Plan Review Details - Permit 22040754
Plan Review Stops For Permit 22040754
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-07-26 Cont ID  
Sent By rmcdouga Date 2022-07-26 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2022-07-26 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-07-14 Cont ID  
Sent By rmcdouga Date 2022-07-14 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2022-07-14 Time 10:43 Sent To  
Notes
2022-07-14 11:23:47PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD ENGINEERING REQUIRES THE GENERATOR
 TO WEIGH 850 LBS. THE 20KW KOHLER GENERATOR ONLY WEIGHS
 555 LBS. SUBMIT THE ENGINEERING FOR THE GENERATOR PAD
 THAT IS FOR THIS GENERATOR. FBC 107.2.1
  
 2) SPECIFY THE SIZE AND LOCATIONS OF THE FASTENERS THAT
 ARE REQUIRED TO ANCHOR THE GENERATOR TO THE SLAB. FBC
 107.2.1
  
 3) SEE THE COMMENTS UNDER THE SIGNATURE REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 15:25 Rev Time 0.00
Received By rmcdouga Date 2022-06-22 Time 15:25 Sent To  
Notes
2022-06-22 15:28:07PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR EXHAUST IS REQUIRED TO BE AT LEAST 10
 FEET FROM ANY OPENINGS INTO A BUILDING. R303.5.1 INTAKE
 OPENINGS
 MECHANICAL AND GRAVITY OUTDOOR AIR INTAKE OPENINGS
 SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 MM) FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT, SUCH AS VENTS,
 CHIMNEYS, PLUMBING VENTS, STREETS, ALLEYS, PARKING LOTS
 AND LOADING DOCKS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 15:09 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-06-30 Cont ID  
Sent By mpeterso Date 2022-06-30 Time 13:02 Rev Time 0.00
Received By mpeterso Date 2022-06-30 Time 13:02 Sent To  
Notes
2022-06-30 13:05:41SEE SIGNATURE REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-04-25 Cont ID  
Sent By mpeterso Date 2022-04-25 Time 09:36 Rev Time 0.00
Received By mpeterso Date 2022-04-25 Time 09:36 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-06-27 Cont ID  
Sent By rwbrown Date 2022-06-27 Time 06:09 Rev Time 0.00
Received By rwbrown Date 2022-06-27 Time 06:09 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2022-04-27 Cont ID  
Sent By lcrespo Date 2022-04-27 Time 11:36 Rev Time 0.00
Received By lcrespo Date 2022-04-27 Time 11:36 Sent To  
Notes
2022-04-27 11:35:2404/27/22 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE CITY OF WEST PALM BEACH HAS A RECORD OF EXISTING
 LP TANK PERMITS BUT WITH NO INSPECTIONS FOR A PASS
 APPROVAL OF THE CURRENT SYSTEM. A SEARCH ON CITY
 RECORDS BACK TO 1995 HAS BEEN DONE AND THERE IS NO
 RECORD OF A PASSNG FOR THE INSTALLING AN LP TANK. A
 COMPLETE EVALUATION OF ALL GAS SYSTEMS AND EQUIPMENT
 MAY BE DONE ON THIS PERMIT BY THE PLUMBING INSPECTOR,
 AND IF NOT TO CODE, IT MAY NEED TO BE BOUT UP TO CODE
 COMPLIANCE AT THE OWNER'S EXPENSE. IF A PERMIT IS
 AVALABLE SHOWING A PASS OF THE SYSTEM THE REQUEST WILL
 NOT APPLY TO THIS PERMIT FOR COMPLIANCE. WHAT OTHER
 APPLIANCES/EQUIPMENT IS SUPPLIED BY THIS "EXISTING"
 TANK? PROVIDE ALL BTU LOADS AND THE TOTAL LOAD ON THE
 SYSTEM. IF THERE IS NO RECORD OF A PERMIT FOR THE LP
 TANK, THE TANK MUST BE INCLUDED IN A SEPARATE PERMIT
 FOR THIS SCOPE OF WORK PER THE WPB AMENDMENTS TO THE
 FBC S EC. 105.1.
  
