| 2022-04-28 12:32:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS OF EXIT SIGNS ALONG THE |
| | EXIT PATHS NOR EXITS. |
| | |
| | PER NFPA 101, CH 13 EXISTING ASSEMBY OCCUPANCIES AND CH |
| | 7 MEANS OF EGRESS, THEY ARE REQUIRED: |
| | |
| | 13.2.10 MARKING OF MEANS OF EGRESS. |
| | 13.2.10.1 MEANS OF EGRESS SHALL BE PROVIDED WITH SIGNS |
| | IN ACCORDANCE |
| | WITH SECTION 7.10 |
| | |
| | 7.10.1 GENERAL. |
| | 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE |
| | MARKED IN ACCOR DANCE WITH SECTION 7.10 WHERE REQUIRED |
| | IN CHAPTERS 11 THROUGH 4 |
| | |
| | 7.10.1.2 EXITS. |
| | 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS |
| | THAT OBVIOUSLY |
| | AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED |
| | BY AN APPROVED |
| | SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT |
| | ACCESS |
| | |
| | 7.10.1.5 EXIT ACCESS. |
| | 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| | READILY VISIBLE |
| | SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| | EXIT IS NOT READILY |
| | APPARENT TO THE OCCUPANTS |
| | |
| | PLEASE REVIEW AND CORRECT/PROVIDE. |
| | |
| | |
| | 2) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING. |
| | |
| | 13.2.9 EMERGENCY LIGHTING. |
| | 13.2.9.1 EMERGENCY LIGHTING, OTHER THAN THAT PERMITTED |
| | BY 13.2.9.3, |
| | SHALL BE PROVIDED IN ACCORDANCE WITH SECTION 7.9. |
| | 13.2.9.2 PRIVATE PARTY TENTS NOT EXCEEDING 1200 FT2 |
| | (112 M2 |
| | ) SHALL NOT |
| | BE REQUIRED TO HAVE EMERGENCY LIGHTING. |
| | 13.2.9.3 ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD NOT |
| | EXCEEDING |
| | 300 AND USED EXCLUSIVELY FOR A PLACE OF WORSHIP SHALL |
| | NOT BE REQUIRED TO |
| | HAVE EMERGENCY LIGHTING |
| | |
| | 7.9 EMERGENCY LIGHTING |
| | 7.9.1 GENERAL. |
| | 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF |
| | EGRESS SHALL BE |
| | PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE |
| | FOLLOWING: |
| | (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS |
| | 11 THROUGH 43 |
| | (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS |
| | ADDRESSED IN |
| | SECTION 11.7 |
| | (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS |
| | OF THIS CODE |
| | (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS |
| | (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF |
| | ENCLOSURES, FOR WHICH |
| | THE FOLLOWING ALSO APPLY: |
| | (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO |
| | INCLUDE A |
| | STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF |
| | ENCLO SURE MECHANICAL VENTILATION EQUIPMENT. |
| | (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED |
| | FOR THE |
| | STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER |
| | SUPPLY. |
| | (6) NEW SENSOR-RELEASE OF ELECTRICAL LOCKING SYSTEMS IN |
| | ACCORDANCE |
| | WITH 7.2.1.6.2 |
| | |
| | 7.9.1.2 FOR THE PURPOSES OF 7.9.1.1, EXIT ACCESS SHALL |
| | INCLUDE ONLY DES IGNATED STAIRS, AISLES, CORRIDORS, |
| | RAMPS, ESCALATORS, AND PASSAGEWAYS |
| | LEADING TO AN EXIT. FOR THE PURPOSES OF 7.9.1.1, EXIT |
| | DISCHARGE SHALL |
| | INCLUDE ONLY DESIGNATED STAIRS, RAMPS, AISLES, |
| | WALKWAYS, AND ESCALATORS |
| | LEADING TO A PUBLIC WAY |
| | |
| | PLEASE REVIEW AND CORRECT/PROVIDE. |
| | |
| | |
| | |
| | 3) THERE ARE INDICATIONS OF THE INSTALLATION OF A FIRE |
| | ALARM SYSTEM. |
| | |
| | THE FIRE ALARM SYSTEM SHALL BE INSTALLED UNDER SEPARATE |
| | PERMIT AND SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | 4) SHEET E 10, GENERAL NOTE # 2. DUCT DETECTORS SHALL |
| | BE INSTALLED PER NFPA 90A AND CAN INITIATE SUPERVISORY |
| | PER NFPA 72 |
| | |
| | PER NFPA 90 A , CHAPTER 6 CONTROLS |
| | 6.4* SMOKE DETECTION FOR AUTOMATIC CONTROL. |
| | 6.4.1 TESTING. ALL AUTOMATIC SHUTDOWN DEVICES SHALL BE |
| | TESTED AT LEAST ANNUALLY. |
| | 6.4.2* LOCATION. |
| | 6.4.2.1 SMOKE DETECTORS LISTED FOR USE IN AIR |
| | DISTRIBUTION SYSTEMS SHALL BE LOCATED AS FOLLOWS: |
| | (1) DOWNSTREAM OF THE AIR FILTERS AND AHEAD OF ANY |
| | BRANCH CONNECTIONS IN AIR SUPPLY SYSTEMS HAVING A |
| | CAPACITY GREATER THAN 944 L/SEC (2000 FT3/MIN) |
| | (2) AT EACH STORY PRIOR TO THE CONNECTION TO A COMMON |
| | RETURN AND PRIOR TO ANY RECIRCULATION OR FRESH AIR |
| | INLET CONNECTION IN AIR RETURN SYSTEMS HAVING A |
| | CAPACITY GREATER THAN 7080 L/SEC (15,000 FT3/MIN) AND |
| | SERVING MORE THAN ONE STORY |
| | |
| | PER NFPA 72 |
| | |
| | PER NFPA 72, 2013 ED |
| | 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS. |
| | 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO |
| | BE MONITORED AND A BUILDING FIRE ALARM SYSTEM IS |
| | INSTALLED, A DUCT DETECTOR ACTIVATION SIGNAL SHALL MEET |
| | THE REQUIREMENTS OF 21.7.4. |
| | 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC |
| | SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL. |
| | 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| | HVAC SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A |
| | CONSTANTLY ATTENDED LOCATION OR SUPERVISING STATION |
| | SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL. |
| | 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| | HVAC SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM |
| | SIGNAL WHERE REQUIRED BY OTHER GOVERNING LAWS, CODES, |
| | OR STANDARDS. |
| | |
| | PLEASE PROGRAM ACCORDINGLY FOR SUPERVISORY ACTIVATION. |
| | |
| | PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |