TABLE
 403.3.1.1. THE CALCULATIONS APPEAR TO BE LOW FOR THE
 MUSEUM/GALLERIES AND THE CONFERENCE ROOM. FMC 403.3.1.1
  
 3) BECAUSE THIS DESIGN USED DX UNITS AND THE OAU UNIT
 PLEASE PROVIDE THE OUTDOOR AIR REQUIREMENTS FOR EACH
 ROOM NOT JUST A GENERAL GALLERY/MUSEUM FOR THE ENTIRE
 AREA. PLEASE SHOW HOW ADJOINING ROOMS WILL BE PROVIDED
 WITH THE REQUIRED OUTDOOR AIR I.E. THE FOYER AND EAST
 GALLERY DO NOT SHOW OUTDOOR AIR DUCTS. THE FOYER DOES
 SHOW DOORS THAT CAN SEPARATE IT FROM THE REST OF THE
 BUILDING. FMC 403.3.1.1
  
 4) SHEET M-10: PLEASE UPDATE THE CODE REFERENCES AS WE
 ARE CURRENTLY ENFORCING THE 2020 FMC. ALL REFERENCES
 SHOULD CALL FOR THE CURRENT EDITIONS REFERENCED IN THE
 2020 FMC.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 16:38 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 16:38 Sent To  
Notes
2022-06-01 16:39:56CBAA CASE NUMBER 1454

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 15:26 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 15:26 Sent To  
Notes
2022-05-09 15:37:29AE 6
 HISTORICAL EXEMPTION - NEED A VARIANCE

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-04-28 Cont ID  
Sent By ccole Date 2022-04-28 Time 13:23 Rev Time 0.00
Received By ccole Date 2022-04-28 Time 12:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-06-03 Cont ID  
Sent By rbrown Date 2022-06-03 Time 11:15 Rev Time 0.00
Received By rbrown Date 2022-06-03 Time 11:15 Sent To  
Notes
2022-06-03 11:15:22ROOFING PRODUCT APPROVAL DEFERRAL STATEMENT ADDED TO
 SHEET A-4, ROOF PLAN.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 16:38 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 16:38 Sent To  
Notes
2022-06-01 16:38:28SEE BLDG PLAN REVIEW

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 15:50 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 15:50 Sent To  
Notes
2022-05-09 15:51:05SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-06-03 Cont ID  
Sent By shill Date 2022-06-03 Time 12:02 Rev Time 0.00
Received By shill Date 2022-06-03 Time 12:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-01 Cont ID  
Sent By rmcphers Date 2022-06-01 Time 16:36 Rev Time 0.00
Received By rmcphers Date 2022-06-01 Time 16:36 Sent To  
Notes
2022-06-01 16:37:58SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS CVR, A-1, A-3, A-4, A-6, A-7 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).- OR - IF YOUR ARCHITECT,
 ENGINEER OR SURVEYOR DOES NOT HAVE A VERIFIABLE
 ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN DROP OFF THE
 ORIGINAL SIGNED AND SEALED DRAWINGS/DOCUMENTS TO THE
 FRONT DESK IN THE BUILDING DIVISION AT THE CITY HALL.
  
2022-05-27 10:38:09DIGITAL SIGNATURES FOR MECHANICAL APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-05-09 Cont ID  
Sent By rmcphers Date 2022-05-09 Time 15:47 Rev Time 0.00
Received By rmcphers Date 2022-05-09 Time 15:47 Sent To  
Notes
2022-05-09 15:48:41SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) THE ARCHITECTURAL AND PLUMBING DRAWINGS DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
2022-05-05 07:42:03DIGITAL SIGNATURES FOR MECHANICAL DOCUMENTS APPROVED ME

Review Stop Z ZONING
Rev No 2 Status P Date 2022-06-03 Cont ID  
Sent By amhamilt Date 2022-06-03 Time 11:02 Rev Time 0.00
Received By amhamilt Date 2022-06-03 Time 11:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-05-13 Cont ID  
Sent By amhamilt Date 2022-05-13 Time 16:16 Rev Time 0.00
Received By amhamilt Date 2022-05-13 Time 16:15 Sent To  
Notes
***NONE***