 2. WOULD YOU PLEASE SHOW A SHUTOFF VALVE AND HARD CAP
 FOR FUTURE POOL HEATER 2020 FBC RES. SEC. G2401.1.3.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 WEST PALM BEACH AMENDMENTS 2017 FBC CHAPTER; UPON
 REQUEST.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-07-26 Cont ID  
Sent By rmcdouga Date 2022-07-26 Time 15:57 Rev Time 0.00
Received By rmcdouga Date 2022-07-21 Time 15:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-07-14 Cont ID  
Sent By rmcdouga Date 2022-07-14 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2022-06-24 Time 07:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2022-04-19 Time 09:22 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-06-27 Cont ID  
Sent By rwbrown Date 2022-06-27 Time 06:07 Rev Time 0.00
Received By rwbrown Date 2022-06-27 Time 06:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2022-04-27 Cont ID  
Sent By lcrespo Date 2022-04-27 Time 11:36 Rev Time 0.00
Received By lcrespo Date 2022-04-27 Time 11:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-07-25 Cont ID  
Sent By mpeterso Date 2022-07-25 Time 15:09 Rev Time 0.00
Received By mpeterso Date 2022-07-25 Time 15:09 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-06-30 Cont ID  
Sent By mpeterso Date 2022-06-30 Time 13:03 Rev Time 0.00
Received By mpeterso Date 2022-06-30 Time 13:03 Sent To  
Notes
2022-06-30 13:05:14SINGNATURE REVIEW FAILED
 PLAN FOR SLAB IS NOT DIGITALLY SIGNED AS REQUIRED
 FS471/FS481 DOCUMENTS PREPARED BY ARCHITECT/ENGINEER OF
 RECORD AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 DIGITALLY SEALED AND SIGNED.
 PLEASE SUBMIT DIGITALLY SEALED AND SIGNED PLANS
 FOLLOWING PROJECTDOX INSTRUCTIONS
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-06-22 Cont ID  
Sent By rmcdouga Date 2022-06-22 Time 15:28 Rev Time 0.00
Received By rmcdouga Date 2022-06-22 Time 15:28 Sent To  
Notes
2022-06-22 15:31:56THE ENGINEER'S DIGITAL SIGNATURE IS SELF-CERTIFIED. THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEER'S REQUIRES THE
 ENGINEER'S DIGAITAL SIGNATURE TO BE CERTIFIED BY A
 THIRD PARTY CERTIFICATION AGENCY. ELECTRONICALLY
 SUBMITTED DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT
 OR ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE
 THE OPTION TO SUBMIT THE SIGNED AND SEALED PAPER
 VERSION OF DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE
 BEEN APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 481 & FAC 61G1 OR FS 471 & FAC 61G15

Review Stop Z ZONING
Rev No 2 Status P Date 2022-07-06 Cont ID  
Sent By vbroglia Date 2022-07-06 Time 13:46 Rev Time 0.00
Received By vbroglia Date 2022-07-06 Time 13:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-04-26 Cont ID  
Sent By vbroglia Date 2022-04-26 Time 16:55 Rev Time 0.00
Received By vbroglia Date 2022-04-26 Time 16:55 Sent To  
Notes
2022-04-26 16:56:104/26/2022 FAILED
  
 PURSUANT TO SECTION 94-305(B)(4) OF THE ZLDR:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK. WINDOW AIR-CONDITIONING UNITS
 MAY NOT PROJECT MORE THAN 18 INCHES INTO A REQUIRED
 SIDE SETBACK.
  
 PLEASE PROVIDE A SITE PLAN THAT DEMONSTRATES THE
 PROPERTY LINES, LOCATION OF PROJECT AND DISTANCES FORM
 BOUNDARY LINES
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  