| Plan Review Stops For Permit 22040709 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-06-01 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-06-01 |
Time |
13:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-12 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-12 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2022-05-12 17:10:17 | WATER TREATMENT PLANT - RENOVATIONS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) DRAWING S-1 STRUCTURAL NOTE #2 SHOULD SHOW THE CODE | | | VERSION - 2020 FBC | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-30 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-30 |
Time |
11:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-06-09 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-09 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2022-06-09 15:02:36 | 22040709 | | | ELECTRIC REVIEW FAILED | | | 1) IT APPEARS SECONDARY CONDUCTORS FOR 15KVA | | | TRANSFORMERS ARE SIZED INCORRECTLY. SECONDARY COPPER | | | CONDUCTORS SIZED TO NOT LESS THAN THE SECONDARY | | | PROTECTION DEVICE RATING [240.21(C)] 75?C TERMINALS | | | [110.14(C)(1)(A)(2)] PER TABLE 310.15(B)(16). PLEASE | | | CORRECT AS APPLICABLE | | | 2) IT APPEARS PANEL BOARD FED FROM PANEL BOARD H4 VIA | | | 15 KVA TRANSFORMER DETAILS THE INCORRECT NOMENCLATURE | | | ?PANELBOARD A?, IT APPEARS THIS SHOULD BE LABELED | | | PANELBOARD D. PLEASE CORRECT AS APPLICABLE | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-05-05 |
|
|
Cont ID |
|
| Sent By |
cwalker |
Date |
2022-05-05 |
Time |
|
Rev Time |
|
| Received By |
cwalker |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-06-30 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-06-30 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-06-23 |
Time |
09:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-06-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-06-09 |
Time |
15:02 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-05-24 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2022-05-18 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2022-05-04 |
Time |
07:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-06-27 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-06-27 |
Time |
07:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2022-06-02 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-06-02 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-06-02 |
Time |
07:28 |
Sent To |
|
|
| Notes |
| 2022-06-02 11:32:27 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22040709 | | | 6/2/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS M1-M5: PROVIDE THE MAKE AND MODEL OF THE | | | BACKFLOW PREVENTERS- SEC. 608.3 FBC P. PLACE A NOTE | | | THAT THE DEVICES WILL BE INSTALLED UNDER A SEPARATE | | | PERMIT- SEC. 105.1 WPB. | | | | | | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR | | | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE | | | BACKFLOW PREVENTERS IN ACCORDANCE WITH SECTION 105.1 | | | WPB AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE | | | SHALL BE TESTED AND CERTIFIED BY THE WPB UTILITIES | | | DEPARTMENT PRIOR TO FINAL INSPECTION BY THE BUILDING | | | DEPARTMENT. PLEASE CONTACT THE WPB UTILITIES CENTRAL | | | OPERATIONS DEPT.AT 561-822-2210 FOR FURTHER | | | INFORMATION. | | | | | | 2) M1-M5: PROVIDE A SUMP DETAIL PIPING DETAIL AND AN | | | EQUIPMENT SCHEDULE- SECS. 712.2- 712.3.5 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-06-27 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-06-27 |
Time |
08:08 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-06-27 |
Time |
07:56 |
Sent To |
|
|
| Notes |
| 2022-06-27 08:10:22 | NEW SHEETS S-1 & E-8 APPROVED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-06-01 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-06-01 |
Time |
13:46 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-06-01 |
Time |
13:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2022-05-12 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-05-12 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-05-12 |
Time |
17:10 |
Sent To |
|
|
| Notes |
| 2022-05-12 17:11:27 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) ALL OF THE SIGNED AND SEALED DRAWINGS DO NOT SHOW AS | | | DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE A VERIFIABLE ELECTRONIC OR DIGITAL SIGNATURE - | | | YOU CAN DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2022-05-18 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2022-05-18 |
Time |
14:41 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2022-05-18 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|