Plan Review Details - Permit 22040674
Plan Review Stops For Permit 22040674
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-06-11 Cont ID  
Sent By shill Date 2022-06-11 Time 09:08 Rev Time 0.00
Received By shill Date 2022-06-11 Time 09:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-05-28 Cont ID  
Sent By shill Date 2022-05-28 Time 06:43 Rev Time 0.00
Received By shill Date 2022-05-28 Time 06:42 Sent To  
Notes
2022-05-28 06:46:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WIND DESIGN CRITERIA HAS BEEN CHANGED TO EXPOSURE C,
 BUT DESIGN PRESSURES PROPOSED ARE NOT CLEAR. DESIGN
 PRESSURES WHICH APPEAR TOO LOW ARE LISTED, THEN A
 STATEMENT ON THE PLAN "MULTIPLIER 1.21". DOES THAT MEAN
 THAT A MULTIPLIER OF 1.21 WAS APPLIED, OR YOU ARE
 PROPOSING THAT SOMEONE ELSE DO THE MATH TO STATE WHAT
 THE DESIGN PRESSURES ARE?
  
 YOU CAN STATE HOW YOU DERIVED THE DESIGN PRESSURES, BUT
 THE PRESSURES SHOULD BE DETERMINED BY THE INDIVIDUAL
 TAKING RESPONSIBILITY FOR THE DESIGN, FBC 107. REVISE
 SO REQUIRED DESIGN PRESSURES ARE CLEAR. IF THEY APPEAR
 TOO LOW, CALCULATIONS WILL BE REQUIRED.
  
 2. NEW COMMENT - ON THE ROOF PLAN, INCLUDE THE PRINTED
 NAME AND SIGNATURE OF THE INDIVIDUAL TAKING
 RESPONSIBILITY FOR THE DESIGN, FBC 107.
  
 3. NEW COMMENT - A NEW METAL ROOF NOA WAS UPLOADED.
 PLEASE COORDINATE WITH [email protected] TO
 REMOVE DOCUMENTS THAT YOU DO NOT WANT REVIEWED AND
 ISSUED, FBC 107.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-05-16 Cont ID  
Sent By shill Date 2022-05-16 Time 11:57 Rev Time 0.00
Received By shill Date 2022-05-16 Time 11:57 Sent To  
Notes
2022-05-16 11:57:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. THIS PROJECCT IS LOCATED IN EXPOSURE C, SEE FBC R
 301. ROOF PLAN STATES THIS IS EXPOSURE B.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-06-11 Cont ID  
Sent By shill Date 2022-06-11 Time 09:08 Rev Time 0.00
Received By shill Date 2022-05-31 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-28 Cont ID  
Sent By shill Date 2022-05-28 Time 06:56 Rev Time 0.00
Received By shill Date 2022-05-17 Time 18:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-05-16 Cont ID  
Sent By shill Date 2022-05-16 Time 11:58 Rev Time 0.00
Received By shill Date 2022-04-18 Time 10:28 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2022-06-11 Cont ID  
Sent By shill Date 2022-06-11 Time 09:08 Rev Time 0.00
Received By shill Date 2022-06-11 Time 09:08 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-05-28 Cont ID  
Sent By shill Date 2022-05-28 Time 06:54 Rev Time 0.00
Received By shill Date 2022-05-28 Time 06:53 Sent To  
Notes
2022-05-28 06:54:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FROM PREVIOUS LIST:
  
 1. FBC R 905.1.1, REVISE PLAN TO INDICATE WHICH METHOD
 WILL BE USED TO COMPLY WITH THIS SECTION.
  
 2ND REVIEW:
  
 NO NEW INFORMATION PROVIDED. REVISE THE ROOF PLAN TO
 CLARIFY WHICH OPTION IS PROPOSED. IF YOU WOULD LIKE A
 DOCUMENT THAT LISTS THE OPTIONS, SEND ME A EMAIL WITH
 THAT REQUEST.
  
 2. NEW COMMENT - FBC107, INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE ROOF DESIGN.
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-05-16 Cont ID  
Sent By shill Date 2022-05-16 Time 11:58 Rev Time 0.00
Received By shill Date 2022-05-16 Time 11:58 Sent To  
Notes
2022-05-16 12:01:49****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 901.1.1, REVISE PLAN TO INDICATE WHICH METHOD
 WILL BE USED TO COMPLY WITH THIS SECTION.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2022-05-16 Cont ID  
Sent By shill Date 2022-05-16 Time 11:58 Rev Time 0.00
Received By shill Date 2022-05-16 Time 11:58 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2022-04-22 Cont ID  
Sent By afowlkes Date 2022-04-22 Time 15:35 Rev Time 0.00
Received By afowlkes Date 2022-04-22 Time 15:35 Sent To  
Notes
2022-04-22 15:39:0804/22/22 PASSED
  
 ALEXANDER FOWLKES
 5618221431
 [email protected]